Niagara - Station Copier - Transfer files failed - config.bog(old) problem

This article described a way to fix an error that can occur when copying a station from a computer to a Supervisor or device, such as the iSMA-B-MAC36NL. It is based on an error of two "config.bog" files in the station.

  1. When trying to copy a station from a computer to a Supervisor or device, it may happen that the ‘Transferring station’ tool selects the wrong BOG type file, in this case "config(old).bog".

Fig. 1 Error related to the use of an archive file, config(old).bog

  1. In such case, open the folder where the station is located - by default, it is: C:\nUserName\Niagara4.7 - and check its contents.

Fig. 2 Contents of the station folder

  1. Delete the config(old).bog file. After deleting it, the next step is to restart the Niagara Workbench and use Station Copier.

Fig. 3 Successful copying of the station

  1. On the next attempt, the' Transferring station' tool will select the appropriate config.bog file and the whole process will be successful.

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.