Skip to main content
Skip table of contents

IO Modules - Sensors - Configuring NTC 10k type 2 temperature sensor in Celsius

Introduction

Configuring an NTC 10k Type 2 temperature sensor in Celsius for the iSMA contollers can be challenging at first sight because the specific sensor type is not directly available in the built-in options. However, a similar characteristic, NTC10K3A1, can be used effectively. This guide explains how to do this.

Best Practice

  • For the NTC 10k Type 2 sensor you use the NTC10K3A1 characteristic. Despite the slight differences in resistance values between the NTC 10k Type 2 sensor and the NTC10K3A1 characteristic, these differences are minimal and will not significantly impact the accuracy of temperature readings.

  • Always cross-check the characteristics of your NTC 10k Type 2 sensor against the NTC10K3A1 characteristic to ensure compatibility. For the commonly used temperature ranges in building automation (5 - 85 degrees Celsius), the NTC10K3A1 characteristic will provide accurate readings. You see the comparison table below.

NTC10K3A1

NTC 10k Type 2

°C

Ω

°C

Ω

-40

335671

-39,44

323839

-35

241840

-35

242427

-30

176683

-30,56

183068

-25

131251

-25

130306

-20

96974

-20,56

100218

-15

72895

-15

72911

-10

55298

-10,56

57017

-5

42314

-5

42317

0

32650

-0,56

33599

5

25396

5

25395

10

19904

10,56

19376

15

15714

15

15714

20

12494

20,56

12182

25

10000

25

10000

30

8056

30,56

7866

35

6530

35

6530

40

5325

40,56

5207

45

4367

45

4367

50

3601

50,56

3525

55

2985

55

2985

60

2487

60,56

2438

65

2082

65

2082

70

1751

70,56

1718

75

1480

75

1480

80

1256

80,56

1234

85

1070

85

1070

  • If you still don’t want to use the NTC10K3A1 characteristic there is no built-in custom table possibility yet. However alternativelly you can set the input to Resistance mode to read the plain resistance and then use Curve4P or Curve10P components to convert Ohms to Celsius.

By following these steps, you can successfully configure an NTC 10k Type 2 temperature sensor in Celsius. Always verify the sensor characteristics to ensure accurate temperature readings.