Power supply |
Voltage |
24 V AC/DC ± 20% |
||
|---|---|---|---|---|
|
Power consumption |
||||
|
Module type |
At 24 V DC |
At 24 V AC |
||
|
8I |
0.4 W |
0.6 VA |
||
|
8I-IP |
1.4 W |
2.1 VA |
||
|
8U |
0.5 W |
0.8 VA |
||
|
8U-IP |
1.5 W |
2.3 VA |
||
|
4I4O-H |
1.2 W |
1.8 VA |
||
|
4I4O-H-IP |
2.2 W |
3.3 VA |
||
|
4U4O-H |
1.2 W |
1.8 VA |
||
|
4U4O-H-IP |
2.2 W |
3.3 VA |
||
|
4U4A-H |
2.2 W |
3.3 VA |
||
|
4U4A-H-IP |
3.2 W |
4.8 VA |
||
|
4O-H |
1.6 W |
2.4 VA |
||
|
4O-H-IP |
2.6 W |
3.9 VA |
||
|
4TO-H |
1.0 W |
1.5 VA |
||
|
4TO-H-IP |
2.0 W |
3.0 VA |
||
|
MIX18 |
3.0 W |
4.5 VA |
||
|
MIX18-IP |
4.4 W |
6.6 VA |
||
|
MIX38 |
5.0 W |
7.5 VA |
||
|
MIX38-IP |
7.4 W |
11.1 VA |
||
|
12O-H |
3.4 W |
9 VA |
||
|
12O-H-IP |
4.5 W |
11.7 VA |
||
|
24I |
1 W |
3.2 VA |
||
|
24I-IP |
2.1 W |
6.2 VA |
||
|
Universal Inputs |
Temperature input |
Measurement with attached RTDs (resistance temperature detectors) Accuracy ± 0.1˚C For PT1000 and NI1000 sensors use 16-bit resolution |
||
|
Voltage input |
Voltage measurement in 0-10 V DC range Input impedance 100 kΩ Measurement accuracy ±0.1% Measurement resolution 3 mV at 12-bit and 1 mV at 16-bit |
|||
|
Current input |
Current measurement in 0 - 20 mA range Required external resistor 200 Ω Measurement accuracy ±1.1% Measurement resolution 15 µA at 12-bit and 5 µA at 16-bit |
|||
|
Resistive input |
Measurement of resistance in 0 to 1000 kΩ range Measurement resolution for 20 kΩ load 20 Ω at 12-bit and 1 Ω at 16-bit Measurement resolution for PT1000 and NI1000 0.1 Ω at 16-bit |
|||
|
Resistance measurement method |
Voltage divider |
|||
|
Dry contact input |
Output current ~1 mA |
|||
|
Measurement resolution |
12-bit (default) or 16-bits |
|||
|
Processing time |
10 ms/channel at 12-bits 140 ms/channel at 16-bits |
|||
|
Digital Inputs |
Type |
Dry contact |
||
|
Max. input frequency |
100 Hz saved in EEPROM memory |
|||
|
Analog Outputs |
Voltage range |
0-10 V DC |
||
|
Max. load current |
20 mA, total 60 mA load current for all outputs for MIX18, MIX18-IP, MIX38, MIX38-IP modules |
|||
|
Resolution |
12-bit |
|||
|
Accuracy |
± 0.5% |
|||
|
Digital Outputs (relays) |
Contact material |
AgSnO2 |
||
|
|
UL compliant ratings |
Maximum ratings |
||
|
Resistive load AC1 |
3 A at 24 V AC 3 A at 30 V DC |
3 A at 230 V AC 3 A at 30 V DC |
||
|
Inductive load AC3 |
8 VA at 24 V AC 30 W at 30 V DC |
75 VA at 230 V AC 30 W at 30 V DC |
||
|
Capacitive load |
|
50 W at LED + PS 230 VAC 100 W at fluorescent lamps with electronic ballast 75 W at CFL Compact fluorescent lamp |
||
|
Digital Outputs (relays) 4O-H and 4O-H-IP
|
Contact material |
AgSnO2 |
||
|
|
UL compliant ratings |
Maximum ratings |
||
|
Resistive load AC1 |
8 A at 230 V AC 8 A at 30 V DC |
8 A at 230 V AC 8 A at 30 V DC |
||
|
Inductive load AC3 |
37 VA at 230 V AC 90 W at 30 V DC |
360 VA at 230 V AC 90 W at 30 V DC |
||
|
Capacitive load |
|
180 W at CFL Compact fluorescent lamp 120 W at LED + PS 230 V AC 240 W at fluorescent lamps with electronic ballast |
||
|
Digital Outputs (relays) 12O-H and 12O-H-IP |
Contact material |
AgSnO2 |
||
|
Resistive load AC1 |
3 A at 230 V AC 3 A at 30 V DC |
|||
|
Inductive load AC3 |
75 VA at 230 V AC 30 W at 30 V DC |
|||
|
Capacitive load |
50 W at LED + PS 230 VAC 100 W at fluorescent lamps with electronic ballast 75 W at CFL Compact fluorescent lamp |
|||
|
Triac Outputs |
Continuous load per channel |
0.5 A at 20 V AC up to max. 250 V AC |
||
|
Peak load per channel |
1.5 A at 20 V AC up to max. 250 V AC (30 s) |
|||
|
Gate Control |
Zero crossing turn ON |
|||
|
Frequency Range |
47 to 63 Hz |
|||
|
Snubber |
Snubberless triac |
|||
|
RS485 Interface |
RS485 |
Up to 128 devices |
||
|
Communication protocols |
Modbus RTU, Modbus ASCII, or BACnet set by switch |
|||
|
Baud rate |
From 2400 to 115200 set by switch |
|||
|
Address |
0 to 99 set by switch |
|||
|
Ethernet |
MIX18-IP, MIX38-IP, 12O-H-IP, 24I-IP |
|||
|
Fast Ethernet |
Switch mode (2 RJ45 ports) |
|||
|
Baud rate |
10/100 Mb/s |
|||
|
8I-IP, 8U-IP, 4I4O-H-IP, 4U4O-H-IP, 4U4A-H-IP, 4O-H-IP, 4TO-H-IP |
||||
|
Fast Ethernet |
IP interface |
|||
|
Baud rate |
10/100 Mb/s |
|||
|
USB |
USB |
Mini USB 2.0 |
||
|
Ingress protection |
IP |
IP20 |
||
|
Temperature |
Storage |
-40˚C to +85˚C (-40°F to 185°F) |
||
|
Operating |
-10˚C to +50˚C (14°F to 122°F) |
|||
|
Humidity |
Relative |
5% to 95% |
||
|
Connectors |
Type |
Removable |
||
|
Maximum cable size |
2.5 mm2 (18–12 AWG) |
|||
|
Maximum tightening torque |
0.35 Nm |
|||
|
Dimensions |
MAX Series |
|||
|
Width |
106.30 mm/4.19 in |
|||
|
Length |
110.00 mm/4.33 in |
|||
|
Height |
Without hand switches |
With hand switches |
||
|
62.00 mm/2.44 in |
70.00 mm/2.76 in |
|||
|
MIX18, MIX18-IP |
||||
|
Width |
87.80 mm/3.46 in |
|||
|
Length |
110.00 mm/4.33 in |
|||
|
Height |
62.00 mm/2.44 in |
|||
|
MIX38, MIX38-IP |
||||
|
Width |
160.20 mm/6.31 in |
|||
|
Length |
110.00 mm/4.33 in |
|||
|
Height |
62.00 mm/2.44 in |
|||
|
MINI Series |
||||
|
Width |
36.30 mm/1.43 in |
|||
|
Length |
110.00 mm/4.30 in |
|||
|
Height |
Without hand switches |
With hand switches |
||
|
62.00 mm/2.44 in |
68.70 mm/2.70 in |
|||
Summary Table for All Modules
|
Module Type |
UI |
DI |
AO |
DO |
TO |
Modbus RTU/ASCII |
Modbus TCP/IP |
BACnet MS/TP |
BACnet IP |
|---|---|---|---|---|---|---|---|---|---|
|
4I4O-H |
|
4 |
|
4 |
|
|
|
|
|
|
4I4O-H-IP |
|
4 |
|
4 |
|
|
|
|
|
|
4O-H |
|
|
|
4 (NC/NO-8A) |
|
|
|
|
|
|
4O-H-IP |
|
|
|
4 (NC/NO-8A) |
|
|
|
|
|
|
4U4A-H |
4 |
|
4 |
|
|
|
|
|
|
|
4U4A-H-IP |
4 |
|
4 |
|
|
|
|
|
|
|
4U4O-H |
4 |
|
|
4 |
|
|
|
|
|
|
4U4O-H-IP |
4 |
|
|
4 |
|
|
|
|
|
|
8I |
|
8 |
|
|
|
|
|
|
|
|
8I-IP |
|
8 |
|
|
|
|
|
|
|
|
8U |
8 |
|
|
|
|
|
|
|
|
|
8U-IP |
8 |
|
|
|
|
|
|
|
|
|
4TO-H |
|
|
|
|
4 |
|
|
|
|
|
4TO-H-IP |
|
|
|
|
4 |
|
|
|
|
|
MIX18 |
5 |
5 |
4 |
4 |
|
|
|
|
|
|
MIX18-IP |
5 |
5 |
4 |
4 |
|
|
|
|
|
|
MIX38 |
8 |
12 |
6 |
12 |
|
|
|
|
|
|
MIX38-IP |
8 |
12 |
6 |
12 |
|
|
|
|
|
|
12O-H |
|
|
|
12 |
|
|
|
|
|
|
12O-H-IP |
|
|
|
12 |
|
|
|
|
|
|
24I |
|
24 |
|
|
|
|
|
|
|
|
24I-IP |
|
24 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RS485 slave |
Modbus gateway IP/RS485 (works only as a master on RS485 network) |
RS485 master slave |
Modbus gateway IP/RS485 (works only as a master on RS485 network) |