Alarm Submenu Objects

BACnet ID

Object property

Object name

Access

Description

AV40

Present value

ALARMS_NUMERIC1:Present Value

Read/write, memory

Current value of the parameter

AV40

Description

ALARMS_NUMERIC1:Name

Read/write, memory

User-defined name of the parameter

AV40

4206

ALARMS_NUMERIC1:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV40

Low limit

ALARMS_NUMERIC1:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV40

High limit

ALARMS_NUMERIC1:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV40

4201

ALARMS_NUMERIC1:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV40

Out of service

ALARMS_NUMERIC1:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV40

4200

ALARMS_NUMERIC1:Editability

Read/write, memory

Enabling editability of the parameter

AV40

4202

ALARMS_NUMERIC1:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV40

Units

ALARMS_NUMERIC1:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV41

Present value

ALARMS_NUMERIC2:Present Value

Read/write, memory

Current value of the parameter

AV41

Description

ALARMS_NUMERIC2:Name

Read/write, memory

User-defined name of the parameter

AV41

4206

ALARMS_NUMERIC2:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV41

Low limit

ALARMS_NUMERIC2:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV41

High limit

ALARMS_NUMERIC2:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV41

4201

ALARMS_NUMERIC2:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV41

Out of service

ALARMS_NUMERIC2:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV41

4200

ALARMS_NUMERIC2:Editability

Read/write, memory

Enabling editability of the parameter

AV41

4202

ALARMS_NUMERIC2:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV41

Units

ALARMS_NUMERIC2:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV42

Present value

ALARMS_NUMERIC3:Present Value

Read/write, memory

Current value of the parameter

AV42

Description

ALARMS_NUMERIC3:Name

Read/write, memory

User-defined name of the parameter

AV42

4206

ALARMS_NUMERIC3:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV42

Low limit

ALARMS_NUMERIC3:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV42

High limit

ALARMS_NUMERIC3:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV42

4201

ALARMS_NUMERIC3:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV42

Out of service

ALARMS_NUMERIC3:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV42

4200

ALARMS_NUMERIC3:Editability

Read/write, memory

Enabling editability of the parameter

AV42

4202

ALARMS_NUMERIC3:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV42

Units

ALARMS_NUMERIC3:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV43

Present value

ALARMS_NUMERIC4:Present Value

Read/write, memory

Current value of the parameter

AV43

Description

ALARMS_NUMERIC4:Name

Read/write, memory

User-defined name of the parameter

AV43

4206

ALARMS_NUMERIC4:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV43

Low limit

ALARMS_NUMERIC4:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV43

High limit

ALARMS_NUMERIC4:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV43

4201

ALARMS_NUMERIC4:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV43

Out of service

ALARMS_NUMERIC4:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV43

4200

ALARMS_NUMERIC4:Editability

Read/write, memory

Enabling editability of the parameter

AV43

4202

ALARMS_NUMERIC4:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV43

Units

ALARMS_NUMERIC4:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV44

Present value

ALARMS_NUMERIC5:Present Value

Read/write, memory

Current value of the parameter

AV44

Description

ALARMS_NUMERIC5:Name

Read/write, memory

User-defined name of the parameter

AV44

4206

ALARMS_NUMERIC5:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV44

Low limit

ALARMS_NUMERIC5:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV44

High limit

ALARMS_NUMERIC5:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV44

4201

ALARMS_NUMERIC5:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV44

Out of service

ALARMS_NUMERIC5:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV44

4200

ALARMS_NUMERIC5:Editability

Read/write, memory

Enabling editability of the parameter

AV44

4202

ALARMS_NUMERIC5:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV44

Units

ALARMS_NUMERIC5:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV45

Present value

ALARMS_NUMERIC6:Present Value

Read/write, memory

Current value of the parameter

AV45

Description

ALARMS_NUMERIC6:Name

Read/write, memory

User-defined name of the parameter

AV45

4206

ALARMS_NUMERIC6:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV45

Low limit

ALARMS_NUMERIC6:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV45

High limit

ALARMS_NUMERIC6:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV45

4201

ALARMS_NUMERIC6:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV45

Out of service

ALARMS_NUMERIC6:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV45

4200

ALARMS_NUMERIC6:Editability

Read/write, memory

Enabling editability of the parameter

AV45

4202

ALARMS_NUMERIC6:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV45

Units

ALARMS_NUMERIC6:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV46

Present value

ALARMSNUMERIC7:Present Value

Read/write, memory

Current value of the parameter

AV46

Description

ALARMS_NUMERIC7:Name

Read/write, memory

User-defined name of the parameter

AV46

4206

ALARMS_NUMERIC7:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV46

Low limit

ALARMS_NUMERIC7:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV46

High limit

ALARMS_NUMERIC7:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV46

4201

ALARMS_NUMERIC7:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV46

Out of service

ALARMS_NUMERIC7:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV46

4200

ALARMS_NUMERIC7:Editability

Read/write, memory

Enabling editability of the parameter

AV46

4202

ALARMS_NUMERIC7:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV46

Units

ALARMS_NUMERIC7:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV47

Present value

ALARMS_NUMERIC8:Present Value

Read/write, memory

Current value of the parameter

AV47

Description

ALARMS_NUMERIC8:Name

Read/write, memory

User-defined name of the parameter

AV47

4206

ALARMS_NUMERIC8:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV47

Low limit

ALARMS_NUMERIC8:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV47

High limit

ALARMS_NUMERIC8:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV47

4201

ALARMS_NUMERIC8:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV47

Out of service

ALARMS_NUMERIC8:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV47

4200

ALARMS_NUMERIC8:Editability

Read/write, memory

Enabling editability of the parameter

AV47

4202

ALARMS_NUMERIC8:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV47

Units

ALARMS_NUMERIC8:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

BV40

Present value

ALARMS_BOOLEAN1:Present Value

Read/write, memory

Current value of the parameter

BV40

Description

ALARMS_BOOLEAN1:Name

Read/write, memory

User-defined name of the parameter

BV40

4203

ALARMS_BOOLEAN1:True Text

Read/write, memory

Text for the parameter’s true value

BV40

4204

ALARMS_BOOLEAN1:False Text

Read/write, memory

Text for the parameter’s false value

BV40

4201

ALARMS_BOOLEAN1:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV40

Out of service

ALARMS_BOOLEAN1:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV40

4200

ALARMS_BOOLEAN1:Editability

Read/write, memory

Enabling editability of the parameter

BV41

Present value

ALARMS_BOOLEAN2:Present Value

Read/write, memory

Current value of the parameter

BV41

Description

ALARMS_BOOLEAN2:Name

Read/write, memory

User-defined name of the parameter

BV41

4203

ALARMS_BOOLEAN2:True Text

Read/write, memory

Text for the parameter’s true value

BV41

4204

ALARMS_BOOLEAN2:False Text

Read/write, memory

Text for the parameter’s false value

BV41

4201

ALARMS_BOOLEAN2:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV41

Out of service

ALARMS_BOOLEAN2:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV41

4200

ALARMS_BOOLEAN2:Editability

Read/write, memory

Enabling editability of the parameter

BV42

Present value

ALARMS_BOOLEAN3:Present Value

Read/write, memory

Current value of the parameter

BV42

Description

ALARMS_BOOLEAN3:Name

Read/write, memory

User-defined name of the parameter

BV42

4203

ALARMS_BOOLEAN3:True Text

Read/write, memory

Text for the parameter’s true value

BV42

4204

ALARMS_BOOLEAN3:False Text

Read/write, memory

Text for the parameter’s false value

BV42

4201

ALARMS_BOOLEAN3:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV42

Out of service

ALARMS_BOOLEAN3:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV42

4200

ALARMS_BOOLEAN3:Editability

Read/write, memory

Enabling editability of the parameter

BV43

Present value

ALARMS_BOOLEAN4:Present Value

Read/write, memory

Current value of the parameter

BV43

Description

ALARMS_BOOLEAN4:Name

Read/write, memory

User-defined name of the parameter

BV43

4203

ALARMS_BOOLEAN4:True Text

Read/write, memory

Text for the parameter’s true value

BV43

4204

ALARMS_BOOLEAN4:False Text

Read/write, memory

Text for the parameter’s false value

BV43

4201

ALARMS_BOOLEAN4:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV43

Out of service

ALARMS_BOOLEAN4:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV43

4200

ALARMS_BOOLEAN4:Editability

Read/write, memory

Enabling editability of the parameter

BV44

Present value

ALARMS_BOOLEAN5:Present Value

Read/write, memory

Current value of the parameter

BV44

Description

ALARMS_BOOLEAN5:Name

Read/write, memory

User-defined name of the parameter

BV44

4203

ALARMS_BOOLEAN5:True Text

Read/write, memory

Text for the parameter’s true value

BV44

4204

ALARMS_BOOLEAN5:False Text

Read/write, memory

Text for the parameter’s false value

BV44

4201

ALARMS_BOOLEAN5:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV44

Out of service

ALARMS_BOOLEAN5:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV44

4200

ALARMS_BOOLEAN5:Editability

Read/write, memory

Enabling editability of the parameter

BV45

Present value

ALARMS_BOOLEAN6:Present Value

Read/write, memory

Current value of the parameter

BV45

Description

ALARMS_BOOLEAN6:Name

Read/write, memory

User-defined name of the parameter

BV45

4203

ALARMS_BOOLEAN6:True Text

Read/write, memory

Text for the parameter’s true value

BV45

4204

ALARMS_BOOLEAN6:False Text

Read/write, memory

Text for the parameter’s false value

BV45

4201

ALARMS_BOOLEAN6:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV45

Out of service

ALARMS_BOOLEAN6:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV45

4200

ALARMS_BOOLEAN6:Editability

Read/write, memory

Enabling editability of the parameter

BV46

Present value

ALARMS_BOOLEAN7:Present Value

Read/write, memory

Current value of the parameter

BV46

Description

ALARMS_BOOLEAN7:Name

Read/write, memory

User-defined name of the parameter

BV46

4203

ALARMS_BOOLEAN7:True Text

Read/write, memory

Text for the parameter’s true value

BV46

4204

ALARMS_BOOLEAN7:False Text

Read/write, memory

Text for the parameter’s false value

BV46

4201

ALARMS_BOOLEAN7:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV46

Out of service

ALARMS_BOOLEAN7:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV46

4200

ALARMS_BOOLEAN7:Editability

Read/write, memory

Enabling editability of the parameter

BV47

Present value

ALARMS_BOOLEAN8:Present Value

Read/write, memory

Current value of the parameter

BV47

Description

ALARMS_BOOLEAN8:Name

Read/write, memory

User-defined name of the parameter

BV47

4203

ALARMS_BOOLEAN8:True Text

Read/write, memory

Text for the parameter’s true value

BV47

4204

ALARMS_BOOLEAN8:False Text

Read/write, memory

Text for the parameter’s false value

BV47

4201

ALARMS_BOOLEAN8:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV47

Out of service

ALARMS_BOOLEAN8:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV47

4200

ALARMS_BOOLEAN8:Editability

Read/write, memory

Enabling editability of the parameter


List of alarm submenu objects