Default Settings
Out-of-the-box device, as well as after restoring default values procedure, has the following default registers values:
Register Name | Default Value |
---|---|
USER BAUD RATE | 7680 (76800 bps) |
STOP BITS | 1 |
DATA BITS | 8 |
PARITY BITS | 0 |
RESPONSE DELAY | 0 |
USERNAME | admin |
PASSWORD | 1000 |
IP ADDRESS | 192.168.1.123 |
MASK | 255.255.255.0 |
GATEWAY | 192.168.1.1 |
DHCP | Disabled |
HTTP PORT | 80 |
MODBUS TCP PORT | 502 |
MODBUS TCP TIMEOUT | 60 s |
RS485 TIMEOUT | 500 ms |
SEND MODBUS ERRORS | DISABLE |
MBUS BAUD RATE | 2400 |
MBUS TCP PORT | 6021 |
MBUS UDP PORT | 10002 |
MBUS RESPONSE TIMEOUT | 2000 ms |
RS485 BIASING RESISTORS | Disabled |
Restoring Default Settings
To restore the default configuration of all registers, follow the steps below:
- Turn off the power supply.
- Set section 6 of the S3 switch to on.
- Turn on the power supply, power LED is blinking.
- Switch section 6 of the S3 switch to off to restore the default settings. To cancel the reset, turn off the power, and switch section 6 of S3 switch to the off position.