Module Registers
Registered Access
Modbus Address | Decimal Address | Hex Address | Register Name | Access | Description |
---|---|---|---|---|---|
30001 | 0 | 0x00 | Version/Type | Read | Version and type of the device |
30002 | 1 | 0x01 | Address | Read | Module address |
40003 | 2 | 0x02 | Baud Rate | Read/write | RS485 baud rate |
40004 | 3 | 0x03 | Stop Bits & Data Bits | Read/write | No. of stop bits & data bits |
40005 | 4 | 0x04 | Parity | Read/write | Parity bit |
40006 | 5 | 0x05 | Response Delay | Read/write | Response delay in ms |
40007 | 6 | 0x06 | Modbus Mode | Read/write | Modbus Mode (ASCII or RTU) |
40010 | 9 | 0x09 | Filter | Read/write | Measurement filtering, value from 1 to 10 |
40033 | 32 | 0x20 | Received Packets LSR (Least Significant Register) | Read/write | No. of received packets |
40034 | 33 | 0x21 | Received Packets MSR (Most Significant Register) | Read/write | |
40035 | 34 | 0x22 | Incorrect Packets LSR | Read/write | No. of received packets with error |
40036 | 35 | 0x23 | Incorrect packets MSR | Read/write | |
40037 | 36 | 0x24 | Sent Packets LSR | Read/write | No. of sent packets |
40038 | 37 | 0x25 | Sent Packets MSR | Read/write | |
30051 | 50 | 0x32 | Inputs | Read | Connected sensors |
40052 | 51 | 0x33 | Outputs | Read/write | Alarms state |
30053 | 52 | 0x34 | Temperature | Read | Temperature or measured analog |
30054 | 53 | 0x35 | Junction Temperature | Read | Module junction temperature |
30055 | 54 | 0x36 | Measurement Current | Read | Measurement current |
40056 | 55 | 0x37 | MAX Alarm Level | Read/write | If the temperature exceeds this value the corresponding alarm flag is set |
40057 | 56 | 0x38 | MIN Alarm Level | Read/write | If the temperature is below this value corresponding alarm flag is set |
40058 | 57 | 0x39 | Alarm Settings | Read/write | Alarm settings |
40059 | 58 | 0x3A | Constant Junction Temperature | Read/write | Value of junction temperature |
40060 | 59 | 0x3B | Junction Temperature Offset | Read/write | Junction temperature offset |
40061 | 60 | 0x3C | Input Settings | Read/write | Analog input mode: |
40062 | 61 | 0x3D | Output Settings | Read/write | Alarm output settings |
40063 | 62 | 0x3E | Alarm Value | Read/write | Alarm value for outputs |
40064 | 63 | 0x3F | Alarm Hysteresis | Read/write | The hysteresis value for alarm outputs |
40065 | 64 | 0x40 | Input Resistance | Read/write | Lead wire resistance for each input |
Bit Access
Modbus Address | Dec Address | Hex | Register Name | Access | Description |
---|---|---|---|---|---|
801 | 800 | 0x320 | Input | Read | Set when the sensor is connected |
817 | 816 | 0x330 | Alarm | Read | Alarm state |
818 | 817 | 0x331 | Digital Output | Read/write | State of digital output |