FCU - Default application - Problem with changing the input type

Issue

When trying to change the type of input in the LocalIOConfig component, the slot goes back to its previous value after saving.

image-20231117-090753.png

Figure 1. The LocalIOConfig component

Possible solutions

In the default application, NV variables are linked to the configuration slots. To change the input type, change the SX_Sensor_Type variable value (where X is an input number).

Another way to change the input type is to remove a link incoming to the S IX Type Int slot in the LocalIOConfig component.