Skip to main content
Skip table of contents

MainMenuBoolean

Warning!

Component applicable only for the LP panel.

The MainMenuBoolean component is responsible for reading/writing and configuration of a single Boolean parameter, which is placed in the LP panel main menu.

88 MainMenuBoolean.png

MainMenuBoolean component

The MainMenuBoolean component has the following slots:

  • Status: shows the point’s status;

  • Fault Cause: shows the fault cause description;

  • Fault Status: shows the point error status (true: point read/write error);

  • Enable: enables or disables the point (true: enabled, false: disabled);

  • Poll Frequency: allows to set the reading poll frequency (fast, normal, slow);

  • Write Type: allows to set the writing mode (COV: only on the In slot change, COV_PollFrequency: on the In slot change and periodically, PollFrequency: only periodically, COV_LinkSet: only on the In slot change, using the "reverse following the link" function);

  • Trigger: allows to force sending values on rising edge;

  • Out: the main menu point output slot, the current value;

  • In: the main menu point input slot;

  • Point No: the panel’s main menu point number;

  • Point Display Name: allows to set the point display name on the LCD screen (up to 4, only ASCII characters);

  • Point Visibility: allows to activate or deactivate the point on the display;

  • Point True Text: allows to set the 4 characters LCD display text in the true state (only ASCII characters);

  • Point False Text: allows to set the 4 characters LCD display text in the false state (only ASCII characters);

  • Point Priority: allows to set the displaying priority on the LCD screen (starting from the lowest value);

  • Config Trigger: sends configuration parameters to the device components on rising edge.

The MainMenuBoolean component has the following right-click menu actions:

  • Set True: sets the true state in the In slot and sends it to the main menu point;

  • Set False: sets the false state in the In slot and sends it to the main menu point;

  • Write: sends the In slot state to the main menu point;

  • Read: reads the panel main menu point value and sets the Out slot;

  • Send Value: sends the point user value to the main menu without changing the In slot, from the pop-up window;

  • Read Config: reads the main menu point configuration parameters from the panel (Point Display Name, Point Visibility, Point True Text, Point False Text, Point Priority);

  • Write Config: writes the main menu point configuration parameters to the panel (Point Display Name, Point Visibility, Point True Text, Point False Text, Point Priority).

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.