No. |
1 |
|---|---|
|
Sensor |
10K3A1
|
|
β coefficient |
3975K |
|
Manufacturers |
Aquatrol, Cylon, Honeywell, Johnson, Satchwell, Seachange |
|
°C |
Ω |
|
-50 |
667828 |
|
-45 |
491749 |
|
-40 |
335671 |
|
-35 |
241840 |
|
-30 |
176683 |
|
-25 |
131251 |
|
-20 |
96974 |
|
-15 |
72895 |
|
-10 |
55298 |
|
-5 |
42314 |
|
0 |
32650 |
|
5 |
25396 |
|
10 |
19904 |
|
15 |
15714 |
|
20 |
12494 |
|
25 |
10000 |
|
30 |
8056 |
|
35 |
6530 |
|
40 |
5325 |
|
45 |
4367 |
|
50 |
3601 |
|
55 |
2985 |
|
60 |
2487 |
|
65 |
2082 |
|
70 |
1751 |
|
75 |
1480 |
|
80 |
1256 |
|
85 |
1070 |
|
90 |
916 |
|
95 |
787 |
|
100 |
678 |
|
105 |
587 |
|
110 |
510 |
|
115 |
444 |
|
120 |
388 |
|
125 |
340 |
|
No. |
2 |
|---|---|
|
Sensor |
10K4A1
|
|
β coefficient |
3695K |
|
Manufacturers |
Andover, Delta Controls, Siebe, York |
|
°C |
Ω |
|
-50 |
441667 |
|
-45 |
330749 |
|
-40 |
239831 |
|
-35 |
181532 |
|
-30 |
135233 |
|
-25 |
105081 |
|
-20 |
78930 |
|
-15 |
61030 |
|
-10 |
47549 |
|
-5 |
37316 |
|
0 |
29490 |
|
5 |
23462 |
|
10 |
18787 |
|
15 |
15136 |
|
20 |
12268 |
|
25 |
10000 |
|
30 |
8197 |
|
35 |
6754 |
|
40 |
5594 |
|
45 |
4656 |
|
50 |
3893 |
|
55 |
3271 |
|
60 |
2760 |
|
65 |
2339 |
|
70 |
1990 |
|
75 |
1700 |
|
80 |
1458 |
|
85 |
1255 |
|
90 |
1084 |
|
95 |
939 |
|
100 |
817 |
|
105 |
713 |
|
110 |
624 |
|
115 |
547 |
|
120 |
482 |
|
125 |
426 |
|
No. |
3 |
|---|---|
|
Sensor |
10K Carel
|
|
β coefficient |
3435K |
|
°C |
Ω |
|
-50 |
329500 |
|
-45 |
247700 |
|
-40 |
188500 |
|
-35 |
144100 |
|
-30 |
111300 |
|
-25 |
86430 |
|
-20 |
67770 |
|
-15 |
53410 |
|
-10 |
42470 |
|
-5 |
33900 |
|
0 |
27280 |
|
5 |
22050 |
|
10 |
17960 |
|
15 |
14690 |
|
20 |
12090 |
|
25 |
10000 |
|
30 |
8313 |
|
35 |
6940 |
|
40 |
5827 |
|
45 |
4912 |
|
50 |
4161 |
|
55 |
3536 |
|
60 |
3020 |
|
65 |
2588 |
|
70 |
2228 |
|
75 |
1924 |
|
80 |
1668 |
|
85 |
1451 |
|
90 |
1266 |
|
95 |
1108 |
|
100 |
973 |
|
105 |
857 |
|
110 |
758 |
|
115 |
672 |
|
120 |
597 |
|
125 |
531 |
|
No. |
4 |
|---|---|
|
Sensor |
20K6A1
|
|
β coefficient |
4262K |
|
°C |
Ω |
|
-40 |
806800 |
|
-35 |
574400 |
|
-30 |
413400 |
|
-25 |
300400 |
|
-20 |
220600 |
|
-15 |
163480 |
|
-10 |
122260 |
|
-5 |
92220 |
|
0 |
70140 |
|
5 |
53780 |
|
10 |
41540 |
|
15 |
32340 |
|
20 |
25340 |
|
25 |
20000 |
|
30 |
15886 |
|
35 |
12698 |
|
40 |
10212 |
|
45 |
8260 |
|
50 |
6718 |
|
55 |
5494 |
|
60 |
4518 |
|
65 |
3732 |
|
70 |
3098 |
|
75 |
2586 |
|
80 |
2166 |
|
85 |
1823 |
|
90 |
1541 |
|
95 |
1308 |
|
100 |
1114 |
|
105 |
953 |
|
110 |
818 |
|
115 |
704 |
|
120 |
609 |
|
125 |
528 |
|
115 |
444 |
|
120 |
388 |
|
125 |
340 |
|
No. |
5 |
|---|---|
|
Sensor |
2.2K3A1
|
|
β coefficient |
3975K |
|
Manufacturers |
Ambiflex, Johnson |
|
°C |
Ω |
|
-50 |
150395 |
|
-45 |
112994 |
|
-40 |
75593 |
|
-35 |
57691 |
|
-30 |
39789 |
|
-25 |
30814 |
|
-20 |
21839 |
|
-15 |
16416 |
|
-10 |
12453 |
|
-5 |
9529 |
|
0 |
7353 |
|
5 |
5719 |
|
10 |
4482 |
|
15 |
3539 |
|
20 |
2814 |
|
25 |
2252 |
|
30 |
1814 |
|
35 |
1471 |
|
40 |
1199 |
|
45 |
983 |
|
50 |
810 |
|
55 |
672 |
|
60 |
560 |
|
65 |
468 |
|
70 |
394 |
|
75 |
333 |
|
80 |
282 |
|
85 |
241 |
|
90 |
206 |
|
95 |
177 |
|
100 |
152 |
|
105 |
132 |
|
110 |
114 |
|
115 |
100 |
|
120 |
88 |
|
125 |
77 |
|
No. |
6 |
|---|---|
|
Sensor |
3K3A1
|
|
β coefficient |
3975K |
|
Manufacturers |
Alerton |
|
°C |
Ω |
|
-50 |
200348 |
|
-45 |
150524 |
|
-40 |
100701 |
|
-35 |
76853 |
|
-30 |
53005 |
|
-25 |
41048 |
|
-20 |
29092 |
|
-15 |
21868 |
|
-10 |
16589 |
|
-5 |
12694 |
|
0 |
9795 |
|
5 |
7619 |
|
10 |
5971 |
|
15 |
4714 |
|
20 |
3748 |
|
25 |
3000 |
|
30 |
2417 |
|
35 |
1959 |
|
40 |
1598 |
|
45 |
1310 |
|
50 |
1080 |
|
55 |
896 |
|
60 |
746 |
|
65 |
625 |
|
70 |
526 |
|
75 |
444 |
|
80 |
377 |
|
85 |
321 |
|
90 |
275 |
|
95 |
236 |
|
100 |
204 |
|
105 |
176 |
|
110 |
153 |
|
115 |
133 |
|
120 |
117 |
|
125 |
102 |
|
No. |
7 |
|---|---|
|
Sensor |
30K6A1
|
|
β coefficient |
4262K |
|
Manufacturers |
Drayton |
|
°C |
Ω |
|
-30 |
622911 |
|
-25 |
477393 |
|
-20 |
331876 |
|
-15 |
245785 |
|
-10 |
183697 |
|
-5 |
138502 |
|
0 |
105305 |
|
5 |
80713 |
|
10 |
62347 |
|
15 |
48511 |
|
20 |
38019 |
|
25 |
30000 |
|
30 |
23828 |
|
35 |
19046 |
|
40 |
15317 |
|
45 |
12390 |
|
50 |
10079 |
|
55 |
8243 |
|
60 |
6777 |
|
65 |
5600 |
|
70 |
4650 |
|
75 |
3879 |
|
80 |
3251 |
|
85 |
2737 |
|
90 |
2313 |
|
95 |
1963 |
|
100 |
1672 |
|
105 |
1430 |
|
110 |
1228 |
|
115 |
1058 |
|
120 |
915 |
|
125 |
793 |
|
No. |
8 |
|---|---|
|
Sensor |
SIE1
|
|
Manufacturers |
Barber Colman, Siebe |
|
°C |
Ω |
|
-50 |
10732 |
|
-45 |
10624 |
|
-40 |
10517 |
|
-35 |
10344 |
|
-30 |
10172 |
|
-25 |
9913 |
|
-20 |
9654 |
|
-15 |
9320 |
|
-10 |
8933 |
|
-5 |
8496 |
|
0 |
8044 |
|
5 |
7489 |
|
10 |
6938 |
|
15 |
6370 |
|
20 |
5798 |
|
25 |
5238 |
|
30 |
4696 |
|
35 |
4185 |
|
40 |
3707 |
|
45 |
3271 |
|
50 |
2875 |
|
55 |
2521 |
|
60 |
2206 |
|
65 |
1929 |
|
70 |
1685 |
|
75 |
1472 |
|
80 |
1287 |
|
85 |
1127 |
|
90 |
986 |
|
95 |
866 |
|
100 |
760 |
|
105 |
670 |
|
110 |
590 |
|
115 |
522 |
|
120 |
462 |
|
125 |
410 |
|
No. |
9 |
|---|---|
|
Sensor |
TAC1
|
|
β coefficient |
3500K |
|
Manufacturers |
TAC |
|
°C |
Ω |
|
-40 |
39024 |
|
-35 |
29358 |
|
-30 |
22284 |
|
-25 |
17073 |
|
-20 |
13192 |
|
-15 |
10276 |
|
-10 |
8068 |
|
-5 |
6382 |
|
0 |
5085 |
|
5 |
4078 |
|
10 |
3294 |
|
15 |
2676 |
|
20 |
2188 |
|
25 |
1800 |
|
30 |
1488 |
|
35 |
1237 |
|
40 |
1034 |
|
45 |
869 |
|
50 |
733 |
|
55 |
622 |
|
60 |
529 |
|
65 |
453 |
|
70 |
389 |
|
75 |
335 |
|
80 |
290 |
|
85 |
252 |
|
90 |
220 |
|
95 |
192 |
|
100 |
169 |
|
105 |
149 |
|
110 |
131 |
|
115 |
116 |
|
120 |
103 |
|
125 |
92 |
|
No. |
10 |
|---|---|
|
Sensor |
SAT1
|
|
Manufacturers |
Satchwell |
|
°C |
Ω |
|
-50 |
9719 |
|
-45 |
9652 |
|
-40 |
9584 |
|
-35 |
9467 |
|
-30 |
9349 |
|
-25 |
9159 |
|
-20 |
8968 |
|
-15 |
8708 |
|
-10 |
8396 |
|
-5 |
8031 |
|
0 |
7614 |
|
5 |
7150 |
|
10 |
6649 |
|
15 |
6121 |
|
20 |
5580 |
|
25 |
5039 |
|
30 |
4513 |
|
35 |
4012 |
|
40 |
3545 |
|
45 |
3117 |
|
50 |
2730 |
|
55 |
2386 |
|
60 |
2082 |
|
65 |
1816 |
|
70 |
1585 |
|
75 |
1385 |
|
80 |
1213 |
|
85 |
1064 |
|
90 |
937 |
|
95 |
828 |
|
100 |
734 |
|
105 |
654 |
|
110 |
585 |
|
115 |
525 |
|
120 |
474 |
|
125 |
429 |
|
No. |
11 |
|---|---|
|
Sensor |
PT1000
|
|
Manufacturers |
Honeywell, Sauter, Serck, Siebe, Cylon |
|
°C |
Ω |
|
-50 |
803.1 |
|
-40 |
842.7 |
|
-30 |
882.2 |
|
-20 |
921.6 |
|
-10 |
960.9 |
|
0 |
1000.0 |
|
10 |
1039.0 |
|
20 |
1077.9 |
|
30 |
1116.7 |
|
40 |
1155.4 |
|
50 |
1194.0 |
|
60 |
1232.4 |
|
70 |
1270.8 |
|
80 |
1309.0 |
|
90 |
1347.1 |
|
100 |
1385.1 |
|
110 |
1422.9 |
|
120 |
1460.7 |
|
130 |
1498.3 |
|
140 |
1535.8 |
|
150 |
1573.3 |
|
160 |
1610.5 |
|
170 |
1647.7 |
|
180 |
1684.8 |
|
190 |
1721.7 |
|
200 |
1758.6 |
|
210 |
1795.3 |
|
220 |
1831.9 |
|
230 |
1868.4 |
|
240 |
1904.7 |
|
250 |
1941.0 |
|
260 |
1977.1 |
|
270 |
2013.1 |
|
280 |
2049.0 |
|
290 |
2084.8 |
|
300 |
2120.5 |
|
310 |
2156.1 |
|
320 |
2191.5 |
|
330 |
2226.8 |
|
340 |
2262.1 |
|
350 |
2297.2 |
|
360 |
2332.1 |
|
370 |
2367.0 |
|
380 |
2401.8 |
|
390 |
2436.4 |
|
400 |
2470.9 |
|
No. |
12 |
|---|---|
|
Sensor |
NI1000
|
|
Manufacturers |
Sauter |
|
°C |
Ω |
|
-50 |
742.6 |
|
-40 |
791.3 |
|
-30 |
841.5 |
|
-20 |
893.0 |
|
-10 |
945.8 |
|
0 |
1000.0 |
|
10 |
1055.5 |
|
20 |
1112.4 |
|
30 |
1170.6 |
|
40 |
1230.1 |
|
50 |
1291.1 |
|
60 |
1353.4 |
|
70 |
1417.2 |
|
80 |
1482.5 |
|
90 |
1549.4 |
|
100 |
1617.8 |
|
110 |
1687.9 |
|
120 |
1759.8 |
|
130 |
1833.4 |
|
140 |
1909.0 |
|
150 |
1986.6 |
|
No. |
13 |
|---|---|
|
Sensor |
NI1000 21C (ºC)
|
|
Manufacturers |
Distech |
|
°C |
Ω |
|
-40 |
699,3 |
|
-30 |
745,5 |
|
-20 |
792,8 |
|
-10 |
841,2 |
|
0 |
891,0 |
|
10 |
942,0 |
|
20 |
994,3 |
|
30 |
1047,8 |
|
40 |
1102,6 |
|
50 |
1158,5 |
|
60 |
1215,8 |
|
70 |
1274,3 |
|
80 |
1334,4 |
|
90 |
1407,8 |
|
100 |
1473,1 |
|
110 |
1524,0 |
|
No. |
14 |
|---|---|
|
Sensor |
NI1000 LG (ºC)
|
|
Manufacturers |
LG |
|
°C |
Ω |
|
-50 |
790,9 |
|
-40 |
830,8 |
|
-30 |
871,7 |
|
-20 |
913,5 |
|
-10 |
956,2 |
|
0 |
1000,0 |
|
10 |
1044,8 |
|
20 |
1090,7 |
|
30 |
1137,6 |
|
40 |
1185,7 |
|
50 |
1235,0 |
|
60 |
1285,4 |
|
70 |
1337,1 |
|
80 |
1390,1 |
|
90 |
1444,4 |
|
100 |
1500,0 |
|
110 |
1557,0 |
|
120 |
1615,4 |
|
130 |
1675,2 |
|
140 |
1736,5 |
|
150 |
1799,3 |
|
No. |
15 |
|---|---|
|
Sensor |
10K Type II NTC
|
|
β coefficient |
3975K |
|
Manufacturers |
Alerton |
|
°F |
Ω |
|
-40 |
336095 |
|
-35 |
279921 |
|
-30 |
233942 |
|
-25 |
196184 |
|
-20 |
165062 |
|
-15 |
139324 |
|
-10 |
117968 |
|
-5 |
100192 |
|
0 |
85346 |
|
5 |
72910 |
|
10 |
62464 |
|
15 |
53660 |
|
20 |
46222 |
|
25 |
39919 |
|
30 |
34563 |
|
35 |
30001 |
|
40 |
26104 |
|
45 |
22767 |
|
50 |
19903 |
|
55 |
17439 |
|
60 |
15313 |
|
65 |
13476 |
|
70 |
11884 |
|
75 |
10501 |
|
80 |
9298 |
|
85 |
8249 |
|
90 |
7333 |
|
95 |
6530 |
|
100 |
5826 |
|
105 |
5208 |
|
110 |
4663 |
|
115 |
4182 |
|
120 |
3757 |
|
125 |
3381 |
|
130 |
3047 |
|
135 |
2751 |
|
140 |
2487 |
|
145 |
2252 |
|
150 |
2042 |
|
155 |
1855 |
|
160 |
1687 |
|
165 |
1536 |
|
170 |
1401 |
|
175 |
1279 |
|
180 |
1169 |
|
185 |
1070 |
|
190 |
981 |
|
195 |
901 |
|
200 |
827 |
|
205 |
761 |
|
210 |
701 |
|
215 |
646 |
|
220 |
597 |
|
225 |
551 |
|
230 |
510 |
|
235 |
472 |
|
240 |
438 |
|
245 |
406 |
|
250 |
377 |
|
No. |
16 |
|---|---|
|
Sensor |
10K Type III NTC
|
|
β coefficient |
3695K |
|
Manufacturers |
Andowver |
|
°F |
Ω |
|
-40 |
239831 |
|
-35 |
203801 |
|
-30 |
173631 |
|
-25 |
148378 |
|
-20 |
127139 |
|
-15 |
109226 |
|
-10 |
94078 |
|
-5 |
81235 |
|
0 |
70317 |
|
5 |
61012 |
|
10 |
53063 |
|
15 |
46255 |
|
20 |
40411 |
|
25 |
35382 |
|
30 |
31046 |
|
35 |
27298 |
|
40 |
24051 |
|
45 |
21234 |
|
50 |
18782 |
|
55 |
16646 |
|
60 |
14780 |
|
65 |
13148 |
|
70 |
11717 |
|
75 |
10459 |
|
80 |
9353 |
|
85 |
8378 |
|
90 |
7517 |
|
95 |
6755 |
|
100 |
6080 |
|
105 |
5481 |
|
110 |
4948 |
|
115 |
4474 |
|
120 |
4051 |
|
125 |
3673 |
|
130 |
3335 |
|
135 |
3032 |
|
140 |
2761 |
|
145 |
2517 |
|
150 |
2297 |
|
155 |
2100 |
|
160 |
1921 |
|
165 |
1760 |
|
170 |
1615 |
|
175 |
1453 |
|
180 |
1363 |
|
185 |
1255 |
|
190 |
1156 |
|
195 |
1066 |
|
200 |
985 |
|
205 |
910 |
|
210 |
842 |
|
215 |
780 |
|
220 |
723 |
|
225 |
671 |
|
230 |
623 |
|
235 |
580 |
|
240 |
540 |
|
245 |
503 |
|
250 |
469 |
|
No. |
17 |
|---|---|
|
Sensor |
20K NTC
|
|
β coefficient |
4262K |
|
Manufacturers |
Honeywell |
|
°F |
Ω |
|
-40 |
817605 |
|
-35 |
674624 |
|
-30 |
558679 |
|
-25 |
464299 |
|
-20 |
387186 |
|
-15 |
323956 |
|
-10 |
271927 |
|
-5 |
228972 |
|
0 |
193390 |
|
5 |
163823 |
|
10 |
139177 |
|
15 |
118571 |
|
20 |
101293 |
|
25 |
86764 |
|
30 |
74511 |
|
35 |
64152 |
|
40 |
55369 |
|
45 |
47904 |
|
50 |
41543 |
|
55 |
36109 |
|
60 |
31457 |
|
65 |
27464 |
|
70 |
24029 |
|
75 |
21068 |
|
80 |
18509 |
|
85 |
16294 |
|
90 |
14372 |
|
95 |
12700 |
|
100 |
11244 |
|
105 |
9974 |
|
110 |
8862 |
|
115 |
7888 |
|
120 |
7034 |
|
125 |
6282 |
|
130 |
5620 |
|
135 |
5036 |
|
140 |
4519 |
|
145 |
4062 |
|
150 |
3657 |
|
155 |
3297 |
|
160 |
2976 |
|
165 |
2691 |
|
170 |
2436 |
|
175 |
2209 |
|
180 |
2005 |
|
185 |
1823 |
|
190 |
1659 |
|
195 |
1512 |
|
200 |
1379 |
|
205 |
1260 |
|
210 |
1153 |
|
215 |
1055 |
|
220 |
967 |
|
225 |
888 |
|
230 |
816 |
|
235 |
750 |
|
240 |
691 |
|
245 |
637 |
|
250 |
588 |
|
No. |
18 |
|---|---|
|
Sensor |
3K NTC
|
|
β coefficient |
3975K |
|
°F |
Ω |
|
-40 |
100618 |
|
-35 |
83827 |
|
-30 |
70079 |
|
-25 |
58783 |
|
-20 |
49468 |
|
-15 |
41763 |
|
-10 |
35367 |
|
-5 |
30042 |
|
0 |
25593 |
|
5 |
21866 |
|
10 |
18735 |
|
15 |
16096 |
|
20 |
13865 |
|
25 |
11975 |
|
30 |
10369 |
|
35 |
9000 |
|
40 |
7831 |
|
45 |
6830 |
|
50 |
5971 |
|
55 |
5232 |
|
60 |
4594 |
|
65 |
4043 |
|
70 |
3565 |
|
75 |
3150 |
|
80 |
2789 |
|
85 |
2475 |
|
90 |
2200 |
|
95 |
1959 |
|
100 |
1748 |
|
105 |
1562 |
|
110 |
1399 |
|
115 |
1254 |
|
120 |
1127 |
|
125 |
1014 |
|
130 |
914 |
|
135 |
825 |
|
140 |
746 |
|
145 |
676 |
|
150 |
613 |
|
155 |
556 |
|
160 |
506 |
|
165 |
461 |
|
170 |
420 |
|
175 |
384 |
|
180 |
351 |
|
185 |
321 |
|
190 |
294 |
|
195 |
270 |
|
200 |
248 |
|
205 |
228 |
|
210 |
210 |
|
215 |
194 |
|
220 |
179 |
|
225 |
165 |
|
230 |
153 |
|
235 |
142 |
|
240 |
131 |
|
245 |
122 |
|
250 |
113 |
|
No. |
19 |
|---|---|
|
Sensor |
NI1000 32F (ºF)
|
|
Manufacturers |
Distech |
|
°F |
Ω |
|
-40 |
791,3 |
|
-30 |
818,9 |
|
-20 |
847,1 |
|
-10 |
875,6 |
|
0 |
904,6 |
|
10 |
933,9 |
|
20 |
963,7 |
|
30 |
993,9 |
|
40 |
1024,5 |
|
50 |
1055,5 |
|
60 |
1086,9 |
|
70 |
1118,7 |
|
80 |
1151,0 |
|
90 |
1183,6 |
|
100 |
1216,7 |
|
110 |
1250,2 |
|
120 |
1284,1 |
|
130 |
1318,5 |
|
140 |
1353,4 |
|
150 |
1388,5 |
|
160 |
1424,2 |
|
170 |
1460,3 |
|
180 |
1497,0 |
|
190 |
1534,1 |
|
200 |
1571,7 |
|
210 |
1609,8 |
|
220 |
1648,4 |
|
230 |
1687,9 |
|
240 |
1727,3 |
|
250 |
1767,6 |
|
No. |
20 |
|---|---|
|
Sensor |
NI1000 70F (ºF)
|
|
Manufacturers |
Distech |
|
°F |
Ω |
|
-40 |
699,3 |
|
-30 |
724,8 |
|
-20 |
750,7 |
|
-10 |
776,9 |
|
0 |
803,4 |
|
10 |
830,3 |
|
20 |
857,7 |
|
30 |
885,4 |
|
40 |
913,5 |
|
50 |
942,0 |
|
60 |
970,9 |
|
70 |
1000,2 |
|
80 |
1029,9 |
|
90 |
1059,9 |
|
100 |
1090,3 |
|
110 |
1121,1 |
|
120 |
1152,2 |
|
130 |
1183,8 |
|
140 |
1215,8 |
|
150 |
1248,1 |
|
160 |
1280,9 |
|
170 |
1314,2 |
|
180 |
1347,9 |
|
190 |
1382,0 |
|
200 |
1417,0 |
|
210 |
1452,0 |
|
220 |
1487,0 |
|
230 |
1524,0 |
|
240 |
1560,0 |
|
250 |
1597,0 |
|
No. |
21 |
|---|---|
|
Sensor |
PT1000 (ºF)
|
|
Manufacturers |
Distech |
|
°F |
Ω |
|
-40 |
842,7 |
|
-30 |
864,7 |
|
-20 |
886,6 |
|
-10 |
908,5 |
|
0 |
930,3 |
|
10 |
952,2 |
|
20 |
973,9 |
|
30 |
995,7 |
|
40 |
1017,4 |
|
50 |
1039,0 |
|
60 |
1060,7 |
|
70 |
1082,2 |
|
80 |
1103,8 |
|
90 |
1125,3 |
|
100 |
1146,8 |
|
110 |
1168,3 |
|
120 |
1189,7 |
|
130 |
1211,1 |
|
140 |
1232,4 |
|
150 |
1253,7 |
|
160 |
1275,0 |
|
170 |
1296,2 |
|
180 |
1317,4 |
|
190 |
1338,6 |
|
200 |
1359,7 |
|
210 |
1380,8 |
|
220 |
1401,8 |
|
230 |
1422,9 |
|
240 |
1443,8 |
|
250 |
1464,8 |