Breadcrumbs

Temperature Submenu Registers

Modbus address

Decimal address

Hex address

Register name

Access

Description

40501

500

0x13F

TEMPERATURE_MENU_ACTIVE_POINTS

Read/write, memory

Number of active parameters in the submenu

40059

58

0x3A

TEMPERATURE_NUMERIC1_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40504

503

0x1F7

TEMPERATURE_NUMERIC1_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40506

505

0x1F9

TEMPERATURE_NUMERIC1_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40507

506

0x1FA

TEMPERATURE_NUMERIC1_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40508

507

0x1FB

TEMPERATURE_NUMERIC1_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40509

508

0x1FC

TEMPERATURE_NUMERIC1_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40510

509

0x1FD

TEMPERATURE_NUMERIC1_CONFIGURATION

Read/write, memory

Bit

Parameter

0

1

0

Active

Not active (default)

Active

2

First point active

No decimal place (default)

One decimal place active

3

Second point active

No decimal place (default)

Two decimal places active

4

Third point active

No decimal place (default)

Three decimal places active

6

C unit active

Not active (default)

Active

7

F unit active

Not active (default)

Active

8

Pa unit active

Not active (default)

Active

9

Lx unit active

Not active (default)

Active

10

ppm unit active

Not active (default)

Active

11

m3/h unit active

Not active (default)

Active

12

%Rh unit active

Not active (default)

Active

13

l/s unit active

Not active (default)

Active

14

% unit active

Not active (default)

Active

15

h unit active

Not active (default)

Active

40060

59

0x3B

TEMPERATURE_NUMERIC2_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40513

512

0x200

TEMPERATURE_NUMERIC2_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40515

514

0x202

TEMPERATURE_NUMERIC2_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40516

515

0x203

TEMPERATURE_NUMERIC2_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40517

516

0x204

TEMPERATURE_NUMERIC2_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40518

517

0x205

TEMPERATURE_NUMERIC2_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40519

518

0x1FD

TEMPERATURE_NUMERIC2_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_NUMERIC1_CONFIGURATION (40510)

40061

60

0x3C

TEMPERATURE_NUMERIC3_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40522

521

0x209

TEMPERATURE_NUMERIC3_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40524

523

0x20B

TEMPERATURE_NUMERIC3_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40525

524

0x20C

TEMPERATURE_NUMERIC3_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40526

525

0x20D

TEMPERATURE_NUMERIC3_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40527

526

0x20E

TEMPERATURE_NUMERIC3_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40528

527

0x20F

TEMPERATURE_NUMERIC3_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_NUMERIC1_CONFIGURATION (40510)

40062

61

0x3D

TEMPERATURE_NUMERIC4_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40531

530

0x212

TEMPERATURE_NUMERIC4_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40533

532

0x214

TEMPERATURE_NUMERIC4_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40534

533

0x215

TEMPERATURE_NUMERIC4_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40535

534

0x216

TEMPERATURE_NUMERIC4_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40536

535

0x217

TEMPERATURE_NUMERIC4_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40537

536

0x218

TEMPERATURE_NUMERIC4_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_NUMERIC1_CONFIGURATION (40510)

40063

62

0x3E

TEMPERATURE_NUMERIC5_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40540

539

0x21B

TEMPERATURE_NUMERIC5_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40542

541

0x21D

TEMPERATURE_NUMERIC5_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40543

542

0x21E

TEMPERATURE_NUMERIC5_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40544

543

0x21F

TEMPERATURE_NUMERIC5_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40545

544

0x220

TEMPERATURE_NUMERIC5_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40546

545

0x221

TEMPERATURE_NUMERIC5_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_NUMERIC1_CONFIGURATION (40510)

40064

63

0x3F

TEMPERATURE_NUMERIC6_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40549

548

0x224

TEMPERATURE_NUMERIC6_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40551

550

0x226

TEMPERATURE_NUMERIC6_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40552

551

0x227

TEMPERATURE_NUMERIC6_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40553

552

0x228

TEMPERATURE_NUMERIC6_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40554

553

0x229

TEMPERATURE_NUMERIC6_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40555

554

0x22A

TEMPERATURE_NUMERIC6_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_NUMERIC1_CONFIGURATION (40510)

40065

64

0x40

TEMPERATURE_NUMERIC7_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40558

557

0x22D

TEMPERATURE_NUMERIC7_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40560

559

0x22F

TEMPERATURE_NUMERIC7_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40561

560

0x230

TEMPERATURE_NUMERIC7_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40562

561

0x231

TEMPERATURE_NUMERIC7_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40563

562

0x232

TEMPERATURE_NUMERIC7_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40564

563

0x233

TEMPERATURE_NUMERIC7_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_NUMERIC1_CONFIGURATION (40510)

40066

65

0x41

TEMPERATURE_NUMERIC8_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40567

566

0x236

TEMPERATURE_NUMERIC8_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40569

568

0x238

TEMPERATURE_NUMERIC8_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40570

569

0x239

TEMPERATURE_NUMERIC8_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40571

570

0x240

TEMPERATURE_NUMERIC8_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40572

571

0x241

TEMPERATURE_NUMERIC8_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40573

572

0x242

TEMPERATURE_NUMERIC8_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_NUMERIC1_CONFIGURATION (40510)

40108

107

0x6B

TEMPERATURE_BOOLEAN_ALL_PRESENT_VALUE

Read/write, memory

Bit

Parameter

0

1

0

BOOLEAN1_PRESENT_VALUE

Not active (default)

Active

1

BOOLEAN2_PRESENT_VALUE

Not active (default)

Active

6

BOOLEAN7_PRESENT_VALUE

Not active (default)

Active

7

BOOLEAN8_PRESENT_VALUE

Not active (default)

Active

40122

121

0x79

TEMPERATURE_BOOLEAN1_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40576

575

0x23F

TEMPERATURE_BOOLEAN1_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40578

577

0x241

TEMPERATURE_BOOLEAN1_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

40580

579

0x243

TEMPERATURE_BOOLEAN1_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40582

581

0x245

TEMPERATURE_BOOLEAN1_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40583

582

0x246

TEMPERATURE_BOOLEAN1_CONFIGURATION

Read/write, memory

Bit

Parameter

0

1

0

ACTIVE

Not active (default)

Active

1

EDITABLE

Not editable

Editable (default)

40123

122

0x7A

TEMPERATURE_BOOLEAN2_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40586

585

0x249

TEMPERATURE_BOOLEAN2_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40588

587

0x251

TEMPERATURE_BOOLEAN2_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

40590

589

0x253

TEMPERATURE_BOOLEAN2_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40592

591

0x255

TEMPERATURE_BOOLEAN2_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40593

592

0x256

TEMPERATURE_BOOLEAN2_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_BOOLEAN1_CONFIGURATION (40583)

40124

123

0x7B

TEMPERATURE_BOOLEAN3_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40596

595

0x253

TEMPERATURE_BOOLEAN3_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40598

597

0x255

TEMPERATURE_BOOLEAN3_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

40600

599

0x257

TEMPERATURE_BOOLEAN3_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40602

601

0x259

TEMPERATURE_BOOLEAN3_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40603

602

0x25A

TEMPERATURE_BOOLEAN3_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_BOOLEAN1_CONFIGURATION (40583)

40125

124

0x7C

TEMPERATURE_BOOLEAN4_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40606

605

0x25D

TEMPERATURE_BOOLEAN4_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40608

607

0x25F

TEMPERATURE_BOOLEAN4_TRUE_TEXT (32–bits)

Read/write, memory

Text for the parameter’s true value

40610

609

0x261

TEMPERATURE_BOOLEAN4_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40612

611

0x263

TEMPERATURE_BOOLEAN4_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40613

612

0x264

TEMPERATURE_BOOLEAN4_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_BOOLEAN1_CONFIGURATION (40583)

40126

125

0x7D

TEMPERATURE_BOOLEAN5_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40616

615

0x267

TEMPERATURE_BOOLEAN5_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40618

617

0x269

TEMPERATURE_BOOLEAN5_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

40620

619

0x271

TEMPERATURE_BOOLEAN5_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40622

621

0x273

TEMPERATURE_BOOLEAN5_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40623

622

0x274

TEMPERATURE_BOOLEAN5_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_BOOLEAN1_CONFIGURATION (40583)

40127

126

0x7E

TEMPERATURE_BOOLEAN6 PRESENT_VALUE_

Read/write, memory

Current value of the parameter

40626

625

0x271

TEMPERATURE_BOOLEAN6_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40628

627

0x273

TEMPERATURE_BOOLEAN6_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

40630

629

0x275

TEMPERATURE_BOOLEAN6_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40632

631

0x277

TEMPERATURE_BOOLEAN6_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40633

632

0x278

TEMPERATURE_BOOLEAN6_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_BOOLEAN1_CONFIGURATION (40583)

40128

127

0x7F

TEMPERATURE_BOOLEAN7_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40636

635

0x27B

TEMPERATURE_BOOLEAN7_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40638

637

0x27D

TEMPERATURE_BOOLEAN7_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

40640

639

0x27F

TEMPERATURE_BOOLEAN7_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40642

641

0x281

TEMPERATURE_BOOLEAN7_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40643

642

0x282

TEMPERATURE_BOOLEAN7_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_BOOLEAN1_CONFIGURATION (40583)

40129

128

0x80

TEMPERATURE_BOOLEAN8_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40646

645

0x285

TEMPERATURE_BOOLEAN8_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40648

647

0x287

TEMPERATURE_BOOLEAN8_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

40650

649

0x289

TEMPERATURE_BOOLEAN8_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40652

651

0x28B

TEMPERATURE_BOOLEAN8_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40653

652

0x28C

TEMPERATURE_BOOLEAN8_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_BOOLEAN1_CONFIGURATION (40583)


List of temperature submenu registers