Occupancy Submenu Objects

BACnet ID

Object property

Object name

Access

Description

AV48

Present value

SETTINGS_NUMERIC1:Present Value

Read/write, memory

Current value of the parameter

AV48

Description

SETTINGS_NUMERIC1:Name

Read/write, memory

User-defined name of the parameter

AV48

4206

SETTINGS_NUMERIC1:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV48

Low limit

SETTINGS_NUMERIC1:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV48

High limit

SETTINGS_NUMERIC1:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV48

4201

SETTINGS_NUMERIC1:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV48

Out of service

SETTINGS_NUMERIC1:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV48

4200

SETTINGS_NUMERIC1:Editability

Read/write, memory

Enabling editability of the parameter

AV48

4202

SETTINGS_NUMERIC1:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV48

Units

SETTINGS_NUMERIC1:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV49

Present value

SETTINGS_NUMERIC2:Present Value

Read/write, memory

Current value of the parameter

AV49

Description

SETTINGS_NUMERIC2:Name

Read/write, memory

User-defined name of the parameter

AV49

4206

SETTINGS_NUMERIC2:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV49

Low limit

SETTINGS_NUMERIC2:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV49

High limit

SETTINGS_NUMERIC2:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV49

4201

SETTINGS_NUMERIC2:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV49

Out of service

SETTINGS_NUMERIC2:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV49

4200

SETTINGS_NUMERIC2:Editability

Read/write, memory

Enabling editability of the parameter

AV49

4202

SETTINGS_NUMERIC2:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV49

Units

SETTINGS_NUMERIC2:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV50

Present value

SETTINGS_NUMERIC3:Present Value

Read/write, memory

Current value of the parameter

AV50

Description

SETTINGS_NUMERIC3:Name

Read/write, memory

User-defined name of the parameter

AV50

4206

SETTINGS_NUMERIC3:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV50

Low limit

SETTINGS_NUMERIC3:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV50

High limit

SETTINGS_NUMERIC3:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV50

4201

SETTINGS_NUMERIC3:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV50

Out of service

SETTINGS_NUMERIC3:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV50

4200

SETTINGS_NUMERIC3:Editability

Read/write, memory

Enabling editability of the parameter

AV50

4202

SETTINGS_NUMERIC3:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV50

Units

SETTINGS_NUMERIC3:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV51

Present value

SETTINGS_NUMERIC4:Present Value

Read/write, memory

Current value of the parameter

AV51

Description

SETTINGS_NUMERIC4:Name

Read/write, memory

User-defined name of the parameter

AV51

4206

SETTINGS_NUMERIC4:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV51

Low limit

SETTINGS_NUMERIC4:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV51

High limit

SETTINGS_NUMERIC4:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV51

4201

SETTINGS_NUMERIC4:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV51

Out of service

SETTINGS_NUMERIC4:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV51

4200

SETTINGS_NUMERIC4:Editability

Read/write, memory

Enabling editability of the parameter

AV51

4202

SETTINGS_NUMERIC4:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV51

Units

SETTINGS_NUMERIC4:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV52

Present value

SETTINGS_NUMERIC5:Present Value

Read/write, memory

Current value of the parameter

AV52

Description

SETTINGS_NUMERIC5:Name

Read/write, memory

User-defined name of the parameter

AV52

4206

SETTINGS_NUMERIC5:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV52

Low limit

SETTINGS_NUMERIC5:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV52

High limit

SETTINGS_NUMERIC5:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV52

4201

SETTINGS_NUMERIC5:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV52

Out of service

SETTINGS_NUMERIC5:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV52

4200

SETTINGS_NUMERIC5:Editability

Read/write, memory

Enabling editability of the parameter

AV52

4202

SETTINGS_NUMERIC5:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV52


Units

SETTINGS_NUMERIC5:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV53

Present value

SETTINGS_NUMERIC6:Present Value

Read/write, memory

Current value of the parameter

AV53

Description

SETTINGS_NUMERIC6:Name

Read/write, memory

User-defined name of the parameter

AV53

4206

SETTINGS_NUMERIC6:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV53

Low limit

SETTINGS_NUMERIC6:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV53

High limit

SETTINGS_NUMERIC6:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV53

4201

SETTINGS_NUMERIC6:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV53

Out of service

SETTINGS_NUMERIC6:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV53

4200

SETTINGS_NUMERIC6:Editability

Read/write, memory

Enabling editability of the parameter

AV53

4202

SETTINGS_NUMERIC6:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV53

Units

SETTINGS_NUMERIC6:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV54

Present value

SETTINGSNUMERIC7:Present Value

Read/write, memory

Current value of the parameter

AV54

Description

SETTINGS_NUMERIC7:Name

Read/write, memory

User-defined name of the parameter

AV54

4206

SETTINGS_NUMERIC7:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV54

Low limit

SETTINGS_NUMERIC7:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV54

High limit

SETTINGS_NUMERIC7:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV54

4201

SETTINGS_NUMERIC7:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV54

Out of service

SETTINGS_NUMERIC7:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV54

4200

SETTINGS_NUMERIC7:Editability

Read/write, memory

Enabling editability of the parameter

AV54

4202

SETTINGS_NUMERIC7:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV54

Units

SETTINGS_NUMERIC7:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV55

Present value

SETTINGS_NUMERIC8:Present Value

Read/write, memory

Current value of the parameter

AV55

Description

SETTINGS_NUMERIC8:Name

Read/write, memory

User-defined name of the parameter

AV55

4206

SETTINGS_NUMERIC8:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV55

Low limit

SETTINGS_NUMERIC8:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV55

High limit

SETTINGS_NUMERIC8:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV55

4201

SETTINGS_NUMERIC8:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV55

Out of service

SETTINGS_NUMERIC8:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV55

4200

SETTINGS_NUMERIC8:Editability

Read/write, memory

Enabling editability of the parameter

AV55

4202

SETTINGS_NUMERIC8_POINT ACTIV

Read/write, memory

Number of displayed decimal places from 0 to 3

AV55

Units

SETTINGS_NUMERIC8:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

BV48

Present value

SETTINGS_BOOLEAN1:Present Value

Read/write, memory

Current value of the parameter

BV48

Description

SETTINGS_BOOLEAN1:Name

Read/write, memory

User-defined name of the parameter

BV48

4203

SETTINGS_BOOLEAN1:True Text

Read/write, memory

Text for the parameter’s true value

BV48

4204

SETTINGS_BOOLEAN1:False Text

Read/write, memory

Text for the parameter’s false value

BV48

4201

SETTINGS_BOOLEAN1:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV48

Out of

service

SETTINGS_BOOLEAN1:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV48

4200

SETTINGS_BOOLEAN1:Editability

Read/write, memory

Enabling editability of the parameter

BV49

Present value

SETTINGS_BOOLEAN2:Present Value

Read/write, memory

Current value of the parameter

BV49

Description

SETTINGS_BOOLEAN2:Name

Read/write, memory

User-defined name of the parameter

BV49

4203

SETTINGS_BOOLEAN2:True Text

Read/write, memory

Text for the parameter’s true value

BV49

4204

SETTINGS_BOOLEAN2:False Text

Read/write, memory

Text for the parameter’s false value

BV49

4201

SETTINGS_BOOLEAN2:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV49

Out of service

SETTINGS_BOOLEAN2:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV49

4200

SETTINGS_BOOLEAN2:Editability

Read/write, memory

Enabling editability of the parameter

BV50

Present value

SETTINGS_BOOLEAN3:Present Value

Read/write, memory

Current value of the parameter

BV50

Description

SETTINGS_BOOLEAN3:Name

Read/write, memory

User-defined name of the parameter

BV50

4203

SETTINGS_BOOLEAN3:True Text

Read/write, memory

Text for the parameter’s true value

BV50

4204

SETTINGS_BOOLEAN3:False Text

Read/write, memory

Text for the parameter’s false value

BV50

4201

SETTINGS_BOOLEAN3:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV50

Out of service

SETTINGS_BOOLEAN3:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV50

4200

SETTINGS_BOOLEAN3:Editability

Read/write, memory

Enabling editability of the parameter

BV51

Present value

SETTINGS_BOOLEAN4:Present Value

Read/write, memory

Current value of the parameter

BV51

Description

SETTINGS_BOOLEAN4:Name

Read/write, memory

User-defined name of the parameter

BV51

4203

SETTINGS_BOOLEAN4:True Text

Read/write, memory

Text for the parameter’s true value

BV51

4204

SETTINGS_BOOLEAN4:False Text

Read/write, memory

Text for the parameter’s false value

BV51

4201

SETTINGS_BOOLEAN4:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV51

Out of service

SETTINGS_BOOLEAN4:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV51

4200

SETTINGS_BOOLEAN4:Editability

Read/write, memory

Enabling editability of the parameter

BV52

Present value

SETTINGS_BOOLEAN5:Present Value

Read/write, memory

Current value of the parameter

BV52

Description

SETTINGS_BOOLEAN5:Name

Read/write, memory

User-defined name of the parameter

BV52

4203

SETTINGS_BOOLEAN5:True Text

Read/write, memory

Text for the parameter’s true value

BV52

4204

SETTINGS_BOOLEAN5:False Text

Read/write, memory

Text for the parameter’s false value

BV52

4201

SETTINGS_BOOLEAN5:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV52

Out of service

SETTINGS_BOOLEAN5:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV52

4200

SETTINGS_BOOLEAN5:Editability

Read/write, memory

Enabling editability of the parameter

BV53

Present value

SETTINGS_BOOLEAN6:Present Value

Read/write, memory

Current value of the parameter

BV53

Description

SETTINGS_BOOLEAN6:Name

Read/write, memory

User-defined name of the parameter

BV53

4203

SETTINGS_BOOLEAN6:True Text

Read/write, memory

Text for the parameter’s true value

BV53

4204

SETTINGS_BOOLEAN6:False Text

Read/write, memory

Text for the parameter’s false value

BV53

4201

SETTINGS_BOOLEAN6:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV53

Out of service

SETTINGS_BOOLEAN6:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV53

4200

SETTINGS_BOOLEAN6:Editability

Read/write, memory

Enabling editability of the parameter

BV54

Present value

SETTINGS_BOOLEAN7:Present Value

Read/write, memory

Current value of the parameter

BV54

Description

SETTINGS_BOOLEAN7:Name

Read/write, memory

User-defined name of the parameter

BV54

4203

SETTINGS_BOOLEAN7:True Text

Read/write, memory

Text for the parameter’s true value

BV54

4204

SETTINGS_BOOLEAN7:False Text

Read/write, memory

Text for the parameter’s false value

BV54

4201

SETTINGS_BOOLEAN7:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV54

Out of service

SETTINGS_BOOLEAN7:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV54

4200

SETTINGS_BOOLEAN7:Editability

Read/write, memory

Enabling editability of the parameter

BV55

Present value

SETTINGS_BOOLEAN8:Present Value

Read/write, memory

Current value of the parameter

BV55

Description

SETTINGS_BOOLEAN8:Name

Read/write, memory

User-defined name of the parameter

BV55

4203

SETTINGS_BOOLEAN8:True Text

Read/write, memory

Text for the parameter’s true value

BV55

4204

SETTINGS_BOOLEAN8:False Text

Read/write, memory

Text for the parameter’s false value

BV55

4201

SETTINGS_BOOLEAN8:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV55

Out of service

SETTINGS_BOOLEAN8:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV55

4200

SETTINGS_BOOLEAN8:Editability

Read/write, memory

Enabling editability of the parameter


List of occupancy submenu objects