Niagara - Station Copier - Transfer files failed - config.bog(old) problem
This article described a way to fix an error that can occur when copying a station from a computer to a Supervisor or device, such as the iSMA-B-MAC36NL. It is based on an error of two "config.bog" files in the station.
When trying to copy a station from a computer to a Supervisor or device, it may happen that the ‘Transferring station’ tool selects the wrong BOG type file, in this case "config(old).bog".
Fig. 1 Error related to the use of an archive file, config(old).bog
In such case, open the folder where the station is located - by default, it is: C:\nUserName\Niagara4.7 - and check its contents.
Fig. 2 Contents of the station folder
Delete the config(old).bog file. After deleting it, the next step is to restart the Niagara Workbench and use Station Copier.
Fig. 3 Successful copying of the station
On the next attempt, the' Transferring station' tool will select the appropriate config.bog file and the whole process will be successful.