Module Registers


Registered Access

Modbus Address

Decimal Address

Hex Address

Register Name

Access

Description

30001

0

0x00

Version/Type

Read

Version and type of the device

30002

1

0x01

Address

Read

Module address

40003

2

0x02

Baud Rate

Read/write

RS485 baud rate

40004

3

0x03

Stop Bits & Data Bits

Read/write

No. of stop bits & data bits

40005

4

0x04

Parity

Read/write

Parity bit

40006

5

0x05

Response Delay

Read/write

Response delay in ms

40007

6

0x06

Modbus Mode

Read/write

Modbus Mode (ASCII or RTU)

40010

9

0x09

Filter

Read/write

Measurement filtering, value from 1 to 10

40033

32

0x20

Received Packets LSR (Least Significant Register)

Read/write

No. of received packets

40034

33

0x21

Received Packets MSR (Most Significant Register)

Read/write

40035

34

0x22

Incorrect Packets LSR

Read/write

No. of received packets with error

40036

35

0x23

Incorrect packets MSR

Read/write

40037

36

0x24

Sent Packets LSR

Read/write

No. of sent packets

40038

37

0x25

Sent Packets MSR

Read/write

30051

50

0x32

Inputs

Read

Connected sensors
Bit in high state → sensor is connected

40052

51

0x33

Outputs

Read/write

Alarms state
Bit 2 alarm output

30053

52

0x34

Temperature

Read

Temperature or measured analog

in mV·10 for voltage to 2048 mV
in mV·100 for voltage to 256 mV
in °C·10 for temperature
in Ω for resistance

30054

53

0x35

Junction Temperature

Read

Module junction temperature

30055

54

0x36

Measurement Current

Read

Measurement current

40056

55

0x37

MAX Alarm Level

Read/write

If the temperature exceeds this value the corresponding alarm flag is set

40057

56

0x38

MIN Alarm Level

Read/write

If the temperature is below this value corresponding alarm flag is set

40058

57

0x39

Alarm Settings

Read/write

Alarm settings
0 – alarm due to the current temperature
1 – Remember the value of the alarm, until reset by the master via Modbus

40059

58

0x3A

Constant Junction Temperature

Read/write

Value of junction temperature

40060

59

0x3B

Junction Temperature Offset

Read/write

Junction temperature offset

40061

60

0x3C

Input Settings

Read/write

Analog input mode:

0 – input disabled
1 – voltage to 2048 mV
2 – voltage to 256 mV
3 – J thermocouple
4 – K thermocouple
5 – T thermocouple
6 – N thermocouple
7 – S thermocouple
8 – R thermocouple
9 – B thermocouple
10 – Pt100 3-wire
11 – Pt100 2-wire
12 – resistance to 8 kΩ
13 - Ni100
14 – KTY81-110
15 – Pt500 3-wire
16 – Pt500 2-wire
17 – Pt1000 3-wire
18 – Pt1000 2-wire

+32 – junction temperature is taken from register 40081 "Constant junction temperature"

40062

61

0x3D

Output Settings

Read/write

Alarm output settings
0 – output is set by PLC
+256 – Output is set if value is greater than Alarm Value (register 40065) („cooling")
+512 – Output is set if value is less than Alarm Value ( register 40065) („heating")

40063

62

0x3E

Alarm Value

Read/write

Alarm value for outputs

40064

63

0x3F

Alarm Hysteresis

Read/write

The hysteresis value for alarm outputs

40065

64

0x40

Input Resistance

Read/write

Lead wire resistance for each input

Registered access

Bit Access

Modbus Address

Dec Address

Hex
Address

Register Name

Access

Description

801

800

0x320

Input

Read

Set when the sensor is connected

817

816

0x330

Alarm

Read

Alarm state

818

817

0x331

Digital Output

Read/write

State of digital output

Bit access