A CO2 sensor is an optional equipment in the Control Point panel. It is marked with a letter C in a product code, for example: CP-HC (means the panel is equipped with a temperature, humidity, and CO2 sensors). The CO2 sensor's configuration data is available in the following parameters or in the iSMA Configurator:
CO2_SENSOR: indicates a current CO2 value with offset;
-
Modbus register: 30303;
-
BACnet object: AI6, property: Present Value;
CO2_OFFSET: allows to set an offset value for the CO2 sensor (correction to the CO2 sensor's value). The default value is 0;
-
Modbus register: 40306;
-
BACnet object: AI6, property: 4205;
CO2_FILTER: allows to set a filtering value for the CO2 sensor (expressed in seconds). The default value is 10 seconds;
-
Modbus register: 40309;
-
BACnet object: AI6, property: 4003;
CO2_NAME: allows to set a unique 4-letter name for a CO2 sensor;
-
Modbus registers: 40314, 40315 (each for two letters of the name);
-
BACnet object: AI 6, property: Description Property.
Configuration of CO2 Sensor on Display
CO2_CONFIGURATION: allows to activate or deactivate the CO2 sensor:
-
ACTIVE: activates or deactivates the sensor;
-
Modbus register: 40318, bit 0;
-
BACnet object: AO6, property: 4200;
-
|
Bit |
Name |
0 |
1 |
|---|---|---|---|
|
0 |
ACTIVE |
Inactive |
Active (default) |
Activating CO2 sensor