Alarm Submenu Objects

BACnet ID

Object Property

Object Name

Access

Description

AV 40

Present value

ALARMS_NUMERIC1

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 40

Description

ALARMS_NUMERIC1

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 40

Step increment

ALARMS_NUMERIC1

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 40

Low limit

ALARMS_NUMERIC1

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 40

High limit

ALARMS_NUMERIC1

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 40

4201

ALARMS_NUMERIC1

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 40

Out of service

ALARMS_NUMERIC1

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 40

4200

ALARMS_NUMERIC1

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 40

4202

ALARMS_NUMERIC1

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 40

Units

ALARMS_NUMERIC1

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 41

Present value

ALARMS_NUMERIC2

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 41

Description

ALARMS_NUMERIC2

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 41

Step increment

ALARMS_NUMERIC2

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 41

Low limit

ALARMS_NUMERIC2

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 41

High limit

ALARMS_NUMERIC2

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 41

4201

ALARMS_NUMERIC2

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the Submenu

AV 41

Out of service

ALARMS_NUMERIC2

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 41

4200

ALARMS_NUMERIC2

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 41

4202

ALARMS_NUMERIC2

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 41

Units

ALARMS_NUMERIC2

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 42

Present value

ALARMS_NUMERIC3

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 42

Description

ALARMS_NUMERIC3

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 42

Step increment

ALARMS_NUMERIC3

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 42

Low limit

ALARMS_NUMERIC3

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 42

High limit

ALARMS_NUMERIC3

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 42

4201

ALARMS_NUMERIC3

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 42

Out of service

ALARMS_NUMERIC3

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 42

4200

ALARMS_NUMERIC3

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 42

4202

ALARMS_NUMERIC3

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 42

Units

ALARMS_NUMERIC3

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 43

Present value

ALARMS_NUMERIC4

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 43

Description

ALARMS_NUMERIC4

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 43

Step increment

ALARMS_NUMERIC4

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 43

Low limit

ALARMS_NUMERIC4

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 43

High limit

ALARMS_NUMERIC4

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 43

4201

ALARMS_NUMERIC4

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 43

Out of service

ALARMS_NUMERIC4

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 43

4200

ALARMS_NUMERIC4

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 43

4202

ALARMS_NUMERIC4

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 43

Units

ALARMS_NUMERIC4

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 44

Present value

ALARMS_NUMERIC5

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 44

Description

ALARMS_NUMERIC5

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 44

Step increment

ALARMS_NUMERIC5

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 44

Low limit

ALARMS_NUMERIC5

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 44

High limit

ALARMS_NUMERIC5

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 44

4201

ALARMS_NUMERIC5

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 44

Out of service

ALARMS_NUMERIC5

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 44

4200

ALARMS_NUMERIC5

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 44

4202

ALARMS_NUMERIC5

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 44

Units

ALARMS_NUMERIC5

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 45

Present value

ALARMS_NUMERIC6

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 45

Description

ALARMS_NUMERIC6

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 45

Step increment

ALARMS_NUMERIC6

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 45

Low limit

ALARMS_NUMERIC6

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 45

High limit

ALARMS_NUMERIC6

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 45

4201

ALARMS_NUMERIC6

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 45

Out of service

ALARMS_NUMERIC6

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 45

4200

ALARMS_NUMERIC6

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 45

4202

ALARMS_NUMERIC6

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 45

Units

ALARMS_NUMERIC6

UNITS

Read / write

Memory

Supported Units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 46

Present value

ALARMSNUMERIC7

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 46

Description

ALARMS_NUMERIC7

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 46

Step increment

ALARMS_NUMERIC7

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 46

Low limit

ALARMS_NUMERIC7

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 46

High limit

ALARMS_NUMERIC7

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 46

4201

ALARMS_NUMERIC7

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 46

Out of service

ALARMS_NUMERIC7

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 46

4200

ALARMS_NUMERIC7

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 46

4202

ALARMS_NUMERIC7

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 46

Units

ALARMS_NUMERIC7

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 47

Present value

ALARMS_NUMERIC8

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 47

Description

ALARMS_NUMERIC8

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 47

Step increment

ALARMS_NUMERIC8

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 47

Low limit

ALARMS_NUMERIC8

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 47

High limit

ALARMS_NUMERIC8

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 47

4201

ALARMS_NUMERIC8

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 47

Out of service

ALARMS_NUMERIC8

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 47

4200

ALARMS_NUMERIC8

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 47

4202

ALARMS_NUMERICE8

POINT ACTIV

Read / write

Memory

Number of decimal places from 0 to 3

AV 47

Units

ALARMS_NUMERIC8

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

BV 40

Present value

ALARMS_BOOLEAN1

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 40

Description

ALARMS_BOOLEAN1

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 40

True text

ALARMS_BOOLEAN1

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 40

False text

ALARMS_BOOLEAN1

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 40

4201

ALARMS_BOOLEAN1

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 40

Out of

service

ALARMS_BOOLEAN8

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 40

4200

ALARMS_BOOLEAN8

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 41

Present value

ALARMS_BOOLEAN2

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 41

Description

ALARMS_BOOLEAN2

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 41

True text

ALARMS_BOOLEAN2

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 41

False text

ALARMS_BOOLEAN2

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 41

4201

ALARMS_BOOLEAN2

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 41

Out of service

ALARMS_BOOLEAN2

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 41

4200

ALARMS_BOOLEAN2

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 42

Present value

ALARMS_BOOLEAN3

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 42

Description

ALARMS_BOOLEAN3

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 42

True text

ALARMS_BOOLEAN3

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 42

False text

ALARMS_BOOLEAN3

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 42

4201

ALARMS_BOOLEAN3

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 42

Out of service

ALARMS_BOOLEAN3

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 42

4200

ALARMS_BOOLEAN3

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 43

Present value

ALARMS_BOOLEAN4

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 43

Description

ALARMS_BOOLEAN4

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 43

True text

ALARMS_BOOLEAN4

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 43

False text

ALARMS_BOOLEAN4

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 43

4201

ALARMS_BOOLEAN4

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 43

Out of service

ALARMS_BOOLEAN4

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 43

4200

ALARMS_BOOLEAN4

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 44

Present value

ALARMS_BOOLEAN5

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 44

Description

ALARMS_BOOLEAN5

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 44

True text

ALARMS_BOOLEAN5

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 44

False text

ALARMS_BOOLEAN5

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 44

4201

ALARMS_BOOLEAN5

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 44

Out of service

ALARMS_BOOLEAN5

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 44

4200

ALARMS_BOOLEAN5

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 45

Present value

ALARMS_BOOLEAN6

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 45

Description

ALARMS_BOOLEAN6

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 45

True text

ALARMS_BOOLEAN6

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 45

False text

ALARMS_BOOLEAN6

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 45

4201

ALARMS_BOOLEAN6

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 45

Out of service

ALARMS_BOOLEAN6

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 45

4200

ALARMS_BOOLEAN6

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 46

Present value

ALARMS_BOOLEAN7

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 46

Description

ALARMS_BOOLEAN7

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 46

True text

ALARMS_BOOLEAN7

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 46

False text

ALARMS_BOOLEAN7

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 46

4201

ALARMS_BOOLEAN7

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 46

Out of service

ALARMS_BOOLEAN7

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 46

4200

ALARMS_BOOLEAN7

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 47

Present value

ALARMS_BOOLEAN8

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 47

Description

ALARMS_BOOLEAN8

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 47

True text

ALARMS_BOOLEAN8

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 47

False text

ALARMS_BOOLEAN8

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 47

4201

ALARMS_BOOLEAN8

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 47

Out of service

ALARMS_BOOLEAN8

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 47

4200

ALARMS_BOOLEAN8

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

List of alarm submenu objects