Light Submenu Objects

BACnet ID

Object Property

Object Name

Access

Description

AV 24

Present value

LIGHT_NUMERIC1

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 24

Description

LIGHT_NUMERIC1

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 24

Step increment

LIGHT_NUMERIC1

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 24

Low limit

LIGHT_NUMERIC1

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 24

High limit

LIGHT_NUMERIC1

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 24

4201

LIGHT_NUMERIC1

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

AV 24

Out of service

LIGHT_NUMERIC1

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 24

4200

LIGHT_NUMERIC1

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 24

4202

LIGHT_NUMERIC1

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 24

Units

LIGHT_NUMERIC1

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 25

Present value

LIGHT_NUMERIC2

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 25

Description

LIGHT_NUMERIC2

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 25

Step increment

LIGHT_NUMERIC2

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 25

Low limit

LIGHT_NUMERIC2

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 25

High limit

LIGHT_NUMERIC2

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 25

4201

LIGHT_NUMERIC2

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

AV 25

Out of service

LIGHT_NUMERIC2

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 25

4200

LIGHT_NUMERIC2

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 25

4202

LIGHT_NUMERIC2

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 25

Units

LIGHT_NUMERIC2

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 26

Present value

LIGHT_NUMERIC3

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 26

Description

LIGHT_NUMERIC3

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 26

Step increment

LIGHT_NUMERIC3

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 26

Low limit

LIGHT_NUMERIC3

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 26

High limit

LIGHT_NUMERIC3

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 26

4201

LIGHT_NUMERIC3

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

AV 26

Out of service

LIGHT_NUMERIC3

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 26

4200

LIGHT_NUMERIC3

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 26

4202

LIGHT_NUMERIC3

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 26

Units

LIGHT_NUMERIC3

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 27

Present value

LIGHT_NUMERIC4

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 27

Description

LIGHT_NUMERIC4

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 27

Step increment

LIGHT_NUMERIC4

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 27

Low limit

LIGHT_NUMERIC4

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 27

High limit

LIGHT_NUMERIC4

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 27

4201

LIGHT_NUMERIC4

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

AV 27

Out of service

LIGHT_NUMERIC4

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 27

4200

LIGHT_NUMERIC4

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 27

4202

LIGHT_NUMERIC4

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 27

Units

LIGHT_NUMERIC4

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 28

Present value

LIGHT_NUMERIC5

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 28

Description

LIGHT_NUMERIC5

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 20

Step increment

LIGHT_NUMERIC5

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 28

Low limit

LIGHT_NUMERIC5

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 28

High limit

LIGHT_NUMERIC5

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 28

4201

LIGHT_NUMERIC5

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

AV 28

Out of service

LIGHT_NUMERIC5

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 28

4200

LIGHT_NUMERIC5

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 28

4202

LIGHT_NUMERIC5

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 28

Units

LIGHT_NUMERIC5

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 29

Present value

LIGHT_NUMERIC6

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 29

Description

LIGHT_NUMERIC6

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 29

Step increment

LIGHT_NUMERIC6

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 29

Low limit

LIGHT_NUMERIC6

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 29

High limit

LIGHT_NUMERIC6

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 29

4201

LIGHT_NUMERIC6

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

AV 29

Out of service

LIGHT_NUMERIC6

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 29

4200

LIGHT_NUMERIC6

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 29

4202

LIGHT_NUMERIC6

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 29

Units

LIGHT_NUMERIC6

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 30

Present value

LIGHTNUMERIC7

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 30

Description

LIGHT_NUMERIC7

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 30

Step increment

LIGHT_NUMERIC7

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 30

Low limit

LIGHT_NUMERIC7

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 30

High limit

LIGHT_NUMERIC7

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 30

4201

LIGHT_NUMERIC7

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

AV 30

Out of service

LIGHT_NUMERIC7

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 30

4200

LIGHT_NUMERIC7

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 30

4202

LIGHT_NUMERIC7

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 30

Units

LIGHT_NUMERIC7

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 31

Present value

LIGHT_NUMERIC8

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 31

Description

LIGHT_NUMERIC8

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 31

Step increment

LIGHT_NUMERIC8

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 31

Low limit

LIGHT_NUMERIC8

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 31

High limit

LIGHT_NUMERIC8

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 31

4201

LIGHT_NUMERIC8

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

AV 31

Out of service

LIGHT_NUMERIC8

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 31

4200

LIGHT_NUMERIC8

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 31

4202

LIGHT_NUMERICE8

POINT ACTIV

Read / write

Memory

Number of decimal places from 0 to 3

AV 31

Units

LIGHT_NUMERIC8

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

BV 31

Present value

LIGHT_BOOLEAN1

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 31

Description

LIGHT_BOOLEAN1

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 24

True text

LIGHT_BOOLEAN1

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 24

False text

LIGHT_BOOLEAN1

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 24

4201

LIGHT_BOOLEAN1

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

BV 24

Out of

service

LIGHT_BOOLEAN8

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 24

4200

LIGHT_BOOLEAN8

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 25

Present value

LIGHT_BOOLEAN2

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 25

Description

LIGHT_BOOLEAN2

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 25

True text

LIGHT_BOOLEAN2

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 25

False text

LIGHT_BOOLEAN2

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 25

4201

LIGHT_BOOLEAN2

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

BV 25

Out of service

LIGHT_BOOLEAN2

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 25

4200

LIGHT_BOOLEAN2

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 26

Present value

LIGHT_BOOLEAN3

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 26

Description

LIGHT_BOOLEAN3

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 26

True text

LIGHT_BOOLEAN3

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 26

False text

LIGHT_BOOLEAN3

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 26

4201

LIGHT_BOOLEAN3

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying  in the submenu

BV 26

Out of service

LIGHT_BOOLEAN3

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 26

4200

LIGHT_BOOLEAN3

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 27

Present value

LIGHT_BOOLEAN4

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 27

Description

LIGHT_BOOLEAN4

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 27

True text

LIGHT_BOOLEAN4

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 27

False text

LIGHT_BOOLEAN4

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 27

4201

LIGHT_BOOLEAN4

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

BV 27

Out of service

LIGHT_BOOLEAN4

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 27

4200

LIGHT_BOOLEAN4

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 28

Present value

LIGHT_BOOLEAN5

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 28

Description

LIGHT_BOOLEAN5

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 28

True text

LIGHT_BOOLEAN5

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 28

False text

LIGHT_BOOLEAN5

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 28

4201

LIGHT_BOOLEAN5

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

BV 28

Out of service

LIGHT_BOOLEAN5

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 28

4200

LIGHT_BOOLEAN5

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 29

Present value

LIGHT_BOOLEAN6

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 29

Description

LIGHT_BOOLEAN6

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 29

True text

LIGHT_BOOLEAN6

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 29

False text

LIGHT_BOOLEAN6

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 29

4201

LIGHT_BOOLEAN6

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

BV 29

Out of service

LIGHT_BOOLEAN6

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 29

4200

LIGHT_BOOLEAN6

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 30

Present value

LIGHT_BOOLEAN7

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 30

Description

LIGHT_BOOLEAN7

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 30

True text

LIGHT_BOOLEAN7

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 30

False text

LIGHT_BOOLEAN7

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 30

4201

LIGHT_BOOLEAN7

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

BV 30

Out of service

LIGHT_BOOLEAN7

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 30

4200

LIGHT_BOOLEAN7

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 31

Present value

LIGHT_BOOLEAN8

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 31

Description

LIGHT_BOOLEAN8

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 31

True text

LIGHT_BOOLEAN8

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 31

False text

LIGHT_BOOLEAN8

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 31

4201

LIGHT_BOOLEAN8

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

BV 31

Out of service

LIGHT_BOOLEAN8

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 31

4200

LIGHT_BOOLEAN8

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

Light submenu objects