AAC20 - Application - Error during application upload in the iC Tool
Issue
Sometimes, during application upload in the iC Tool, the Console displays an error log: Could not upload application to the device.
Solution
In this case, the reason for the error log in the Console is a missing ConstFI component from the control kit. To solve this issue, before uploading the application, upload required kits to the device. A list of the required kits is available by opening the app.sax file in any text editor.
After uploading required kits, upload the app.sax file using the Application Manager.