Power supply

Voltage

DC

24 V DC ± 20%, 7 W

AC

24 V AC ± 20%, 18 VA

Universal inputs






Number of inputs

4

Voltage input

Voltage measurement: 0-10 V DC

Input impedance: 100 kΩ

Measurement accuracy: ±0.1%

Measurement resolution: 3 mV at 12-bit and 1 mV at 16-bit

Current input

Current measurement: 0-20 mA

Required external resistor: 200 Ω

Measurement accuracy: ±1.1%

Measurement resolution: 15 µA at 12-bit and 5 µA at 16-bit

Digital input

Output current ~1 mA

Resistance input

Measurement of resistance: 0-1000 kΩ

Measurement resolution for 20 kΩ load: 20 Ω at 12-bit and 1 Ω at 16-bit

Measurement resolution for PT1000 and NI1000: 0.1 Ω at 16-bit

Resistance measurement method: voltage divider

Temperature input

Measurement with attached RTDs (resistance temperature detectors)

Accuracy: ±0.1˚C

The PT1000 and NI1000 sensors use 16-bit resolution

Measurement resolution

12-bit (default), 16-bit

Processing time

10 ms/channel at 12-bit

140 ms/channel at 16-bit

Digital inputs

Number of inputs

2

Type

Dry contact or fast pulse counter (saved on SD card)

Max. input frequency

100 Hz

Analog outputs



Number of outputs

3

Voltage range

0-10 V DC

Max. load current

20 mA

PWM

0.01 Hz, 0.1 Hz, 1 Hz, 10 Hz, 100 Hz

Resolution

12-bit

Accuracy

±0.5%

Triac outputs

Number of outputs

4

Load

0.5 A at 20 V AC up to max. 24 V AC

Peak load per channel

1.5 A at 20 V AC up to max. 24 V AC (30 s)

Gate control

Zero crossing turn ON

Frequency range

47 to 63 Hz

Snubber

Snubberless triac

Differential pressure sensor

Pressure range

-500 to 500 Pa/-2 to 2 inWC

Accuracy

3% of reading

Zero point accuracy

0.1 Pa/0.0004 inWC

Calibration

Air and N2

Resolution

16-bit

Damper actuator

Torque

4 Nm/35 in-lb

Angle of rotation

95° adjustable

Rotation time

95º in 95 sec (+/- 5 sec)

Fits shaft damper

8.5 to 18.2 mm (5/16 to 3/4 in)

Power supply

From controller

COM1

RS485 communication

Up to 128 devices

Communication protocol

BACnet MS/TP, Modbus RTU

Connectors

RJ45, screw connector

Baud rate

2400-115200

Vout

Max. 2.5 W, max. 40 V DC - depends on the input supply voltage

23 V DC for 24 V DC input supply voltage

33 V DC for 24 V AC input supply voltage

ETH1

Switches

2 ports, fail-safe protected

Communication protocol

BACnet IP, Modbus TCP/IP

Baud rate

10/100 Mb/s

Spigots

Number of spigots

2

Dimension

For 4 to 8 mm (1/8 to 5/16 in) tube

Ingress protection

IP rating

IP 20 for indoor installation

Temperature

Storage

-40°C to +85°C (-40°F to +185°F)

Operating

0°C to +50°C (32°F to 122°F)

Humidity

Relative

5 to 95% RH (without condensation)

Connector cables

RS485

Separable max. 2.5 mm2 (18 – 12 AWG)

RJ45

Ethernet

RJ45

Minimum cable category

UTP 5E

Housing

Material

Plastic (PC/ABS)

Dimensions

Width

196.89 mm/7.75 in

Length

112.61 mm/4.43 in

Height

77.00 mm/3.00 in