Skip to main content
Skip table of contents

Protocol

Both RS485 and IP I/O modules work with Modbus protocol by default. Protocol configuration can be adjusted by changes on the 4th and 5th bit of the S3 DIP switch according to the table:

4

5

Protocol

Off (0)

Off (0)

Modbus RTU (in IP modules: Modbus TCP/IP)

Off (0)

On (1)

Modbus ASCII

On (1)

Off (0)

BACnet master (in IP modules: BACnet IP)

On (1)

On (1)

BACnet server

Protocol selection

Warning!

The BACnet slave mode does not support the discover function.

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.