VAV Submenu
Note
This section applies only to the Control Point VAV series.
The VAV submenu is especially dedicated to operate with the VAV14-IP controller from iSMA CONTROLLI, allowing for locally configuring of the VAV application and balancing of the controller.
Note
Please note that all VAV configuration and points use BACnet communication.
App Configuration
In the Control Point panel’s VAV submenu dedicated to the VAV14-IP application, it is possible to configure the following parameters:
DEVT: allows to choose a device type between VAV and VVT;
VAV_DEVICE_TYPE:
Modbus register: 41817;
BACnet object: BO68, property: Present Value;
Register/object value | Value |
---|---|
0/false | VAV |
1/true | VVT |
REHT: allows to set a reheater type;
VAV_REHEATER_TYPE:
Modbus register: 41818;
BACnet object: MSV10, property: Present Value;
Register/object value | Value |
---|---|
1 | None |
2 | Time proportional (PWM) |
3 | Staged |
4 | Float |
PERT: allows to set a perimeter type;
VAV_PERIMETER_TYPE:
Modbus register: 41819;
BACnet object: MSV11, property: Present Value;
Register/object value | Value |
---|---|
1 | None |
2 | Time proportional (PWM) |
3 | Digital |
FANT: allows to set a fan type;
VAV_FAN_TYPE:
Modbus register: 41820;
BACnet object: MSV9, property: Present Value;
Register/object value | Value |
---|---|
1 | None |
2 | Series |
3 | Parallel |
SPCS: allows to set a source for temperature readings;
VAV_SPACE_TEMPERATURE_SOURCE:
Modbus register: 41831;
BACnet object: MSV15, property: Present Value;
Register/object value | Value |
---|---|
1 | Panel |
2 | Input |
3 | Network |
SPCT: allows to set a space temperature type on the universal input 2;
VAV_SPACE_TEMP_TYPE:
Modbus register: 41822;
BACnet object: MSV13, property: Present Value;
DIST: allows to set a discharge temperature type on the universal input 1;
VAV_DISCHARGE_TEMP_TYPE:
Modbus register: 41821;
BACnet object: MSV12, property: Present Value;
Register/object value | Value |
---|---|
1 | Voltage measurement |
2 | Current |
3 | Resistance input |
4 | 10K3A1 NTC |
5 | 10K4A1 NTC |
6 | 10K NTC Carel |
7 | 20K6A1 NTC |
8 | 2,2K3A1 NTC |
9 | 3K3A1 NTC |
10 | 30K6A1 NTC |
11 | SIE1 |
12 | TAC1 |
13 | SAT1 |
14 | PT1000 |
15 | NI1000 |
16 | NI1000 21C |
17 | NI1000 LG F |
18 | 10K Type2 NTC F |
19 | 10K Type3 NTC F |
20 | 20K NTC F |
21 | 3K NTC F |
22 | PT1000 F |
23 | NI1000 32F |
24 | NI1000 70F |
OFFS: allows to set a source for setpoint offset settings;
VAV_SETPOINT_OFFSET_SOURCE:
Modbus register: 41833;
BACnet object: MSV16, property: Present Value;
CO2S: allows to set a source for CO2 readings;
VAV_CO2_SOURCE:
Modbus register: 41832;
BACnet object: MSV17, property: Present Value;
Register/object value | Value |
---|---|
1 | Panel |
2 | Input |
3 | Network |
CO2R: allows to set a range for CO2 alarm settings;
VAV_CO2_RANGE:
Modbus register: 41823;
BACnet object: AO37, property: Present Value;
Register/object value | Value |
---|---|
Min. | 0 |
Max. | 10000 |
HPRI: allows to select a priority order for the heat source;
VAV_HEATER_PRIORITY:
Modbus register: 41825;
BACnet object: MSV14, property: Present Value;
Register/object value | Value |
---|---|
1 | Reheater |
2 | Perimeter |
3 | Simultaneous |
DUHT: allows to enable a possibility to use one or two heat sources;
VAV_DUAL_HEAT:
Modbus register: 41826;
BACnet object: BO69, property: Present Value;
Register/object value | Value |
---|---|
0/false | No |
1/true | Yes |
OCCT: allows to select an occupancy contact type;
VAV_OCCUPANCY_CONTACT_TYPE:
Modbus register: 41827;
BACnet object: BO66, property: Present Value;
WNDT: allows to select a window contact type;
VAV_WINDOW_CONTACT_TYPE:
Modbus register: 41828;
BACnet object: BO67, property: Present Value;
DAMP: allows to set a damper actuator’s direction to open to clockwise or counterclockwise;
VAV_DAMPER_DIRECTION:
Modbus register: 41830;
BACnet object: BO65, property: Present Value.
Register/object value | Value |
---|---|
0/false | Clockwise |
1/true | Counterclockwise |
Flow Settings
In the Control Point panel’s VAV submenu dedicated to airflow settings, it is possible to configure the following parameters:
MAXC: allows to set a maximum airflow value for cooling;
VAV_MAX_FLOW_COOLING:
Modbus register: 41801;
BACnet object: AO29, property: Present Value;
MINC: allows to set a minimum airflow value for cooling;
VAV_MIN_FLOW_COOLING:
Modbus register: 41802;
BACnet object: AO30, property: Present Value;
MAXH: allows to set a maximum airflow for heating;
VAV_MAX_FLOW_HEATING:
Modbus register: 41803;
BACnet object: AO31, property: Present Value;
MINH: allows to set a minimum airflow for heating;
VAV_MIN_FLOW_HEATING:
Modbus register: 41804;
BACnet object: AO32, property: Present Value;
STBY: allows to set a minimum airflow in a standby state;
VAV_MIN_FLOW_STANDBY:
Modbus register: 41805;
BACnet object: AO33, property: Present Value;
UNOC: allows to set a minimum airflow in an unoccupied state;
VAV_MIN_FLOW_UNOCCUPIED:
Modbus register: 41806;
BACnet object: AO34, property: Present Value;
FANS: allows to set a minimum airflow value for a fan to start operating;
VAV_FLOW_FAN_START:
Modbus register: 41807;
BACnet object: AO35, property: Present Value;
KFAC: allows to set a K-factor value according to the type of device for use in the airflow calculations;
VAV_K_FACTOR_VALUE:
Modbus register: 40288;
BACnet object: AO23, property: Present Value.
Balancing
KFAC: sets the K-factor value to the airflow calculations;
VAV_K_FACTOR_VALUE:
Modbus register: 40288;
BACnet object: AO23, property: Present Value;
FCAL: executes a calibration action according to a new maximum and/or minimum airflow value(s);
VAV_CALCULATED_FLOW:
Modbus register: 40290;
BACnet object: AO25, property: Present Value;
Note
If performing the balancing process based on the maximum airflow calibration, it is possible to skip the MINF action here.
Actions | |
---|---|
MAXF | Performs a calibration action according to a new maximum airflow value |
MINF (optional) | Performs a calibration action according to a new minimum airflow value |

PRES: allows to set a differential pressure (initially displayed value measured by the VAV);
VAV_PRESSURE_SENSOR_VALUE:
Modbus register: 40287;
BACnet object: AO22, property: Present Value;
Note
If performing the balancing process based on the maximum and/or minimum airflow calibration, it is possible to skip the ZERO action here.
Action | |
---|---|
ZERO:
| Performs the pressure sensor zeroing action |

DAMP: allows to force an operating mode to a damper;
VAV_DAMPER_COMMAND:
Modbus register: 40291;
BACnet object: MSV5, property: Present Value;
Damper mode | Action |
---|---|
AUTO | Set auto mode (VAV application logic takes control) |
MAXF | Go to a maximum airflow |
MINF | Go to a minimum airflow |
USRF | Go to a user-set airflow |
USRP | Go to a user-set position (% of damper opening) |
OPEN | Damper fully open |
CLOS | Damper fully closed |
CLBR | Performs a damper calibration (the damper goes to 100%, than to 0%, and goes back to the control loop output) |
USER_DESIRED_DAMPER_POSITION: user-set opening level (after selecting the USRF opting in the VAV_DAMPER_COMMAND variable);
Modbus register: 40295;
BACnet object: AO26, property: Present Value;
USER_DESIRED_FLOW: user-set airflow setpoint (after selecting the USRP opting in the VAV_DAMPER_COMMAND variable);
Modbus register: 40296;
BACnet object: AO27, property: Present Value;
USER_MEASURED_FLOW: allows to enter the airflow value measured by the hood for calibration;
Modbus register: 40297;
BACnet object: AO28, property: Present Value;

FAN: allows to force an operating mode to a fan;
VAV_FAN_COMMAND:
Modbus register: 40292;
BACnet object: MSV6, property: Present Value;
Fan mode | Action |
---|---|
AUTO | Set an auto mode (VAV application logic takes control) |
MAXS | Set a maximum fan speed |
MINS | Set a minimum fan speed |
STOP | Stop fan |
REH: allows to force an operating mode to a reheater;
VAV_REHEATER_COMMAND:
Modbus register: 40293;
BACnet object: MSV7, property: Present Value;
Reheater mode | Action |
---|---|
AUTO | Set an auto mode (VAV application logic takes control) |
OPEN | Fully open |
CLOS | Fully closed |
PER: allows to force an operating mode to a perimeter;
VAV_PERIMETER_COMMAND:
Modbus register: 40294;
BACnet object: MSV8, property: Present Value;
Perimeter mode | Action |
---|---|
AUTO | Set an auto mode (VAV application logic takes control) |
OPEN | Fully open |
CLOS | Fully closed |
Panel Access to the VAV Submenu
By default, access to the VAV submenu is hidden and password protected. In order to enter the VAV submenu:
long-press the OK button;
edit PIN (default: 0000);
short-press the OK button.

Panel access to the VAV submenu