nE2 Link - Links - Editing problems
Issue
Problem with editing an existing link between nano components using the Edit option.
Possible causes and solutions
Disabling the link using the Edit option does not work
When a user attempts to use the Edit option to disable the link between components under the ne2DeviceExt, it does not function as expected. Modifying the Enabled slot has no effect - the link still works.


Solution
Delete the link to disable it.
Editing link and changing slots to non-existing ones.
Using the Edit action on a link and changing its slot names to non-existent ones causes the link to disappear.
The next time the user tries to create a link, they encounter a Link Creation Error.


Solution
Do not change slot names to non existing ones.