MainMenuBoolean
Warning!
Component applicable only for the LP panel.
The MainMenuBoolean component is responsible for reading/writing and configuration of a single Boolean parameter, which is placed in the LP panel main menu.
The MainMenuBoolean component has the following slots:
Status: shows the point’s status;
Fault Cause: shows the fault cause description;
Fault Status: shows the point error status (true: point read/write error);
Enable: enables or disables the point (true: enabled, false: disabled);
Poll Frequency: allows to set the reading poll frequency (fast, normal, slow);
Write Type: allows to set the writing mode (COV: only on the In slot change, COV_PollFrequency: on the In slot change and periodically, PollFrequency: only periodically, COV_LinkSet: only on the In slot change, using the "reverse following the link" function);
Trigger: allows to force sending values on rising edge;
Out: the main menu point output slot, the current value;
In: the main menu point input slot;
Point No: the panel’s main menu point number;
Point Display Name: allows to set the point display name on the LCD screen (up to 4, only ASCII characters);
Point Visibility: allows to activate or deactivate the point on the display;
Point True Text: allows to set the 4 characters LCD display text in the true state (only ASCII characters);
Point False Text: allows to set the 4 characters LCD display text in the false state (only ASCII characters);
Point Priority: allows to set the displaying priority on the LCD screen (starting from the lowest value);
Config Trigger: sends configuration parameters to the device components on rising edge.
The MainMenuBoolean component has the following right-click menu actions:
Set True: sets the true state in the In slot and sends it to the main menu point;
Set False: sets the false state in the In slot and sends it to the main menu point;
Write: sends the In slot state to the main menu point;
Read: reads the panel main menu point value and sets the Out slot;
Send Value: sends the point user value to the main menu without changing the In slot, from the pop-up window;
Read Config: reads the main menu point configuration parameters from the panel (Point Display Name, Point Visibility, Point True Text, Point False Text, Point Priority);
Write Config: writes the main menu point configuration parameters to the panel (Point Display Name, Point Visibility, Point True Text, Point False Text, Point Priority).