Breadcrumbs

Protocol

Both RS485 and IP I/O modules work with Modbus protocol by default. Protocol configuration can be adjusted by changes on the 4th and 5th bit of the S3 DIP switch according to the table:

4

5

Protocol

Off (0)

Off (0)

Modbus RTU (in IP modules: Modbus TCP/IP)

Off (0)

On (1)

Modbus ASCII

On (1)

Off (0)

BACnet master (in IP modules: BACnet IP)

On (1)

On (1)

BACnet server

Protocol selection


Warning!

The BACnet slave mode does not support the discover function.