FCU - Default application - Problem with changing the input type
Issue
When trying to change the type of input in the LocalIOConfig component, the slot goes back to its previous value after saving.
Possible solutions
In the default application, NV variables are linked to the configuration slots. To change the input type, change the SX_Sensor_Type variable value (where X is an input number).
Another way to change the input type is to remove a link incoming to the S IX Type Int slot in the LocalIOConfig component.