BACnet Object

BACnet ID

Object properties

Object type

Object name

Access

0

Mac Address

Network port

Module address

Read only

0

Present value

Analog value

UP TIME

Read only

0

Link speed

Network port

Baud rate

Read/write

9

Present value

Multi state value

MAX. FLOW SETTING

Read/write (only for MVE/MVC-2-RS)

1

1,25

1,5

1,75

2

2,25

2,5

2,75

3

3,25

3,5

3,75

4

4,25

4,5

4,75

5

0

Present value

Multi state value

TYPE OF CONTROL

Read/write

Modbus/BACnet

0-10V

2-10V

0-5V (only for EBV/MVE-2-RS)

5-10V (only for EBV/MVE-2-RS)

2-6V (only for EBV/MVE-2-RS)

6-10V (only for EBV/MVE-2-RS)

Selected by dip

0

Present value

Binary value

DIRECT/REVERSE ACTION

Read/write

1

FAILSAFE DIRECTION

15

TYPE OF STROKE (only for MVC-2-RS)

2

Present value

Binary value

ENABLE CALIBRATION

Read/write

3

Present value

Binary value

JUMPER ENABLE (ER BOARD)

Read/write (it’s visible only for EBV/MVE-2-RS)

1

Present value

Multi state value

CHANGEOVER SETTING

Read/write

Heating

Cooling

Automatic (depends on delta T)

2

Present value

Multi state value

TEMPERATURE SENSOR SELECTION

Read/write

T1 (supply)

T2 (return)

T1, T2 (delta T)

10

Present value

Multi state value

ACTUATOR SPEED

Read/write (MVC-2-RS only)

5s/mm

3s/mm

3

Present value

Multi state value

VALVE CHARACTERISTICS CONFIGURATION:

Read/write

Linear

Equipercentage

4

Present value

Multi state value

FUNCTIONS ENABLE:

Read/write

BMS

Temperature control

Temperature ΔT limit

Temperature max limit

Temperature min limit

Power control

Power limit

14

Present value

Binary value

FUNCTIONS ENABLE (ENERGY)

Read/write

5

Present value

Multi state value

Functions status

Read only

1

Present value

Analog value

MINIMUM OPENING VALVE

Read/write

2

Present value

Analog value

DIP SWITCH SETTING

Read only

6

Present value

Multi state value

VALVE TYPE:

Read/write (the visible options depend on the connected actuator)

Generic

Reserved

Reserved

Reserved

Custom energy valve

VLX6P

VLX8P

VLX1/VLX1P

VLX2/VLX2P

VLX3/VLX3P

VLX4/VLX4P

VLX5/VLX5P

Custom PICV

2FGB65B-EBV

2FGB80B-EBV

2FGB100B-EBV

2FGB125B-EBV

2FGB150B-EBV

3

Present value

Analog value

VALVE STROKE (mm*100)

Read only

4

Present value

Analog value

OVER VOLTAGE EVENTS (24 v ac > 20%) (230 v > 10%)

Read only

5

Present value

Analog value

UNDER VOLTAGE EVENTS (v ac < 20%) (230 v < 10%)

Read only

6

Present value

Analog value

FULLY OPEN EVENTS

Read only

7

Present value

Analog value

FULLY OPEN EVENTS

Read only

8

Present value

Analog value

UNEXPECTED STALL CONDITION EVENTS (within calculated stroke)

Read only

9

Present value

Analog value

UNEXPECTED STALL CONDITION EVENTS (outside calculated stroke)

Read only

10

Present value

Analog value

VALVE STROKE ERROR > MAX (60 mm)

Read only

11

Present value

Analog value

VALVE STROKE ERROR < MIN (5 mm)

Read only

7

Present value

Multi state value

ACTUATOR OPERATING MODE:

Read only

Normal running

Initial positioning

Stroke calibration

Fail safe

Manual override

4

Present value

Binary value

ACTUATOR OPERATING MODE (ERROR)

Read only

5

Present value

Binary value

(ERROR TYPE)

TEMPERATURE SENSOR 1 ERROR

Read only

6

TEMPERATURE SENSOR 2 ERROR

20

PRESSURE SENSOR 1 ERROR

21

PRESSURE SENSOR 2 ERROR

7

CALIBRATED STROKE < 5MM ERROR

8

CALIBRATED STROKE > 60MM ERROR

9

UNEXPECTED STALL (INSIDE STROKE) ERROR

10

UNEXPECTED STALL (OUTSIDE STROKE) ERROR

11

UNDERVOLTAGE

12

OVERVOLTAGE

13

CLOCK ERROR

16

Present value

Binary value

COUNTERS RESET

Read/write

13

Present value

Analog value

FEEDBACK

Read only

14

Present value

Analog value

MAX. FLOW RATE

Read/write

15

Present value

Analog value

DESIGN FLOW RATE

Read/write

2

Present value

Analog input

INPUT PRESSURE VALUE

Read only

3

Present value

Analog input

OUTPUT PRESSURE VALUE

Read only

119

Present value

Analog value

DIFFERENTIAL PRESSURE

Read only

16

Present value

Analog value

FLOW RATE SP X1

Read only

17

Present value

Analog value

VALVE POSITION Y1

Read only

18

Present value

Analog value

FLOW RATE SP X2

Read/write

19

Present value

Analog value

VALVE POSITION Y2

Read/write

20

Present value

Analog value

FLOW RATE SP X3

Read/write

21

Present value

Analog value

VALVE POSITION Y3

Read/write

22

Present value

Analog value

FLOW RATE SP X4

Read/write

23

Present value

Analog value

VALVE POSITION Y4

Read/write

24

Present value

Analog value

FLOW RATE SP X5

Read/write

25

Present value

Analog value

VALVE POSITION Y5

Read/write

26

Present value

Analog value

FLOW RATE SP X6

Read/write

27

Present value

Analog value

VALVE POSITION Y6

Read/write

28

Present value

Analog value

FLOW RATE SP X7

Read/write

29

Present value

Analog value

VALVE POSITION Y7

Read/write

30

Present value

Analog value

FLOW RATE SP X8

Read/write

31

Present value

Analog value

VALVE POSITION Y8

Read/write

32

Present value

Analog value

FLOW RATE SP X9

Read/write

34

Present value

Analog value

FLOW RATE SP X10

Read only

35

Present value

Analog value

VALVE POSITION Y10

Read only

36

Present value

Analog value

INDICATED FLOW RATE

Read/write

37

Present value

Analog value

SETPOINT DELTA T CONTROL - HEATING

Read/write

38

Present value

Analog value

SETPOINT DELTA T CONTROL - COOLING

Read/write

39

Present value

Analog value

SETPOINT SUPPLY TEMPERATURE CONTROL - HEATING

Read/write

40

Present value

Analog value

SETPOINT SUPPLY TEMPERATURE CONTROL - COOLING

Read/write

41

Present value

Analog value

SETPOINT RETURN TEMPERATURE CONTROL - HEATING

Read/write

42

Present value

Analog value

SETPOINT RETURN TEMPERATURE CONTROL - COOLING

Read/write

43

Present value

Analog value

SETPOINT MIN. DELTA T HEATING

Read/write

44

Present value

Analog value

SETPOINT MIN. DELTA T COOLING

Read/write

45

Present value

Analog value

SETPOINT MAX. SUPPLY TEMPERATURE - HEATING

Read/write

46

Present value

Analog value

SETPOINT MIN. SUPPLY TEMPERATURE - COOLING

Read/write

47

Present value

Analog value

SETPOINT MAX. RETURN TEMPERATURE - HEATING

Read/write

48

Present value

Analog value

SETPOINT MIN. RETURN TEMPERATURE - COOLING

Read/write

49

Present value

Analog value

DESIGN POWER

Read/write

50

Present value

Analog value

SET MAX. POWER LIMIT

Read/write

0

Present value

Analog input

SUPPLY TEMPERATURE VALUE

Read only if Binay Value 19 is 0 (Temperature Test Mode)

1

Present value

Analog input

RETURN TEMPERATURE VALUE

Read only if Binay Value 19 is 0 (Temperature Test Mode)

51

Present value

Analog value

DELTA T VALUE (T1 – T2)

Read only

52

Present value

Analog value

INSTANT POWER

Read only

53

Present value

Analog value

HEATING ENERGY (LSR)

Read only

53

Present value

Analog value

HEATING ENERGY (MSR)

Read only

54

Present value

Analog value

COOLING ENERGY (LSR)

Read only

54

Present value

Analog value

COOLING ENERGY (MSR)

Read only

55

Present value

Analog value

HEATING ENERGY AT 31/12 (MSR)

Read only

56

Present value

Analog value

HEATING ENERGY AT VALUE 1

Read only

57

Present value

Analog value

HEATING ENERGY AT VALUE 2

Read only

58

Present value

Analog value

HEATING ENERGY AT VALUE 3

Read only

59

Present value

Analog value

HEATING ENERGY AT VALUE 4

Read only

60

Present value

Analog value

HEATING ENERGY AT VALUE 5

Read only

61

Present value

Analog value

HEATING ENERGY AT VALUE 6

Read only

62

Present value

Analog value

HEATING ENERGY AT VALUE 7

Read only

63

Present value

Analog value

HEATING ENERGY AT VALUE 8

Read only

64

Present value

Analog value

HEATING ENERGY AT VALUE 9

Read only

65

Present value

Analog value

HEATING ENERGY AT VALUE 10

Read only

66

Present value

Analog value

HEATING ENERGY AT VALUE 11

Read only

67

Present value

Analog value

HEATING ENERGY AT VALUE 12

Read only

68

Present value

Analog value

COOLING ENERGY AT 31/12 (LSR)

Read only

68

Present value

Analog value

COOLING ENERGY AT 31/12 (MSR)

Read only

69

Present value

Analog value

COOLING ENERGY VALUE 1

Read only

70

Present value

Analog value

COOLING ENERGY VALUE 2

Read only

71

Present value

Analog value

COOLING ENERGY VALUE 3

Read only

72

Present value

Analog value

COOLING ENERGY VALUE 4

Read only

73

Present value

Analog value

COOLING ENERGY VALUE 5

Read only

74

Present value

Analog value

COOLING ENERGY VALUE 6

Read only

75

Present value

Analog value

COOLING ENERGY VALUE 7

Read only

77

Present value

Analog value

COOLING ENERGY VALUE 9

Read only

78

Present value

Analog value

COOLING ENERGY VALUE 10

Read only

79

Present value

Analog value

COOLING ENERGY VALUE 11

Read only

80

Present value

Analog value

COOLING ENERGY VALUE 12

Read only

81

Present value

Analog value

CLOCK MINUTES

Read/write

1

Local time

Device

82

Present value

Analog value

CLOCK HOURS

Read/write

1

Local time

Device

83

Present value

Analog value

CLOCK DAY

Read/write

1

Local date

Device

84

Present value

Analog value

CLOCK MONTH

Read/write

1

Local date

Device

85

Present value

Analog value

CLOCK YEAR

Read/write

1

Local date

Device

17

Present value

Binary value

FORCE FULLY CLOSE

Read/write

18

Present value

Binary value

FORCE FULLY OPEN

Read/write

19

Present value

Binary value

TEST TEMPERATURE MODE

Read/write

86

Present value

Analog value

MAX. POWER

Read/write (read-only for EBV/MVC-2-RS)

87

Present value

Analog value

MEDIA DENSITY

Read/write

88

Present value

Analog value

MEDIA SPECIFIC HEAT

Read/write

118

Present value

Analog value

DESIGN POWER DELTAT

Read/write

8

Present value

Multi state value

LOOP TYPE (P, P+I, P+I+D)

Read/write

89

Present value

Analog value

DERIVATIVE TIME (GAIN)

Read/write

90

Present value

Analog value

INTEGRAL TIME (MINUTES)

Read/write

91

Present value

Analog value

PROPORTIONAL BANDWIDTH (°C*10)

Read/write

92

Present value

Analog value

MONTH TIMESTAMP OF 31TH DECEMBER

Read only

93

Present value

Analog value

YEAR TIMESTAMP OF 31TH DECEMBER

Read only

94

Present value

Analog value

MONTH TIMESTAMP OF VALUE 1

Read only

95

Present value

Analog value

YEAR TIMESTAMP OF VALUE 1

Read only

96

Present value

Analog value

MONTH TIMESTAMP OF VALUE 2

Read only

97

Present value

Analog value

YEAR TIMESTAMP OF VALUE 2

Read only

98

Present value

Analog value

MONTH TIMESTAMP OF VALUE 3

Read only

99

Present value

Analog value

YEAR TIMESTAMP OF VALUE 3

Read only

100

Present value

Analog value

MONTH TIMESTAMP OF VALUE 4

Read only

101

Present value

Analog value

YEAR TIMESTAMP OF VALUE 4

Read only

102

Present value

Analog value

MONTH TIMESTAMP OF VALUE 5

Read only

103

Present value

Analog value

YEAR TIMESTAMP OF VALUE 5

Read only

104

Present value

Analog value

MONTH TIMESTAMP OF VALUE 6

Read only

105

Present value

Analog value

YEAR TIMESTAMP OF VALUE 6

Read only

106

Present value

Analog value

MONTH TIMESTAMP OF VALUE 7

Read only

107

Present value

Analog value

YEAR TIMESTAMP OF VALUE 7

Read only

108

Present value

Analog value

MONTH TIMESTAMP OF VALUE 8

Read only

109

Present value

Analog value

YEAR TIMESTAMP OF VALUE 8

Read only

110

Present value

Analog value

MONTH TIMESTAMP OF VALUE 9

Read only

111

Present value

Analog value

YEAR TIMESTAMP OF VALUE 9

Read only

112

Present value

Analog value

MONTH TIMESTAMP OF VALUE 10

Read only

113

Present value

Analog value

YEAR TIMESTAMP OF VALUE 10

Read only

114

Present value

Analog value

MONTH TIMESTAMP OF VALUE 11

Read only

115

Present value

Analog value

YEAR TIMESTAMP OF VALUE 11

Read only

116

Present value

Analog value

MONTH TIMESTAMP OF VALUE 12

Read only

117

Present value

Analog value

YEAR TIMESTAMP OF VALUE 12

Read only

List of BACnet object