In the Control Point panel’s VAV submenu dedicated to the VAV application, it is possible to configure the following parameters:
DEVT: allows to choose a device type between VAV and VVT;
-
DeviceType:
-
Modbus register: 00107;
-
BACnet object: BV6, property: Present Value;
-
|
Register/object value |
Value |
|---|---|
|
0/false |
VAV |
|
1/true |
VVT |
REHT: allows to set a reheater type;
-
ReheaterType:
-
Modbus register: 40273;
-
BACnet object: MSV12, property: Present Value;
-
|
Register/object value |
Value |
|---|---|
|
1 |
None |
|
2 |
Time proportional (PWM) |
|
3 |
Staged |
|
4 |
Float |
PERT: allows to set a perimeter type;
-
PerimeterType:
-
Modbus register: 40274;
-
BACnet object: MSV13, property: Present Value;
-
|
Register/object value |
Value |
|---|---|
|
1 |
None |
|
2 |
Time proportional (PWM) |
|
3 |
Digital |
FANT: allows to set a fan type;
-
FanType:
-
Modbus register: 40272;
-
BACnet object: MSV11, property: Present Value;
-
|
Register/object value |
Value |
|---|---|
|
1 |
None |
|
2 |
Series |
|
3 |
Parallel |
SPCS: allows to set a source for temperature readings;
-
TemperatureInputSelector:
-
Modbus register: 40284;
-
BACnet object: MSV23, property: Present Value;
-
|
Register/object value |
Value |
|---|---|
|
1 |
Panel |
|
2 |
Input |
|
3 |
Network |
SPCT: allows to set a space temperature type on the universal input 2;
-
U2SpaceTempType:
-
Modbus register: 40283;
-
BACnet object: MSV22, property: Present Value;
-
DIST: allows to set a discharge temperature type on the universal input 1;
-
U1DischargeTempType:
-
Modbus register: 40282;
-
BACnet object: MSV21, property: Present Value;
-
|
Register/object value |
Value |
|---|---|
|
1 |
Voltage measurement |
|
2 |
Current |
|
3 |
Resistance input |
|
4 |
10K3A1 NTC |
|
5 |
10K4A1 NTC |
|
6 |
10K NTC Carel |
|
7 |
20K6A1 NTC |
|
8 |
2,2K3A1 NTC |
|
9 |
3K3A1 NTC |
|
10 |
30K6A1 NTC |
|
11 |
SIE1 |
|
12 |
TAC1 |
|
13 |
SAT1 |
|
14 |
PT1000 |
|
15 |
NI1000 |
|
16 |
NI1000 21C |
|
17 |
NI1000 LG F |
|
18 |
10K Type2 NTC F |
|
19 |
10K Type3 NTC F |
|
20 |
20K NTC F |
|
21 |
3K NTC F |
|
22 |
PT1000 F |
|
23 |
NI1000 32F |
|
24 |
NI1000 70F |
OFFS: allows to set a source for setpoint offset settings;
-
SetpointOffsetSelector:
-
Modbus register: 40285;
-
BACnet object: MSV24, property: Present Value;
-
CO2S: allows to set a source for CO2 readings;
-
CO2InputSelector:
-
Modbus register: 40286;
-
BACnet object: MSV25, property: Present Value;
-
|
Register/object value |
Value |
|---|---|
|
1 |
Panel |
|
2 |
Input |
|
3 |
Network |
CO2R: allows to set a range for CO2 alarm settings;
-
CO2SensorRange:
-
Modbus register: 40239;
-
BACnet object: AV38, property: Present Value;
-
|
Register/object value |
Value |
|---|---|
|
Min. |
0 |
|
Max. |
10000 |
HPRI: allows to select a priority order for the heat source;
-
HeaterPriority:
-
Modbus register: 40275;
-
BACnet object: MSV14, property: Present Value;
-
|
Register/object value |
Value |
|---|---|
|
1 |
Reheater |
|
2 |
Perimeter |
|
3 |
Simultaneous |
DUHT: allows to enable a possibility to use one or two heat sources;
-
DualHeat:
-
Modbus register: 00109;
-
BACnet object: BV8, property: Present Value;
-
|
Register/object value |
Value |
|---|---|
|
0/false |
No |
|
1/true |
Yes |
OCCT: allows to select an occupancy contact type;
-
PresenceSensorInvert:
-
Modbus register: 00105;
-
BACnet object: BV4, property: Present Value;
-
WNDT: allows to select a window contact type;
-
WindowContactInvert:
-
Modbus register: 00106;
-
BACnet object: BV5, property: Present Value;
-
DAMP: allows to set a damper actuator’s direction to open to clockwise or counterclockwise;
-
DamperDirection:
-
Modbus register: 00110;
-
BACnet object: BV9, property: Present Value.
-
|
Register/object value |
Value |
|---|---|
|
0/false |
Clockwise |
|
1/true |
Counterclockwise |