Control Point |
Control Point VAV |
|
|---|---|---|---|
|
Power Supply |
DC |
20-34 V |
|
|
AC |
24 V ± 20% |
||
|
Power consumption |
0.6 W at 24 V DC - panels without CO2 sensor 0.9 W at 24 V DC - panels with CO2 sensor 1.8 VA at 24 V AC - panels without CO2 sensor 2.5 VA at 24 V AC - panels with CO2 sensor |
||
|
Built-in Sensors |
Temperature sensor |
10k NTC type, range: 0-50˚C, accuracy: ± 0.5˚C, resolution: ± 0.1˚C |
|
|
Humidity sensor (applies to versions with humidity sensor) |
Range: 0-100% RH, accuracy: ± 2% RH in range of 10-90% RH, resolution: ± 1% RH |
||
|
CO2 sensor (applies to versions with CO2 sensor) |
Range: 400-2000 ppm, accuracy: 50 ppm + 5% of reading |
||
|
COM1 |
RS485 interface |
Up to 128 devices |
|
|
Half-duplex |
|||
|
Communication protocols |
Modbus RTU/ASCII, BACnet MS/TP |
||
|
Ports |
2 RJ45, screw connector |
||
|
Baud rate |
2400-115200 |
||
|
USB |
Type |
USB type C |
|
|
Power supply |
5 V DC |
||
|
Front Panel |
Display |
LCD 2.6" |
|
|
Buttons |
4 buttons (fan, up +, down -, occupancy) |
4 buttons (menu, up +, down -, confirmation) |
|
|
Ingress Protection |
IP rating |
IP20 for indoor installation |
|
|
Temperature |
Operating |
From 0°C to +50°C (32°F to 122°F) |
|
|
Storage |
From -40°C to 85°C (-40°F to 185°F) |
||
|
Humidity |
Relative |
From 5% to 95% RH (without condensation) |
|
|
Screw Connector
|
Type |
Removable screw terminals |
|
|
Maximum cable size |
1.5 mm2 (26…16 AWG) |
||
|
Housing |
Material |
PC/ABS |
|
|
Mounting |
|
||
|
Dimensions
|
Width |
86.30 mm/3.40 in |
|
|
Length |
129.30 mm/5.10 in |
||
|
Height |
24.80 mm/0.98 in |
||
Technical specification