Alarms Submenu Registers

Modbus address

Decimal address

Hex address

Register name

Access

Description

41113

1112

0x458

ALARMS_MENU_ACTIVE_POINTS

Read/write, memory

Number of active parameters in the submenu

40091

90

0x5A

ALARMS_NUMERIC1__PRESENT_VALUE

Read/write, memory

Current value of the parameter

41116

1115

0x45B

ALARMS_NUMERIC1_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

41118

1117

0x45D

ALARMS_NUMERIC1_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

41119

1118

0x45E

ALARMS_NUMERIC1_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

41120

1119

0x45F

ALARMS_NUMERIC1_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

41121

1120

0x460

ALARMS_NUMERIC1_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

41122

1121

0x461

ALARMS_NUMERIC1_CONFIGURATION

Read/write, memory

Bit

Parameter

0

1

0

Active

Not active (default)

Active

2

First point active

No decimal places (default)

One decimal places active

3

Second point active

No decimal places (default)

Two decimal placess active

4

Third point active

No decimal places (default)

Three decimal placess active

6

C unit active

Not active (default)

Active

7

F unit active

Not active (default)

Active

8

Pa unit active

Not active (default)

Active

9

Lx unit active

Not active (default)

Active

10

ppm unit active

Not active (default)

Active

11

m3/h unit active

Not active (default)

Active

12

%Rh unit active

Not active (default)

Active

13

l/s unit active

Not active (default)

Active

14

% unit active

Not active (default)

Active

15

h unit active

Not active (default)

Active

40092

91

0x5B

ALARMS_NUMERIC2_PRESENT_VALUE

Read/write, memory

Current value of the parameter

41125

1124

0x464

ALARMS_NUMERIC2_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

41127

1126

0x466

ALARMS_NUMERIC2_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

41128

1127

0x467

ALARMS_NUMERIC2_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

41129

1128

0x468

ALARMS_NUMERIC2_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

41130

1129

0x469

ALARMS_NUMERIC2_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

41131

1130

0x46A

ALARMS_NUMERIC2_CONFIGURATION

Read/write, memory

See the table in ALARMS_NUMERIC1_CONFIGURATION (41122)

40093

92

0x5C

ALARMS_NUMERIC3_PRESENT_VALUE

Read/write, memory

Current value of the parameter

41134

1133

0x46D

ALARMS_NUMERIC3_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

41136

1135

0x46F

ALARMS_NUMERIC3_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

41137

1136

0x470

ALARMS_NUMERIC3_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

41138

1137

0x471

ALARMS_NUMERIC3_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

41139

1138

0x472

ALARMS_NUMERIC3_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

41140

1139

0x473

ALARMS_NUMERIC3_CONFIGURATION

Read/write, memory

See the table in ALARMS_NUMERIC1_CONFIGURATION (41122)

40094

93

0x5D

ALARMS_NUMERIC4_PRESENT_VALUE

Read/write, memory

Current value of the parameter

41143

1142

0x476

ALARMS_NUMERIC4_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

41145

1144

0x478

ALARMS_NUMERIC4_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

41146

1145

0x479

ALARMS_NUMERIC4_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

41147

1146

0x47A

ALARMS_NUMERIC4_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

41148

1147

0x47B

ALARMS_NUMERIC4_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

41149

1148

0x47C

ALARMS_NUMERIC4_CONFIGURATION

Read/write, memory

See the table in ALARMS_NUMERIC1_CONFIGURATION (41122)

40095

94

0x5E

ALARMS_NUMERIC5_PRESENT_VALUE

Read/write, memory

Current value of the parameter

41152

1151

0x47F

ALARMS_NUMERIC5_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

41154

1153

0x481

ALARMS_NUMERIC5_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

41155

1154

0x482

ALARMS_NUMERIC5_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

41156

1155

0x483

ALARMS_NUMERIC5_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

41157

1156

0x484

ALARMS_NUMERIC5_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

41158

1157

0x485

ALARMS_NUMERIC5_CONFIGURATION

Read/write, memory

See the table in ALARMS_NUMERIC1_CONFIGURATION (41122)

40096

95

0x5F

ALARMS_NUMERIC6_PRESENT_VALUE

Read/write, memory

Current value of the parameter

41161

1160

0x488

ALARMS_NUMERIC6_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

41163

1162

0x48A

ALARMS_NUMERIC6_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

41164

1163

0x48B

ALARMS_NUMERIC6_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

41165

1164

0x48C

ALARMS_NUMERIC6_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

41166

1165

0x48D

ALARMS_NUMERIC6_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

41167

1166

0x48E

ALARMS_NUMERIC6_CONFIGURATION

Read/write, memory

See the table in ALARMS_NUMERIC1_CONFIGURATION (41122)

40097

96

0x60

ALARMS_NUMERIC7_PRESENT_VALUE

Read/write, memory

Current value of the parameter

41170

1169

0x491

ALARMS_NUMERIC7_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

41172

1171

0x493

ALARMS_NUMERIC7_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

41173

1172

0x494

ALARMS_NUMERIC7_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

41174

1173

0x495

ALARMS_NUMERIC7_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

41175

1174

0x496

ALARMS_NUMERIC7_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

41176

1175

0x497

ALARMS_NUMERIC7_CONFIGURATION

Read/write, memory

See the table in ALARMS_NUMERIC1_CONFIGURATION (41122)

40098

97

0x61

ALARMS_NUMERIC8_PRESENT_VALUE

Read/write, memory

Current value of the parameter

41179

1178

0x49A

ALARMS_NUMERIC8_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

41181

1180

0x49C

ALARMS_NUMERIC8_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

41182

1181

0x49D

ALARMS_NUMERIC8_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

41183

1182

0x49E

ALARMS_NUMERIC8_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

41184

1183

0x49F

ALARMS_NUMERIC8_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

41185

1184

0x4A0

ALARMS_NUMERIC8_CONFIGURATION

Read/write, memory

See the table in ALARMS_NUMERIC1_CONFIGURATION (41122)

40112

111

0x6F

ALARMS_BOOLEAN_ALL_PRESENT_VALUE

Read/write, memory

Bit

Parameter

0

1

0

BOOLEAN1_PRESENT_VALUE

Not active (default)

Active

1

BOOLEAN2_PRESENT_VALUE

Not active (default)

Active

6

BOOLEAN7_PRESENT_VALUE

Not active (default)

Active

7

BOOLEAN8_PRESENT_VALUE

Not active (default)

Active

40138

153

0x99

ALARMS_BOOLEAN1_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40882

1187

0x4A3

ALARMS_BOOLEAN1_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40884

1189

0x4A5

ALARMS_BOOLEAN1_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

40886

1191

0x4A7

ALARMS_BOOLEAN1_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40888

1193

0x4A9

ALARMS_BOOLEAN1_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

41195

1194

0x4AA

ALARMS_BOOLEAN1_CONFIGURATION

Read/write, memory

Bit

Parameter

0

1

0

ACTIVE

Not active (default)

Active

1

EDITABLE

Not editable

Editable (default)

40155

154

0x9A

ALARMS_BOOLEAN2_PRESENT_VALUE

Read/write, memory

Current value of the parameter

41199

1197

0x4AD

ALARMS_BOOLEAN2_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

41201

1199

0x4AF

ALARMS_BOOLEAN2_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

41202

1201

0x4B1

ALARMS_BOOLEAN2_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

41204

1203

0x4B3

ALARMS_BOOLEAN2_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

41205

1204

0x4B4

ALARMS_BOOLEAN2_CONFIGURATION

Read/write, memory

See the table in ALARMS_BOOLEAN1_CONFIGURATION (41195)

40156

155

0x9B

ALARMS_BOOLEAN3_PRESENT_VALUE

Read/write, memory

Current value of the parameter

41208

1207

0x4B7

ALARMS_BOOLEAN3_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

41210

1209

0x4B9

ALARMS_BOOLEAN3_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

41212

1211

0x4BB

ALARMS_BOOLEAN3_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

41214

1213

0x4BD

ALARMS_BOOLEAN3_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

41215

1214

0x4BE

ALARMS_BOOLEAN3_CONFIGURATION

Read/write, memory

See the table in ALARMS_BOOLEAN1_CONFIGURATION (41195)

40157

156

0x9C

ALARMS_BOOLEAN4_PRESENT_VALUE

Read/write, memory

Current value of the parameter

41218

1217

0x4C1

ALARMS_BOOLEAN4_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

41220

1219

0x4C3

ALARMS_BOOLEAN4_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

41222

1221

0x4C5

ALARMS_BOOLEAN4_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

41224

1223

0x4C7

ALARMS_BOOLEAN4_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

41225

1224

0x4C8

ALARMS_BOOLEAN4_CONFIGURATION

Read/write, memory

See the table in ALARMS_BOOLEAN1_CONFIGURATION (41195)

40158

157

0x9D

ALARMS_BOOLEAN5_PRESENT_VALUE

Read/write, memory

Current value of the parameter

41228

1227

0x4CB

ALARMS_BOOLEAN5_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

41230

1229

0x4CD

ALARMS_BOOLEAN5_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

41232

1231

0x4CF

ALARMS_BOOLEAN5_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

41234

1233

0x4D1

ALARMS_BOOLEAN5_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

41235

1234

0x4D2

ALARMS_BOOLEAN5_CONFIGURATION

Read/write, memory

See the table in ALARMS_BOOLEAN1_CONFIGURATION (41195)

40159

158

0x9E

ALARMS_BOOLEAN6_PRESENT_VALUE

Read/write, memory

Current value of the parameter

41238

1237

0x4D5

ALARMS_BOOLEAN6_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

41240

1239

0x4D7

ALARMS_BOOLEAN6_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

41242

1241

0x4D9

ALARMS_BOOLEAN6_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

41244

1243

0x4DB

ALARMS_BOOLEAN6_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

41245

1244

0x4DC

ALARMS_BOOLEAN6_CONFIGURATION

Read/write, memory

See the table in ALARMS_BOOLEAN1_CONFIGURATION (41195)

40160

159

0x9F

ALARMS_BOOLEAN7_PRESENT_VALUE

Read/write, memory

Current value of the parameter

41248

1247

0x4DF

ALARMS_BOOLEAN7_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

41250

1249

0x4E1

ALARMS_BOOLEAN7_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

41252

1251

0x4E3

ALARMS_BOOLEAN7_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

41254

1253

0x4E5

ALARMS_BOOLEAN7_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

41255

1254

0x4E6

ALARMS_BOOLEAN7_CONFIGURATION

Read/write, memory

See the table in ALARMS_BOOLEAN1_CONFIGURATION (41195)

40161

160

0xA0

ALARMS_BOOLEAN8_PRESENT_VALUE

Read/write, memory

Current value of the parameter

41258

1257

0x4E9

ALARMS_BOOLEAN8_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

41260

1259

0x4EB

ALARMS_BOOLEAN8_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

41262

1261

0x4ED

ALARMS_BOOLEAN8_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

41264

1263

0x4EF

ALARMS_BOOLEAN8_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

41265

1264

0x4F0

ALARMS_BOOLEAN8_CONFIGURATION

Read/write, memory

See the table in ALARMS_BOOLEAN1_CONFIGURATION (41195)


List of alarms submenu registers