LIVE_TIME (AI 0)

The LIVE_TIME is an Analog Input object number 0, which value contains the uptime value in seconds. After the power supply failure or panel restart, the value of this object resets, and the uptime counts from 0.

SENSORS (MI 1)

The SENSOR is a Multistate Input object number 1, which value contains information about the configuration of sensors, which are already built into the room panel.


Object Value

Temperature
Sensor

Humidity
Sensor

CO2
Sensor

Hardware Name

1

Built-in

No sensor

No sensor

iSMA-B-LP

2

Built-in

Built-in

No sensor

iSMA-B-LP-H

3

Built-in

No sensor

Built-in

iSMA-B-LP-C

4

Built-in

Built-in

Built-in

iSMA-B-LP-HC

Sensors configuration

BEEPER (BO 0)

The BEEPER is a Boolean Output object number 0, which status activates/deactivates the beeper sound. If the status of this object is true, any time a button is pushed it is signalized by the beeper sound. In addition, the beeper can be also used for the CO2 alarm signalization. The default status of this object is true (beeper active).

TIME_FORMAT (BO 1)

The TIME_FORMAT is a Boolean Output object number 1, which status defines the time format display. If the status of this object is true, the time is set to the 12 h format, otherwise the time is displayed in the 24 h format (default).

If the clock is set to the 12 h format, and it receives hour values in the 24 h format, the AM and PM icons are displayed according to calculation. The semicolon, which separates the hour and minute section in the clock, flashes with 1 Hz frequency.

BACKGROUND_ILLUMINATION _LCD_ACTIVE (BO 3)

The BACKGROUND_ILLUMINATION _LCD_ACTIVE is a Boolean Output object number 3, which status activates or deactivates an LCD illumination. If the status of this object is true, the LCD display is illuminated with intensity depending on the values stored in objects dedicated to particular room panel modes. If the status of this object is false, the LCD display is not illuminated in any mode. The default status of this object is true.

BACKGROUND_ILLUMINATION_KEY_PAD_ACTIVE (BO 4)

The BACKGROUND_ILLUMINATION_KEY_PAD_ACTIVE is a Boolean Output object number 4, which status activates or deactivates the keypad illumination. If the status of this object is true, the keypad is illuminated with intensity depending on the values stored in objects dedicated to particular room panel modes. If the status of this object is false, the keypad is not illuminated in any mode. The default status of this object is false (keypad not illuminated).

CO2_IN_ALARM_FLASHING_LCD (BO 5)

The CO2_IN_ALARM_FLASHING_LCD is a Boolean Output object number 5, which status activates or deactivates flashing of an LCD illumination during a CO2 alarm. If the status of this object is true, the CO2 alarm is indicated by flashing of the LCD illumination. For more details about this function please refer to the CO2 Sensor section. The default status of this object is false (function deactivated).

CO2_IN_ALARM_BUZZER (BO 6)

The CO2_IN_ALARM_BUZZER is a Boolean Output object number 6, which status activates or deactivates a beeper sound during a CO2 alarm. If the status of this object is true, the CO2 alarm is indicated by the beeper, which emits sound with 1 Hz frequency. For more details about this function please refer to the CO2 Sensor section. The default value of this object is false (function deactivated).

CO2_IN_ALARM_SHOW_HIGH (BO 7)

The CO2_IN_ALARM_SHOW_HIGH is a Boolean Output object number 7, which status activates or deactivates displaying a HIGH label on the LCD during a CO2 alarm. If the status of this object is true, and the CO2 alarm is active, the LCD display shows a CO2 sensor actual value on the 8-segment display block and the blinking text “HIGH” on the 14-segment display block. The default status of this object is false (function deactivated).

SUBMENU_ICON_DISPLAY_OFF (BO 8)

The SUBMENU_ICON_DISPLAY_OFF is a Boolean Output object number 8, which status activates or deactivates displaying submenu icons. If the status of this object is true, all submenu icons are hidden, even in case if one or more submenus contain active points. The user can enter an active submenu (with at least one active point) and proceed normal operation, but its icon is invisible in the main menu display view. The default status of this object is false.

PANEL_OFF (BO 9)

The PANEL_OFF is a Boolean Output object number 9, which status activates or deactivates the room panel. If the status of this object is true, the room panel is inactive, which means that it is impossible to control the room panel locally (access to submenus and parameters configuration is blocked: the keypad is deactivated). The LCD display and background illumination are also off. The main menu is not displayed. The room panel works as the temperature sensor (or multisensor, if either a CO2 sensor or a humidity sensor is built-in). If the status of this object is false, the room panel works in normal mode (functions for local control are active). The default status of this object is false (Panel ON).

KEY_PAD_OFF (BO 10)

The KEY_PAD_OFF is a Boolean Output object number 10, which status activates or deactivates the keypad. If the status of this object is true, the keypad is deactivated. Pushing any button once emits a beeper sound (if the beeper is activated), and activates the Active Mode (set a background illumination level) but the submenu access is blocked (it is impossible to enter any menu, or to change any parameters and settings). The Main Menu is displayed. The default status of this object is false (keypad is on).

FLASHING_LCD (BO 11)

The FLASHING_LCD is a Boolean Output object number 11, which status is responsible for the LCD display flashing activation. If the status of this object is true, the LCD display flashes with the frequency stored in the LCD_ICON_FLASHING_TIME object (AO 14). The flashing brightness level changes from 0% to the maximum value from the object values:

BACKGROUND_ILLUMINATION_LCD_FOR_ACTIVE_MODE (AO 3)

BACKGROUND_ILLUMINATION_LCD_FOR_IDLE_MODE (AO 4)

BACKGROUND_ILLUMINATION_LCD_FOR_STANDY_MODE (AO 5)

The default status of this object is false (LCD flashing inactive).

FLASHING_KEY_PAD (BO 12)

The FLASHING_KEY_PAD is a Boolean Output object number 12, which status is responsible for the keypad flashing activation. If the status of this object is true, the keypad flashes with the frequency stored in the LCD_ICON_FLASHING object. The flashing brightness level changes from 0% to the maximum value from the objects:

BACKGROUND_ILLUMINATION_KEY_PAD_FOR_ACTIVE_MODE (AO 8)

BACKGROUND_ILLUMINATION_KEY_PAD_FOR_IDLE_MODE (AO 9)

BACKGROUND_ILLUMINATION_KEY_PAD_FOR_STANDBY_MODE (AO 10)

The default status of this object is false (keypad flashing inactive).