A temperature sensor is a standard equipment in the Control Point panel. The temperature sensor's configuration data is available in the following parameters or in the iSMA Configurator:
TEMPERATURE_SENSOR: indicates a current temperature value with offset;
-
Modbus register: 30301;
-
BACnet object: AI4, property: Present Value;
TEMPERATURE_SENSOR_OFFSET: allows to set an offset value for the temperature sensor (correction to the temperature sensor's value). The default value is 0;
-
Modbus register: 40304;
-
BACnet object: AI4, property: 4205;
TEMPERATURE_FILTER: allows to set a filtering value for the temperature sensor (expressed in seconds). The default value is 10 seconds;
-
Modbus register: 40307;
-
BACnet object: AI4, property: 4003;
TEMPERATURE_NAME: allows to set a unique 4-letter name for a temperature sensor;
-
Modbus registers: 40310, 40311 (each for two letters of the name);
-
BACnet object: AI 4, property: Description Property.
Configuration of Temperature Sensor
TEMPERATURE_CONFIGURATION: allows to configure the temperature sensor with two bits:
-
ACTIVE: activates or deactivates the sensor;
-
Modbus register: 40316, bit 0;
-
BACnet object: AO4, property: 4200;
-
-
THIRD_POINT_ACTIVE: enables or disables decimal values in the sensor;
-
Modbus register: 40316, bit 4;
-
BACnet object: AO4, property: 4202;
-
|
Bit |
Name |
0 |
1 |
|---|---|---|---|
|
0 |
ACTIVE |
Inactive |
Active (default) |
|
4 |
THIRD_POINT_ACTIVE |
No decimal |
Decimal (default) |
Configuration of temperature sensor