Out-of-the-box device, as well as after restoring default values procedure, has the following default registers values:
|
Register Name |
Default Value |
|---|---|
|
USER BAUD RATE |
7680 (76800 bps) |
|
STOP BITS |
1 |
|
DATA BITS |
8 |
|
PARITY BITS |
0 |
|
RESPONSE DELAY |
0 |
|
USERNAME |
admin |
|
PASSWORD |
1000 |
|
IP ADDRESS |
192.168.1.123 |
|
MASK |
255.255.255.0 |
|
GATEWAY |
192.168.1.1 |
|
DHCP |
Disabled |
|
HTTP PORT |
80 |
|
MODBUS TCP PORT |
502 |
|
MODBUS TCP TIMEOUT |
60 s |
|
RS485 TIMEOUT |
500 ms |
|
SEND MODBUS ERRORS |
DISABLE |
|
MBUS BAUD RATE |
2400 |
|
MBUS TCP PORT |
6021 |
|
MBUS UDP PORT |
10002 |
|
MBUS RESPONSE TIMEOUT |
2000 ms |
|
RS485 BIASING RESISTORS |
Disabled |
Default values
Restoring Default Settings
To restore the default configuration of all registers, follow the steps below:
-
Turn off the power supply.
-
Set section 6 of the S3 switch to on.
-
Turn on the power supply, power LED is blinking.
-
Switch section 6 of the S3 switch to off to restore the default settings. To cancel the reset, turn off the power, and switch section 6 of S3 switch to the off position.