SubmenuBoolean
Warning!
Component applicable only for the LP panel.
The SubmenuBoolean component is responsible for reading/writing and configuration of a single (one of 8 points) Boolean parameter, which is placed in the LP panel submenus. There are 6 submenus in LP panel: Temperature, Fan, Light, Blind, Alarm, and Occupancy, and each submenu can have up to 8 Boolean points.
The SubmenuBoolean component has the following slots:
Status: shows the point’s status;
Fault Cause: shows the fault cause description;
Fault Status: shows the point error status true: point read/write error);
Enable: enables or disables the point (true: enabled, false: disabled);
Poll Frequency: allows to set the reading poll frequency (fast, normal, slow);
Write Type: allows to set the writing mode (COV: only on input change, COV_PollFrequency: on the In slot change and periodically, PollFrequency: only periodically, COV_LinkSet: on the In slot change, using the "reverse following the link" function);
Trigger: allows to force sending values on rising edge;
Out: the output slot, the current value of read/write register;
In: the register input slot;
Submenu: the panel submenu number;
Point No: the submenu point number;
Point Display Name: allows to set the 4 characters submenu point LCD display name (only ASCII characters);
Point Visibility: allows to activate or deactivate the point on the display;
Point Editable: enables or disables the editing of the point;
Point True Text: allows to set the 4 characters LCD display text in the true state (only ASCII characters);
Point False Text: allows to set the 4 characters LCD display text in the false state (only ASCII characters);
Point Priority: allows to set the displaying priority on the LCD screen (starting from the lowest value);
Config Trigger: sends configuration parameters to the device components on rising edge.
The SubmenuBoolean component has the following right-click menu actions:
Set True: sets the In slot to true and sends it to the submenu point;
Set False: sets the In slot to false and sends it to the submenu point;
Write: sends the In state to the submenu point;
Read: reads the LP panel submenu point value and sets the Out slot;
Send Value: sends the user value to the submenu point without changing the input slot, from the pop-up window;
Read Config: reads the submenu point configuration parameters from the LP panel (Point Display Name, Point Visibility, Point True Text, Point False Text, Point Priority);
Write Config: writes the submenu point configuration parameters to the LP panel (Point Display Name, Point Visibility, Point True Text, Point False Text, Point Priority).