The below table lists all Data Points used in the VAV application as variables.
The application employs 116 licensed Data Points.
|
Name |
DP
|
Def.
|
Units |
Exposed
|
BACnet
|
Modbus dec. addr. |
Conf.
|
Description |
|---|---|---|---|---|---|---|---|---|
|
OccupancyCalculator |
|
|||||||
|
OccupancyStatus |
MDP |
Unocc. |
N/a |
True |
MSI2 |
22 |
No |
Current occupancy status: 1: occupied 2: unoccupied 3: bypass 4: standby |
|
OccupancyMode |
MDP |
Unocc. |
N/a |
True |
MSV2 |
262 |
No |
Allows to set room the occupancy mode from the BMS system: 1: occupied 2: unoccupied 3: bypass 4: standby |
|
PanelOccupancyStatus |
MDP |
Unocc. |
N/a |
True |
MSV3 |
700 |
No |
Current room occupancy status dedicated to Control Point room panel 1: unoccupied 2: occupied 3: standby 4: bypass |
|
PanelOccupancyMode |
MDP |
Unocc. |
N/a |
True |
MSV4 |
701 |
No |
Status of set room occupancy mode from Control Point room panel 1: unoccupied 2: occupied |
|
PresenceSensor |
BDP |
N/a
|
True/
|
True |
BI0 |
301 |
No |
Actual presence sensor state from the I1 input |
|
WindowContact |
BDP |
N/a
|
True/
|
True |
BI1 |
303 |
No |
Actual window contact state from the I2 input |
|
BypassTimeOverride |
ADP |
120 |
s |
True |
AV34 |
234 |
Yes |
Time required to maintain the bypass occupancy status (after expiration it returns to the previous status) |
|
StandbyTimeOverride |
ADP |
15 |
s |
True |
AV35 |
235 |
Yes |
Time required to change the occupancy status to standby (after motion detection disappears) |
|
AutoOccMode |
BDP |
Disabled |
True/
|
True |
BV0 |
100 |
Yes |
Automatically changes occupancy to occupied when increased airflow is detected: false (disabled), true (enabled) |
|
PanelOccupancyReset |
MDP |
Unocc. |
N/a |
True |
MSV5 |
702 |
No |
Resetting the room occupancy mode from occupied to unoccupied in the Control Point room panel 1: unoccupied 2: occupied |
|
PresenceSensorInvert |
BDP |
Invert |
True/
|
True |
BV4 |
104 |
Yes |
Allows to invert the I1 input signal if required: false (normal), true (invert) |
|
WindowContactInvert |
BDP |
Normal |
True/
|
True |
BV5 |
105 |
Yes |
Allows to invert the I2 input signal if required: false (normal), true (invert) |
|
TemperatureSelector |
|
|||||||
|
SpaceTemperature |
ADP |
N/a
|
°C/°F |
True |
AI1 |
4 |
No |
Calculated space temperature |
|
NetTemperature |
ADP |
-327 |
°C/°F |
True |
AV10 |
210 |
No |
Temperature sensor value from the network |
|
U2SpaceTemperature |
ADP |
N/a
|
°C/°F |
True |
AI3 |
3 |
No |
Actual temperature sensor value from the local U2 input |
|
PanelTemperature |
ADP |
N/a
|
°C/°F |
True |
AI4 |
300 |
No |
Actual temperature sensor value from the room panel |
|
DischargeTemperature |
ADP |
N/a
|
°C/°F |
True |
AI13 |
13 |
No |
Calculated discharge temperature |
|
NetDuctInTemp |
ADP |
-327 |
°C/°F |
True |
AV18 |
218 |
No |
Discharge temperature sensor value from the network |
|
U1DischTemperature |
ADP |
N/a
|
°C/°F |
True |
AI16 |
16 |
No |
Actual discharge temperature sensor value comes from the U1 input |
|
U2SpaceTempType |
MDP |
10K3A1 NTC |
°C/°F |
True |
MSV22 |
282 |
Yes |
Allows to select the space temperature type: 1: Voltage measurement 2: Current 3: Resistance input 4: 10K3A1 NTC 5: 10K4A1 NTC 6: 10K NTC Carel 7: 20K6A1 NTC 8: 2,2K3A1 NTC 9: 3K3A1 NTC 10: 30K6A1 NTC 11: SIE1 12: TAC1 13: SAT1 14: PT1000 15: NI1000 16: NI1000 21C 17: NI1000 LG F 18: 10K Type2 NTC F 19: 10K Type3 NTC F 20: 20K NTC F 21: 3K NTC F 22: PT1000 F 23: NI1000 32F 24: NI1000 70F |
|
U1DischargeTempType |
MDP |
10K3A1 NTC |
°C/°F |
True |
MSV21 |
281 |
Yes |
Allows to select the discharge temperature type: 1: Voltage measurement 2: Current 3: Resistance input 4: 10K3A1 NTC 5: 10K4A1 NTC 6: 10K NTC Carel 7: 20K6A1 NTC 8: 2,2K3A1 NTC 9: 3K3A1 NTC 10: 30K6A1 NTC 11: SIE1 12: TAC1 13: SAT1 14: PT1000 15: NI1000 16: NI1000 21C 17: NI1000 LG F 18: 10K Type2 NTC F 19: 10K Type3 NTC F 20: 20K NTC F 21: 3K NTC F 22: PT1000 F 23: NI1000 32F 24: NI1000 70F Connected to CP MSV12 |
|
TemperatureInputSelector |
MDP |
Panel |
N/a |
True |
MSV23 |
283 |
Yes |
Allows to choose the temperature source for control logic: 1: panel 2: input 3: network |
|
OffsetCalculator |
|
|||||||
|
OffsetTempSetpoint |
ADP |
N/a
|
°C/°F |
True |
AV58 |
503 |
No |
Temperature offset for setpoint from the room panel |
|
SetpointOffsetRange |
ADP |
6 |
N/a |
True |
AV37 |
237 |
Yes |
Sets the setpoint offset range to be changed by the user (e.g., a value of 5 means a range from -5 to +5), (min = 0, max = 10) |
|
U3SetpointOffset |
ADP |
N/a
|
°C/°F |
True |
AI17 |
17 |
No |
Actual setpoint offset value (calculated from resistance) from the U3 input |
|
PanelSetpointDisplay |
BDP |
N/a
|
True/
|
True |
BO56 |
156 |
Yes |
Allows to select which value to be displayed during the offset editing according to the set Panel Setpoint Mode false (offset), true (setpoint) |
|
NetOffsetSetpoint |
ADP |
0 |
°C/°F |
|
AV41 |
241 |
No |
Offset temperature setpoint value from the network |
|
SetpointOffsetSelector |
MDP |
Panel |
N/a |
|
MSV24 |
284 |
Yes |
Allows to choose the setpoint offset source for control logic: 1: panel 2: input 3: network |
|
TemperatureSetpointSelector |
|
|||||||
|
PanelSetpointMode |
BDP |
N/a
|
True/
|
True |
BO55 |
155 |
Yes |
Sets the temperature setpoint mode in the Control Point room panel - directly or as an offset false (offset), true (setpoint) |
|
OccCoolTempSetpoint |
ADP |
23°C/74°F |
°C/°F |
True |
AV0 |
200 |
Yes |
Temperature setpoint for cooling in the occupied state |
|
OccHeatTempSetpoint |
ADP |
21°C/70°F |
°C/°F |
True |
AV1 |
201 |
Yes |
Temperature setpoint for heating in the occupied state |
|
StandbyCoolTempSetpoint |
ADP |
25°C/77°F |
°C/°F |
True |
AV2 |
202 |
Yes |
Temperature setpoint for cooling in the standby state |
|
StandbyHeatTempSetpoint |
ADP |
19°C/67°F |
°C/°F |
True |
AV3 |
203 |
Yes |
Temperature setpoint for heating in the standby state |
|
UnoccCoolTempSetpoint |
ADP |
28°C/80°F |
°C/°F |
True |
AV4 |
204 |
Yes |
Temperature setpoint for cooling in the unoccupied state |
|
UnoccHeatTempSetpoint |
ADP |
16°C/64°F |
°C/°F |
True |
AV5 |
205 |
Yes |
Temperature setpoint for heating in the unoccupied state |
|
EffectiveTempSetpoint |
ADP |
N/a
|
°C/°F |
True |
AI9 |
9 |
No |
Calculated effective temperature setpoint based on occupancy status and heating or cooling temperature setpoints (depending on demand) |
|
CentralTempSetpoint |
ADP |
N/a
|
°C/°F |
True |
AI10 |
10 |
No |
Calculated Central Temperature Setpoint based on setpoints and occupancy status |
|
PanelTempSetpoint |
ADP |
N/a
|
°C/°F |
True |
AV56 |
501 |
No |
Temperature setpoint from the room panel |
|
MaxDischTempSetpoint |
ADP |
32°C/90°F |
°C/°F |
True |
AV7 |
207 |
Yes |
High limit of discharge temperature supplied to the room |
|
ActDischTempSetpoint |
ADP |
N/a
|
°C/°F |
True |
AI14 |
14 |
No |
Calculated discharge temperature setpoint based on the effective temperature setpoint and heating demand for high-limiting discharge temperature |
|
MinDischTempSetpoint |
ADP |
13°C/55°F |
°C/°F |
True |
AV8 |
208 |
Yes |
Low limit of discharge temperature supplied to the room |
|
CO2Selector |
|
|||||||
|
PanelCO2 |
ADP |
N/a
|
ppm |
True |
AI6 |
302 |
No |
Actual CO2 sensor value from the room panel |
|
NetCO2 |
ADP |
N/a
|
ppm |
True |
AV40 |
240 |
No |
CO2 sensor value comes from the network |
|
U4CO2Sensor |
ADP |
N/a
|
ppm |
True |
AI8 |
8 |
No |
Actual CO2 sensor value from the local U4 input |
|
SpaceCO2 |
ADP |
N/a
|
ppm |
True |
AI5 |
5 |
Yes |
Calculated space CO2 |
|
U4CO2SensorRange |
ADP |
2000 |
N/a |
True |
AV38 |
238 |
Yes |
Sets the range of the CO2 sensor used (min = 0, max = 10000) |
|
CO2InputSelector |
MDP |
Panel |
N/a |
|
MSV25 |
285 |
Yes |
Allows to select the CO2 source for control logic: 1: panel 2: input 3: network |
|
AirflowCalculator |
|
|||||||
|
K-Factor |
ADP |
1000 |
N/a |
True |
AV61 |
288 |
Yes |
Sets the K-Factor (the flow rate at a differential pressure of 1inWC/1Pa on the measuring cross) for the given VAV model (min = 0) |
|
DifferentialPressure |
ADP |
N/a
|
Pa/WC |
True |
AI15 |
15 |
No |
Actual differential pressure sensor-measured value from the built-in pressure input |
|
ActualAirFlow |
ADP |
N/a
|
L/s/cfm |
True |
AI11 |
11 |
No |
Actual calculated airflow based on the K-Factor value and differential pressure measure |
|
AirflowCalibration |
ADP |
0 |
L/s/cfm |
True |
AV66 |
293 |
No |
Allows to enter the airflow value measured by the hood for calibration |
|
CalculatedKFactor |
ADP |
N/a
|
N/a |
False |
AV62 |
289 |
No |
Calculated K-Factor value (meaning the flow rate at a differential pressure of 1 inWC/1 Pa on the measuring cross) based on the entered measured airflow (using the hood) and the measured differential pressure from the built-in PI input |
|
PressureZeroing |
BDP |
No |
True/
|
True |
BV13 |
113 |
No |
Allows to perform zeroing action on the built-in PI pressure transducer if there is a non-zero value in the absence of airflow. Important: perform in the absence of airflow through the pressure transducer ports False (no), true (zeroing) |
|
AirflowSetpointCalculator |
|
|||||||
|
EffectiveAirFlowSetpoint |
ADP |
N/a
|
L/s/cfm |
True |
AI12 |
12 |
No |
Calculated effective airflow setpoint based on the occupancy status and heating or cooling airflow setpoints |
|
HVACMode |
MDP |
Auto |
N/a |
True |
MSV1 |
261 |
No |
Allows to set the operating mode for the VAV device: 1: Auto 2: Heat 3: Morning WarmUp 4: Cool 5: Night Purge 6: PreCool 7: Off (depressurize) 8: Fire (pressurize) |
|
MaxOccCoolAirflowSetpoint |
ADP |
400 |
L/s/cfm |
True |
AV11 |
211 |
Yes |
Maximum airflow setpoint for cooling in the occupied state (min = 0) |
|
MaxOccHeatAirflowSetpoint |
ADP |
200 |
L/s/cfm |
True |
AV13 |
213 |
Yes |
Minimum airflow setpoint for cooling in the occupied state (min = 0) |
|
MinOccCoolAirflowSetpoint |
ADP |
100 |
L/s/cfm |
True |
AV12 |
212 |
Yes |
Maximum airflow setpoint for heating in the occupied state (min = 0) |
|
MinOccHeatAirflowSetpoint |
ADP |
100 |
L/s/cfm |
True |
AV14 |
214 |
Yes |
Minimum airflow setpoint for heating in the occupied state (min = 0) |
|
StandbyAirflowSetpoint |
ADP |
50 |
L/s/cfm |
True |
AV15 |
215 |
Yes |
Airflow setpoint in the standby state (min = 0) |
|
UnoccAirflowSetpoint |
ADP |
25 |
L/s/cfm |
True |
AV16 |
216 |
Yes |
Airflow setpoint in the unoccupied state (min = 0) |
|
StartupFanAirflowSetpoint |
ADP |
35 |
L/s/cfm |
True |
AV17 |
217 |
Yes |
Airflow setpoint for a fan startup only (min = 0) |
|
UserSetAirflow |
ADP |
0 |
L/s/cfm |
True |
AV65 |
292 |
No |
User-set airflow setpoint (after selecting the User Position mode in the Damper Command variable) (min = 0) |
|
Heat&CoolLoops |
|
|||||||
|
HotAirTempSetpoint |
ADP |
26°C/78°F |
°C/°F |
True |
AV9 |
209 |
Yes |
Discharge temperature setpoint for detecting warm air to change the heating/cooling mode |
|
PanelHeating |
BDP |
N/a
|
True/
|
True |
BO16 |
116 |
No |
Heating mode status to be displayed as an icon on the Control Point room panel false (no heating), true (heating) |
|
PanelCooling |
BDP |
N/a
|
True/
|
True |
BO17 |
117 |
No |
Cooling mode status to be displayed as an icon on the Control Point room panel false (no cooling), true (cooling) |
|
ChangeoverDelay |
ADP |
2 |
min |
True |
AV36 |
236 |
No |
Delay time for changing the heating/cooling operating mode |
|
Airflow/DAT/CO2Loops |
|
|||||||
|
SpaceCO2Setpoint |
ADP |
1000 |
ppm |
True |
AV6 |
206 |
Yes |
CO2 setpoint for the room (regardless of the occupancy status) |
|
AHUOutdoorDamper |
ADP |
N/a
|
% |
True |
AO4 |
254 |
No |
Required opening level of the fresh air damper in the AHU resulting from the current CO2 level in the room (network signal to the AHU control) |
|
DamperControl |
|
|||||||
|
DeviceType |
BDP |
VAV |
True/
|
True |
BV6 |
106 |
Yes |
Allows to choose VAV device control type from airflow demand (VAV also known as pressure independent) or from cooling/heating demand (VVT also known as pressure dependent): false (VAV), true (VVT) |
|
MaxDamperPosition |
ADP |
100 |
% |
True |
AV21 |
221 |
Yes |
Maximum damper open position limit (min = 0, max = 100) |
|
MinDamperPosition |
ADP |
0 |
% |
True |
AV22 |
222 |
Yes |
Minimum damper open position limit (min = 0, max = 100) |
|
UserSetPosition |
ADP |
0 |
% |
True |
AV64 |
291 |
No |
User-set damper opening level (after selecting the User Position mode in the Damper Command variable) (min = 0, max = 100) |
|
DualHeat |
BDP |
No |
True/
|
True |
BV8 |
108 |
Yes |
Allows to enable dual heating mode with repeater/perimeter and damper (no effect without damper): false (no), true (yes) |
|
HeatDamperPriority |
BDP |
Secondary |
True/
|
True |
BV11 |
111 |
Yes |
Allows to set the priority of the damper heating operation when working in the active DualHeat mode: false (secondary), true (primary) |
|
DamperPosition |
ADP |
N/a
|
% |
True |
AO0 |
250 |
No |
Actual damper opening level coming from the Rotary Actuator component (Position Feedback signal) |
|
DamperResponse |
ADP |
2 |
% |
True |
AV26 |
226 |
Yes |
Sets the value of how much the control signal must change to perform the next damper movement |
|
DamperDriveTime |
ADP |
90 |
s |
True |
AV25 |
225 |
Yes |
Time required to reach full damper open position (from 0% to 100%) (min = 0) |
|
DirectionActuator |
BDP |
Clockwise |
True/
|
True |
BV9 |
109 |
Yes |
Sets the damper opening direction: false (CW), true (CCW) |
|
DamperControl |
ADP |
0 |
% |
True |
AV67 |
294 |
No |
Damper opening level control resulting from the application |
|
DamperCommand |
MDP |
None |
N/a |
True |
MSV7 |
267 |
No |
Allows to set different damper command modes for calibration, balancing, or testing: 1: Auto/none (null) 2: Max flow 3: Min flow 4: User flow 5: User position 6: Full open 7: Full close 8: Calibrate |
|
FanControl |
|
|||||||
|
FanCommand |
MDP |
Auto |
N/a |
True |
MSV8 |
268 |
No |
Allows to set different fan command modes for testing 1: Auto/none (null) 2: Max speed 3: Min speed 4: Stop |
|
FanControlMode |
BDP |
Digital |
True/
|
True |
BV10 |
110 |
Yes |
Allows to select the fan control mode: false (digital), true (analog) |
|
MaxFanSpeed |
ADP |
100 |
% |
True |
AV23 |
223 |
Yes |
Maximum fan speed level limit (min = 0, max = 100) |
|
MinFanSpeed |
ADP |
20 |
% |
True |
AV24 |
224 |
Yes |
Minimum fan speed level limit (min = 0, max = 100) |
|
WarmUpParallelFan |
BDP |
Disabled |
True/
|
True |
BV2 |
102 |
Yes |
Allows to use the parallel fan also in the Morning WarmUp mode (in the HVAC Mode variable): false (disabled), true (enabled) |
|
StandbySeriesFan |
BDP |
Disabled |
True/
|
True |
BV3 |
103 |
Yes |
Allows to use the series fan also in standby occupancy: false (disabled), true (enabled) |
|
FanDelayOff |
ADP |
30 |
s |
True |
AV39 |
239 |
Yes |
Delay time for switching off the fan |
|
PanelFanStatus |
MDP |
Off |
N/a |
True |
MSV0 |
600 |
No |
Fan status to be displayed as an icon on the Control Point room panel: 1: off 5: speed 1 (auto) 6: speed 2 (auto) 7: speed 3 (auto) |
|
FanStatus |
BDP |
Off |
True/
|
True |
BO1 |
121 |
No |
Fan digital control status (if configured as digital) from the application: false (off), true (on) |
|
FanSpeed |
ADP |
N/a
|
% |
True |
AO2 |
252 |
No |
Fan speed level control resulting from the application |
|
ReheaterControl |
|
|||||||
|
LoadShedding |
ADP |
0 |
% |
True |
AV20 |
220 |
No |
Load-shedding level required from the network (min = 0, max = 100) |
|
ReheaterCommand |
MDP |
Auto |
N/a |
True |
MSV9 |
269 |
No |
Allows to set different reheater command modes for testing 1: Auto/none (null) 2: Full open 3: Full close |
|
HeaterPriority |
MDP |
Reheater |
N/a |
True |
MSV14 |
274 |
Yes |
Possibility to select heating priority for heating sources: 1: reheater 2: perimeter 3: simultaneous |
|
WarmUpHeater |
BDP |
Disabled |
True/
|
True |
BV1 |
101 |
Yes |
Allows to use the reheater also in the Morning WarmUp mode (in the HVAC Mode variable): false (disabled), true (enabled) |
|
ReheaterControl |
ADP |
N/a
|
% |
True |
AO1 |
251 |
No |
Reheater valve opening level control resulting from the application |
|
TimePropReheaterPeriod |
ADP |
60 |
s |
True |
AV32 |
232 |
Yes |
Time required for a PWM valve for a full cycle time of a reheater |
|
FloatReheaterValveDriveTime |
ADP |
120 |
s |
True |
AV30 |
230 |
Yes |
Time required for a PWM valve for a full cycle time of a perimeter |
|
ReheaterStatus |
MDP |
Off |
N/a |
True |
MSO0 |
290 |
No |
Reheater staged control status (if configured as digital or staged) from application: 1: off 2: stage 1 on 3: stage 2 on |
|
PerimeterControl |
|
|||||||
|
PerimeterCommand |
MDP |
Auto |
N/a |
True |
MSV10 |
270 |
No |
Allows to set different perimeter command modes for testing 1: Auto/none (null) 2: Full open 3: Full close |
|
PerimeterControl |
ADP |
N/a
|
% |
True |
AO3 |
253 |
No |
Perimeter valve opening level control resulting from the application |
|
PerimeterStatus |
BDP |
Off |
True/
|
True |
BO0 |
120 |
No |
Perimeter digital control status (if configured as digital) from the application: false (off), true (on) |
|
TimePropPerimeterPeriod |
ADP |
60 |
s |
True |
AV33 |
233 |
Yes |
Time required for a PWM valve for a full cycle time of a perimeter |
|
OutsideTemperatureControl |
|
|||||||
|
MaxOatReheater |
ADP |
32°C/90°F |
°C/°F |
True |
AV28 |
228 |
Yes |
Maximum outside air temperature limit that allows the use of a reheater |
|
MaxOatPerimeter |
ADP |
18°C/65°F |
°C/°F |
True |
AV29 |
229 |
Yes |
Maximum outside air temperature limit that allows the use of a perimeter |
|
NetOutdoorTemp |
ADP |
-327 |
°C/°F |
True |
AV19 |
219 |
No |
Outside air temperature sensor value from the network |
|
DeviceConfiguration |
|
|||||||
|
DeviceConfigurationSource |
BDP |
BACnet |
True/
|
True |
BV12 |
112 |
Yes |
Allows to choose to set a source of the device application configuration: false (BACcnet), true (DIP switch) |
|
PerimeterType |
MDP |
None |
N/a |
True |
MSV13 |
273 |
Yes |
Allows to set the perimeter type: 1: none 2: TimeProp 3: digital |
|
ReheaterType |
MDP |
None |
N/a |
True |
MSV12 |
272 |
Yes |
Allows to set the reheater type: 1: none 2: TimeProp 3: staged 4: float |
|
FanType |
MDP |
None |
N/a |
True |
MSV11 |
271 |
Yes |
Allows to set the fan type: 1: none 2: series 3: parallel |
|
Units |
BDP |
Metric |
True/
|
True |
BO2 |
122 |
Yes |
Allows to change the unit in the application provided that the BACnet configuration is allowed in the Device Configuration Source variable: false (metric), true (imperial) |
|
UpTime |
ADP |
N/a
|
s |
True |
AI0 |
0 |
No |
Device’s up time |
|
AppVersion |
ADP |
1.0 |
N/a |
True |
AI100 |
102 |
No |
Current application version |
|
TriacOutputsConfig |
|
|||||||
|
TO4 |
ADP |
0 |
|
False |
996 |
996 |
No |
|
|
TO3 |
ADP |
0 |
|
False |
997 |
997 |
No |
|
|
TO2 |
ADP |
0 |
|
False |
998 |
998 |
No |
|
|
TO1 |
ADP |
0 |
|
False |
999 |
999 |
No |
|