Breadcrumbs

List of Modbus Registers

The table below shows all registers available for the room panel.

Modbus address

Decimal address

Hex address

Register name

Access

Description

40001

0

0x00

VERSION_TYPE

Read/write

First byte indicates a version, and another one indicates a type of a device. Allows to enable 1 of 4 device actions.

30004

3

0x03

RECEIVED_FRAMES_COUNTER (32-bit)

Read-only

The default state is 0. Reset at the unit start and change of transmission parameters.

30006

5

0x05

ERROR_FRAMES_COUNTER (32-bit)

Read-only

The default state is 0. Reset at the unit start and change of transmission parameters.

30008

7

0x07

TRANSMITTED_FRAME_COUNTER _(32-bit)

Read-only

The default state is 0. Reset at the unit start and change of transmission parameters.

30012

11

0x0C

LIVE_TIME (32-bit)

Read-only

Device uptime in sec

40015

14

0x0E

BACNET_DEVICE_ID (32-bit)

Read/write

Memory

Default 0xFFFFFFFF

40017

16

0x10

BAUD_RATE

Read/write

Memory

Transmission speed is defined by the user, calculated using the formula:

baud rate = register value * 10

The default value is 11520 (115200 bps).

40018

17

0x11

STOP_BITS

Read/write

Memory

Supported values are 1 and 2.

The default value is 1.

40020

19

0x13

PARITY_BIT

Read/write

Memory

The default value is 0 (no parity).

Allowed values:

Value

Description

0 (default)

None

1

Odd

2

Even

40021

20

0x14

REPLAY_DELAY

Read/write

Memory

Delay in ms before sending response.

The default value is 0.

40023

22

0x16

ADDRESS

Read/write

Memory

Modbus address of the device.

The default value is 1.

40024

23

0x17

PROTOCOL

Read/write

Memory

0: Modbus RTU (default)

1: Modbus ASCII

2: BACnet MS/TP

40028

27

0x1B

PANEL_PASSWORD

Read/write

Memory

Password for the menu edit mode. The default is 1000.

30029

28

0x1C

SENSORS

Read-only

BIT0: humidity sensor

BIT1: CO2 sensor

BIT2: NTC sensor

30030

29

0x1D

BOOTLOADER_VERSION

Read-only

Bootloader version

30031

30

0x1E

HW_VERSION

Read-only

Hardware version

30201

200

0xC8

BACKGROUND_ILLUMINATION_LCD_CURRENT_VALUE

Read-only

Actual display illumination value

30202

201

0xC9

BACKGROUND_ILLUMINATION_KEY_PAD_CURRENT_VALUE

Read-only

Actual keypad illumination value

40203

202

0xCA

HOURS

Read/write

Hours part in time display

40204

203

0xCB

MINUTES

Read/write

Minutes part in time display

40205

204

0xCC

DEVICE_CONFIGURATION

Read/write

Memory

Bit

Name

0

1

0

BEEPER

Not active

Active (def)

1

TIME_FORMAT

24 h (def)

12 h

2

DEFAULT_TEMPERATURE_UNIT

Celsius (def)

Fahrenheit

3

BACKGROUND_ILLUMINATION_ LCD_ACTIVE

Not active

Active (def)

4

BACKGROUND_ILLUMINATION_KEY_PAD_ACTIVE

Not active (def)

Active

5

CO2_IN_ALARM_FLASHING_LCD

Not active

Active

6

CO2_IN_ALARM_BUZZER

Not active

Active

7

CO2_IN_ALARM_SHOW_HIGH

Not active

Active

8

CO2_ALARM_CONFIRM_ENABLE

Not active

Active

10

SUBMENU_ICON_DISPLAY_OFF

Not active

Active

11

PANEL_OFF

Panel on (def)

Panel off

12

KEY_PAD_OFF

Keypad on (def)

Keypad off

13

LCD_FLASHING

Not active (def)

Active

14

KEY_PAD_FLASHING

Not active (def)

Active

40207

206

0xCE

BACKGROUND_ILLUMINATION_LCD_FOR_ACTIVE_MODE

Read/write

Memory

Default 60%

40208

207

0xCF

BACKGROUND_ILLUMINATION_LCD_FOR_IDLE_MODE

Read/write

Memory

Default 40%

40209

208

0xD0

BACKGROUND_ILLUMINATION_LCD_FOR_STANDBY_MODE

Read/write

Memory

Default 0%

40210

209

0xD1

BACKGROUND_ILLUMINATION_LCD_TIME_TO_IDLE

Read/write

Memory

Default 10 sec

40211

210

0xD2

BACKGROUND_ILLUMINATION_LCD_TIME_TO_STANDBY

Read/write

Memory

Default 5 sec

40212

211

0xD3

BACKGROUND_ILLUMINATION_KEY_PAD_ACTIVE_MODE

Read/write

Memory

Default 10%

40213

212

0xD4

BACKGROUND_ILLUMINATION_KEY_PAD_IDLE_MODE

Read/write

Memory

Default 40%

40214

213

0xD5

BACKGROUND_ILLUMINATION_KEY_PAD_STANDBY_MODE

Read/write

Memory

Default 60%

40215

214

0xD6

BACKGROUND_ILLUMINATION_KEY_PAD_TIME_TO_IDLE

Read/write

Memory

Default 10 sec

40216

215

0xD7

BACKGROUND_ILLUMINATION_KEY_PAD_TIME_TO_STANDBY

Read/write

Memory

Default 5 sec

40217

216

0xD8

REFRESH_TIME

Read/write

Memory

Default 2 sec

40218

217

0xD9

TIME_CONFIGURATION

Read/write

Memory

Bit 0: 1 clock is visible (default)

Bit 0: 0 clock is not visible

40219

218

0xDA

LCD_ICON_DISPLAY

Read/write

Memory

Each bit of the register shows or hides assigned icon, as in the table below:

Bit

Icon name

Icon

0

Sun

03 sun.png

1

Moon

03 moon.png

2

Heating

03 heating.png

3

Cooling

03 cooling.png

4

Humidifier

03 humidifier.png

5

Dehumidifier

03 dehumidifier.png

6

Wireless

03 wireless.png

7

Settings

03 settings.png

8

Eco

03 eco.png

9

Recirculation

03 circulation.png

10

PC

03 pc.png

40220

219

0xDB

LCD_ICON_FLASHING

Read/write

Memory

Each bit of the register starts flashing of the assigned icon.

See table in LCD ICON DISPLAY register description.

40221

220

0xDC

LCD_ICON_FLASHING_TIME

Read/write

Memory

The time value, which is the base for calculating frequency of icon flashing. Icons are visible for 100% of the time value stored in the register, and hidden for 20% of that time. Default time: 500ms.

40222

221

0xDD

SUBMENU_ICON_FLASHING_TIME

Read/write

Memory

The time value, which is the base for calculating frequency of icon flashing. Icons are visible for 100% of the time value stored in the register, and hidden for 20% of that time. Default time 1000 ms.

40223

222

0xDE

ENTER_MENU_TIME

Read/write

Memory

Default 2 sec

40224

223

0xDF

EXIT_EDIT_TIME

Read/write

Memory

Default 5 sec

40225

224

0xE0

EXIT_MENU_TIME

Read/write

Memory

Default 10 sec

40226

225

0xE1

CO2_SETPOINT_FOR_ALARM

Read/write

Memory

CO2 alarm setpoint. By default, 1500 ppm.

40227

226

0xE2

CO2_HYSTERESIS_FOR_ALARM

Read/write

Memory

CO2 alarm hysteresis. By default, 100 ppm.

40228

227

0xE3

SUBMENU_PROTECTION

Read/write

Memory

Password protection from editing of submenus. By default, inactive.

40229

228

0xE4

SUBMENU_ICONS_FLASHING

Read/write

Memory

Switching on icons blinking

30230

229

0xE5

ALARM_STATUS

Read/write

Memory

CO2 current alarm status

Bit

Name

0

1

0

Alarm status

Not active

Active

1

Alarm confirmed

Not confirmed

Confirmed

30301

300

0x12C

TEMPERATURE_SENSOR

Read-only

Actual temperature sensor value with offset.

30302

301

0x12D

HUMIDITY_SENSOR

Read-only

Actual humidity sensor value with offset.

30303

302

0x12E

CO2_SENSOR

Read-only

Actual CO2 sensor value with offset.

40304

303

0x12F

TEMPERATURE_SENSOR_OFFSET

Read/write

Memory

Temperature sensor offset. The default is 0.

40305

304

0x130

HUMIDITY_SENSOR_OFFSET

Read/write

Memory

Humidity sensor offset. The default is 0.

40306

305

0x131

CO2_SENSOR_OFFSET

Read/write

Memory

CO2 sensor offset. The default is 0.

40307

306

0x132

TEMPERATURE_FILTER

Read/write

Memory

Default 60 sec

40308

307


0x133

HUMIDITY_FILTER

Read/write

Memory

Default 60 sec

40309

308



0x134

CO2_FILTER

Read/write

Memory

Default 60 sec

40310

309


0x135

TEMPERATURE_NAME (32-bit)

Read/write

Memory

Displayed temperature sensor name: TEMP.

40312

311


0x137

HUMIDITY_NAME (32-bit)

Read/write

Memory

Displayed humidity sensor name: HUMI.

40314

313

0x139

CO2_NAME (32-bit)

Read/write

Memory

Displayed CO2 sensor name: CO2.

40316

315

0x13B

TEMPERATURE_CONFIGURATION

Read/write

Memory

Bit

Name

0

1

0

Active

Not active

Active (def)

4

ThirdPointActive

No decimal places

Decimal (def)

40317

316

0x13C

HUMIDITY_CONFIGURATION

Read/write

Memory

Bit

Name

0

1

0

Active

Not active

Active (def)

4

ThirdPointActive

No decimal places

Decimal (def)

40318

317

0x13D

CO2_CONFIGURATION

Read/write

Memory

Bit

Name

0

1

0

Active

Not active

Active (def)

41501

1500

0x5DC

SETPOINT_VALUE

Read/write

Actual setpoint value. After reset, the default value is set to the setpoint value.

41502

1501

0x5DD

EFFECTIVE_SETPOINT

Read-only

Sum of Effective Setpoint and Offset value.

41503

1502

0x5DE

DEFAULT_SETPOINT

Read/write

Memory

Default 21oC

41504

1503

0x5DF

OFFSET_SETPOINT

Read/write

Memory

Default 0oC

41505

1504

0x5E0

SETPOINT_LOW_LIMIT

Read/write

Memory

Min. available setpoint value. By default 18oC.

41506

1505

0x5E1

SETPOINT_HIGH_LIMIT

Read/write

Memory

Max. available setpoint value. By default 24oC.

41507

1506


0x5E2

OFFSET_RANGE

Read/write

Memory

Limit offset value. By default 3oC.

41508

1507


0x5E3

SETPOINT_STEP

Read/write

Memory

Setpoint value step. By default 1oC.

41509

1508


0x5E4

OFFSET_NAME (32-bit)

Read/write

Memory

Displayed offset name: OFFS.

41511

1510

0x5E6

SETPOINT_NAME (32-bit)

Read/write

Memory

Displayed setpoint name: SETP.

41513

1512

0x5E8

SETPOINT_CONFIGURATION

Read/write

Memory

Bit

Name

0

1

0

Visible

Not visible

Visible (def)

1

Editable

Not editable

Editable (def)

2

Operating mode

Changing offset

Changing setpoint (def)

3

Setpoint display

Show/change offset

Show/change EffectiveSetpoint

4

Third point active

Not active

Active (def)

5

Fast edit mode

Not active (def)

Active

41601

1600

0x640

FAN_CURRENT_SPEED

Read/write


Register value

Fan mode

Comment

0

Off (def)

Fan is off

1

Manual speed 1

Fan works in speed 1 manual mode

2

Manual speed 2

Fan works in speed 2 manual mode

3

Manual speed 3

Fan works in speed 3 manual mode

4

Auto speed 1

Fan works in speed 1 auto mode

5

Auto speed 2

Fan works in speed 2 auto mode

6

Auto speed 3

Fan works in speed 3 auto mode

41602

1601

0x641

FAN_MODE

Read/write

Register value

Fan mode

0

Off

1

Manual speed 1 (def)

2

Manual speed 2

3

Manual speed 3

4

Auto

41603

1602


0x642

FAN_TYPE

Read/write

Memory

Register value

Fan type

Comment

0

0-10 V (def)

Fan is controlled by analog value 0-10 V DC

1

1-speed

1-speed fan

2

2-speed

2-speed fan

3

3-speed

3-speed fan

41604

1603


0x643

FAN_MODE_0_NAME (32-bit)

Read/write

Memory

Name for FAN MODE = 0. Default = OFF

41606

1605


0x645

FAN_MODE_1_NAME (32-bit)

Read/write

Memory

Name for FAN MODE = 1. Default = AUTO

41608

1607


0x647

FAN_MODE_2_NAME (32-bit)

Read/write

Memory

Name for FAN MODE = 2. Default = _ _ _1

41610

1609


0x649

FAN_MODE_3_NAME (32-bit)

Read/write

Memory

Name for FAN MODE = 3. Default = _ _11

41612

1611

0x64B

FAN_MODE_4_NAME (32-bit)

Read/write

Memory

Name for FAN MODE = 4. Default = _111

41614

1613

0x64D

FAN_CONFIGURATION

Read/write

Memory

Bit

Name

0

1

0

Visible

Not visible

Visible (def)

1

Editable

Not editable

Editable (def)

2

Part editable

Filly editable (def)

Auto off mode

5

Fast edit mode

Not active (def)

Active

6

Local mode

Not active

Active

BMS mode

Active (def)

Not active

41615

1614

0x64E

FAN_ICON_FLASHING_TIME

Read/write

Memory

The time base for calculating the frequency of the fan icon rotation simulation. By default 500 ms.

41701

1700


0x6A4

OCCUPANCY_CURRENT_STATUS

Read/write

Occupancy mode setting remotely:

Register value

Occupancy mode

0

Unoccupied

1

Occupied

2

Standby

3

Forced occupied

41702

1701

0x6A5

OCCUPANCY_MODE

Read/write

Memory

Occupancy mode setting from the room panel:

0: unoccupied

1: occupied

41703

1702


0x6A6

OCCUPANCY_MODE_0_NAME (32-bit)

Read/write

Memory

Name for OCCUPANCY MODE = 0. Default = UNOC

41705

1704

0x6A8

OCCUPANCY_MODE_1_NAME (32-bit)

Read/write

Memory

Name for OCCUPANCY MODE = 1. Default = OCC

41707

1706

0x6AA

OCCUPANCY_CONFIGURATION

Read/write

Memory

Bit

Name

0

1

0

Visible

Not visible

Visible (def)

1

Editable

Not editable

Editable (def)

5

Fast edit mode

Not active (def)

Active

6

Local mode

Not active

Active

BMS mode

Active (def)

Not active


List of Modbus registers available for a room panel