Skip to main content
Skip table of contents

VAV Submenu

Note

This section applies only to the Control Point VAV series.

The VAV submenu is especially dedicated to operate with the VAV14-IP controller from iSMA CONTROLLI, allowing for locally configuring of the VAV application and balancing of the controller.

Note

Please note that all VAV configuration and points use BACnet communication.

App Configuration

In the Control Point panel’s VAV submenu dedicated to the VAV14-IP application, it is possible to configure the following parameters:

DEVT: allows to choose a device type between VAV and VVT;

  • VAV_DEVICE_TYPE:

    • Modbus register: 41817;

    • BACnet object: BO68, property: Present Value;

Register/object value

Value

0/false

VAV

1/true

VVT

Register/object values

REHT: allows to set a reheater type;

  • VAV_REHEATER_TYPE:

    • Modbus register: 41818;

    • BACnet object: MSV10, property: Present Value;

Register/object value

Value

1

None

2

Time proportional (PWM)

3

Staged

4

Float

Register/object values

PERT: allows to set a perimeter type;

  • VAV_PERIMETER_TYPE:

    • Modbus register: 41819;

    • BACnet object: MSV11, property: Present Value;

Register/object value

Value

1

None

2

Time proportional (PWM)

3

Digital

Register/object values

FANT: allows to set a fan type;

  • VAV_FAN_TYPE:

    • Modbus register: 41820;

    • BACnet object: MSV9, property: Present Value;

Register/object value

Value

1

None

2

Series

3

Parallel

Register/object values

SPCS: allows to set a source for temperature readings;

  • VAV_SPACE_TEMPERATURE_SOURCE:

    • Modbus register: 41831;

    • BACnet object: MSV15, property: Present Value;

Register/object value

Value

1

Panel

2

Input

3

Network

Register/object values

SPCT: allows to set a space temperature type on the universal input 2;

  • VAV_SPACE_TEMP_TYPE:

    • Modbus register: 41822;

    • BACnet object: MSV13, property: Present Value;

DIST: allows to set a discharge temperature type on the universal input 1;

  • VAV_DISCHARGE_TEMP_TYPE:

    • Modbus register: 41821;

    • BACnet object: MSV12, property: Present Value;

Register/object value

Value

1

Voltage measurement

2

Current

3

Resistance input

4

10K3A1 NTC

5

10K4A1 NTC

6

10K NTC Carel

7

20K6A1 NTC

8

2,2K3A1 NTC

9

3K3A1 NTC

10

30K6A1 NTC

11

SIE1

12

TAC1

13

SAT1

14

PT1000

15

NI1000

16

NI1000 21C

17

NI1000 LG F

18

10K Type2 NTC F

19

10K Type3 NTC F

20

20K NTC F

21

3K NTC F

22

PT1000 F

23

NI1000 32F

24

NI1000 70F

Register/object values

OFFS: allows to set a source for setpoint offset settings;

  • VAV_SETPOINT_OFFSET_SOURCE:

    • Modbus register: 41833;

    • BACnet object: MSV16, property: Present Value;

CO2S: allows to set a source for CO2 readings;

  • VAV_CO2_SOURCE:

    • Modbus register: 41832;

    • BACnet object: MSV17, property: Present Value;

Register/object value

Value

1

Panel

2

Input

3

Network

Register/object values

CO2R: allows to set a range for CO2 alarm settings;

  • VAV_CO2_RANGE:

    • Modbus register: 41823;

    • BACnet object: AO37, property: Present Value;

Register/object value

Value

Min.

0

Max.

10000

Register/object values

HPRI: allows to select a priority order for the heat source;

  • VAV_HEATER_PRIORITY:

    • Modbus register: 41825;

    • BACnet object: MSV14, property: Present Value;

Register/object value

Value

1

Reheater

2

Perimeter

3

Simultaneous

Register/object values

DUHT: allows to enable a possibility to use one or two heat sources;

  • VAV_DUAL_HEAT:

    • Modbus register: 41826;

    • BACnet object: BO69, property: Present Value;

Register/object value

Value

0/false

No

1/true

Yes

Register/object values

OCCT: allows to select an occupancy contact type;

  • VAV_OCCUPANCY_CONTACT_TYPE:

    • Modbus register: 41827;

    • BACnet object: BO66, property: Present Value;

WNDT: allows to select a window contact type;

  • VAV_WINDOW_CONTACT_TYPE:

    • Modbus register: 41828;

    • BACnet object: BO67, property: Present Value;

DAMP: allows to set a damper actuator’s direction to open to clockwise or counterclockwise;

  • VAV_DAMPER_DIRECTION:

    • Modbus register: 41830;

    • BACnet object: BO65, property: Present Value.

Register/object value

Value

0/false

Clockwise

1/true

Counterclockwise

Register/object values

Flow Settings

In the Control Point panel’s VAV submenu dedicated to airflow settings, it is possible to configure the following parameters:

MAXC: allows to set a maximum airflow value for cooling;

  • VAV_MAX_FLOW_COOLING:

    • Modbus register: 41801;

    • BACnet object: AO29, property: Present Value;

MINC: allows to set a minimum airflow value for cooling;

  • VAV_MIN_FLOW_COOLING:

    • Modbus register: 41802;

    • BACnet object: AO30, property: Present Value;

MAXH: allows to set a maximum airflow for heating;

  • VAV_MAX_FLOW_HEATING:

    • Modbus register: 41803;

    • BACnet object: AO31, property: Present Value;

MINH: allows to set a minimum airflow for heating;

  • VAV_MIN_FLOW_HEATING:

    • Modbus register: 41804;

    • BACnet object: AO32, property: Present Value;

STBY: allows to set a minimum airflow in a standby state;

  • VAV_MIN_FLOW_STANDBY:

    • Modbus register: 41805;

    • BACnet object: AO33, property: Present Value;

UNOC: allows to set a minimum airflow in an unoccupied state;

  • VAV_MIN_FLOW_UNOCCUPIED:

    • Modbus register: 41806;

    • BACnet object: AO34, property: Present Value;

FANS: allows to set a minimum airflow value for a fan to start operating;

  • VAV_FLOW_FAN_START:

    • Modbus register: 41807;

    • BACnet object: AO35, property: Present Value;

KFAC: allows to set a K-factor value according to the type of device for use in the airflow calculations;

  • VAV_K_FACTOR_VALUE:

    • Modbus register: 40288;

    • BACnet object: AO23, property: Present Value.

Balancing

KFAC: sets the K-factor value to the airflow calculations;

  • VAV_K_FACTOR_VALUE:

    • Modbus register: 40288;

    • BACnet object: AO23, property: Present Value;

FCAL: executes a calibration action according to a new maximum and/or minimum airflow value(s);

  • VAV_CALCULATED_FLOW:

    • Modbus register: 40290;

    • BACnet object: AO25, property: Present Value;

Note

If performing the balancing process based on the maximum airflow calibration, it is possible to skip the MINF action here.

Actions

MAXF

Performs a calibration action according to a new maximum airflow value

MINF (optional)

Performs a calibration action according to a new minimum airflow value

Actions
02 CP balancing.png

PRES: allows to set a differential pressure (initially displayed value measured by the VAV);

  • VAV_PRESSURE_SENSOR_VALUE:

    • Modbus register: 40287;

    • BACnet object: AO22, property: Present Value;

Note

If performing the balancing process based on the maximum and/or minimum airflow calibration, it is possible to skip the ZERO action here.

Action

ZERO:

  • VAV_PRESSURE_SENSOR_RESET_TRIGGER:

    • Modbus register: 40286;

    • BACnet object: BO64, property: Present Value;

Performs the pressure sensor zeroing action

Action
02a CP balancing - PRES.png

DAMP: allows to force an operating mode to a damper;

  • VAV_DAMPER_COMMAND:

    • Modbus register: 40291;

    • BACnet object: MSV5, property: Present Value;

Damper mode

Action

AUTO

Set auto mode (VAV application logic takes control)

MAXF

Go to a maximum airflow

MINF

Go to a minimum airflow

USRF

Go to a user-set airflow

USRP

Go to a user-set position (% of damper opening)

OPEN

Damper fully open

CLOS

Damper fully closed

CLBR

Performs a damper calibration (the damper goes to 100%, than to 0%, and goes back to the control loop output)

Damper modes
  • USER_DESIRED_DAMPER_POSITION: user-set opening level (after selecting the USRF opting in the VAV_DAMPER_COMMAND variable);

    • Modbus register: 40295;

    • BACnet object: AO26, property: Present Value;

  • USER_DESIRED_FLOW: user-set airflow setpoint (after selecting the USRP opting in the VAV_DAMPER_COMMAND variable);

    • Modbus register: 40296;

    • BACnet object: AO27, property: Present Value;

  • USER_MEASURED_FLOW: allows to enter the airflow value measured by the hood for calibration;

    • Modbus register: 40297;

    • BACnet object: AO28, property: Present Value;

02b CP balancing - MODE.png

FAN: allows to force an operating mode to a fan;

  • VAV_FAN_COMMAND:

    • Modbus register: 40292;

    • BACnet object: MSV6, property: Present Value;

Fan mode

Action

AUTO

Set an auto mode (VAV application logic takes control)

MAXS

Set a maximum fan speed

MINS

Set a minimum fan speed

STOP

Stop fan

Fan modes

REH: allows to force an operating mode to a reheater;

  • VAV_REHEATER_COMMAND:

    • Modbus register: 40293;

    • BACnet object: MSV7, property: Present Value;

Reheater mode

Action

AUTO

Set an auto mode (VAV application logic takes control)

OPEN

Fully open

CLOS

Fully closed

Reheater modes

PER: allows to force an operating mode to a perimeter;

  • VAV_PERIMETER_COMMAND:

    • Modbus register: 40294;

    • BACnet object: MSV8, property: Present Value;

Perimeter mode

Action

AUTO

Set an auto mode (VAV application logic takes control)

OPEN

Fully open

CLOS

Fully closed

Perimeter modes

Panel Access to the VAV Submenu

By default, access to the VAV submenu is hidden and password protected. In order to enter the VAV submenu:

  • long-press the OK button;

  • edit PIN (default: 0000);

  • short-press the OK button.

01 Entering VAV submenu.png

Panel access to the VAV submenu

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.