Skip to main content
Skip table of contents

Setting

Setting the setpoint is possible from the main menu level.

If the room panel is in the active mode or the idle mode, pushing one of the arrow buttons leads to the setpoint edit mode.

OPERATING_MODE (BO 55)

OPERATING_MODE (BO 55) is True

If the setpoint is in the edit mode, its value, unit and name flashes with a frequency calculated according to the value stored in the SUBMENU­_ICON_FLASHING_TIME object.

Pushing the up arrow button increases the setpoint value by the step stored in the SETPOINT_STEP object.

If the entered value is higher than the value stored in the SETPOINT_HIGH_LIMIT object, the current setpoint value is overwritten by the value in that object.

Pushing the down arrow button decreases the setpoint value by the step stored in the SETPOINT_STEP object.

If the entered value is lower than the value stored in the SETPOINT_LOW_LIMIT object, the current setpoint value is overwritten by the value in that object.

OPERATING_MODE (BO 55) is False

If the OPERATING_MODE is false, the user changes the setpoint indirectly by changing the offset.

If the SETPOINT DISPLAY (BO 56) is false, then the OFFSET_SETPOINT is displayed.

If the offset is in the edit mode, its value, unit and name flashes with a frequency calculated according to the value stored in the SUBMENU_ICON_FLASHING_TIME object.

Pushing the up arrow button increases the OFFSET_SETPOINT value by the step stored in the SETPOINT_STEP object.

If the entered value is higher than the value stored in the OFFSET_RANGE object, the current OFFSET_SETPOINT value is overwritten by the value in that object.

Pushing the down arrow button decreases the OFFSET_SETPOINT value by the step stored in the SETPOINT_STEP object.

If the entered value is lower than the negative value of the OFFSET_RANGE object, the current OFFSET_SETPOINT value is overwritten by the value in that object.

If the SETPOINT_DISPLAY (BO 56) is true, the procedure is analogical, but instead of displaying the OFFSET_SETPOINT, and the offset name on the LCD display, the EFFECTIVE_SETPOINT with the SETPOINT_NAME is displayed.