RaiseLower
The RaiseLower component simplifies a control of 3-point valve actuators. This component has the following functions:
analog input, works with PID regulators;
2 digital outputs for 3-point direct control valve actuators;
analog output for 3-point control valve actuators by voltage level (additional device required);
midnight reset function to automatically adjust physical and virtual valve position.
The RaiseLower component has the following slots:
Function: the current function description (Lower_State, Static_State, Raise_State, Adjustment_Opening, Adjustment_Closing);
Virtual Position: shows the valve virtual position in %;
Out: the analog output slot;
Rise Out: the digital output for the rising function;
Rise Low: the digital output for the lowing function;
In: allows to set the valve position demand;
Full Open Time: allows to set the time for opening valve position from 0% to 100%;
Full Close Time: allows to set the time for closing valve position from 100% to 0%;
Adjustment Active: triggers the remote adjustment procedure;
Adjustment Period: allows to set the adjustment procedure recall period in hours;
Next Adjustment In: shows the time (in minutes) to the next adjustment procedure.
The RaiseLower component has the following action:
Adjust: valve adjustment procedure recall (adjusts physical and virtual valve position).
Out Value | Raise | Lower | Description |
---|---|---|---|
0 | Off | Off | Off |
4 | Off | On | Lower |
7 | Off | Off | Static |
10 | On | Off | Rise |