Occupancy Submenu Objects

BACnet ID

Object Property

Object Name

Access

Description

AV 48

Present value

SETTINGS_NUMERIC1

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 48

Description

SETTINGS_NUMERIC1

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 48

Step increment

SETTINGS_NUMERIC1

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 48

Low limit

SETTINGS_NUMERIC1

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 48

High limit

SETTINGS_NUMERIC1

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 48

4201

SETTINGS_NUMERIC1

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 48

Out of service

SETTINGS_NUMERIC1

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 48

4200

SETTINGS_NUMERIC1

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 48

4202

SETTINGS_NUMERIC1

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 48

Units

SETTINGS_NUMERIC1

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 49

Present value

SETTINGS_NUMERIC2

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 49

Description

SETTINGS_NUMERIC2

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 49

Step increment

SETTINGS_NUMERIC2

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 49

Low limit

SETTINGS_NUMERIC2

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 49

High limit

SETTINGS_NUMERIC2

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 49

4201

SETTINGS_NUMERIC2

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 49

Out of service

SETTINGS_NUMERIC2

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 49

4200

SETTINGS_NUMERIC2

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 49

4202

SETTINGS_NUMERIC2

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 49

Units

SETTINGS_NUMERIC2

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 50

Present value

SETTINGS_NUMERIC3

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 50

Description

SETTINGS_NUMERIC3

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 50

Step increment

SETTINGS_NUMERIC3

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 50

Low limit

SETTINGS_NUMERIC3

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 50

High limit

SETTINGS_NUMERIC3

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 50

4201

SETTINGS_NUMERIC3

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 50

Out of service

SETTINGS_NUMERIC3

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 50

4200

SETTINGS_NUMERIC3

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 50

4202

SETTINGS_NUMERIC3

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 50

Units

SETTINGS_NUMERIC3

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 51

Present value

SETTINGS_NUMERIC4

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 51

Description

SETTINGS_NUMERIC4

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 51

Step increment

SETTINGS_NUMERIC4

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 51

Low limit

SETTINGS_NUMERIC4

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 51

High limit

SETTINGS_NUMERIC4

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 51

4201

SETTINGS_NUMERIC4

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 51

Out of service

SETTINGS_NUMERIC4

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 51

4200

SETTINGS_NUMERIC4

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 51

4202

SETTINGS_NUMERIC4

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 51

Units

SETTINGS_NUMERIC4

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 52

Present value

SETTINGS_NUMERIC5

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 52

Description

SETTINGS_NUMERIC5

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 52

Step increment

SETTINGS_NUMERIC5

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 52

Low limit

SETTINGS_NUMERIC5

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 52

High limit

SETTINGS_NUMERIC5

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 52

4201

SETTINGS_NUMERIC5

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 52

Out of service

SETTINGS_NUMERIC5

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 52

4200

SETTINGS_NUMERIC5

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 52

4202

SETTINGS_NUMERIC5

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 52


Units

SETTINGS_NUMERIC5

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 53

Present value

SETTINGS_NUMERIC6

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 53

Description

SETTINGS_NUMERIC6

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 53

Step increment

SETTINGS_NUMERIC6

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 53

Low limit

SETTINGS_NUMERIC6

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 53

High limit

SETTINGS_NUMERIC6

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 53

4201

SETTINGS_NUMERIC6

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 53

Out of service

SETTINGS_NUMERIC6

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 53

4200

SETTINGS_NUMERIC6

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 53

4202

SETTINGS_NUMERIC6

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 53

Units

SETTINGS_NUMERIC6

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 54

Present value

SETTINGSNUMERIC7

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 54

Description

SETTINGS_NUMERIC7

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 54

Step increment

SETTINGS_NUMERIC7

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 54

Low limit

SETTINGS_NUMERIC7

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 54

High limit

SETTINGS_NUMERIC7

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 54

4201

SETTINGS_NUMERIC7

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 54

Out of service

SETTINGS_NUMERIC7

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 54

4200

SETTINGS_NUMERIC7

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 54

4202

SETTINGS_NUMERIC7

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 54

Units

SETTINGS_NUMERIC7

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 55

Present value

SETTINGS_NUMERIC8

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 55

Description

SETTINGS_NUMERIC8

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 55

Step increment

SETTINGS_NUMERIC8

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 55

Low limit

SETTINGS_NUMERIC8

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 55

High limit

SETTINGS_NUMERIC8

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 55

4201

SETTINGS_NUMERIC8

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 55

Out of service

SETTINGS_NUMERIC8

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 55

4200

SETTINGS_NUMERIC8

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 55

4202

SETTINGS_NUMERICE8

POINT ACTIV

Read / write

Memory

Number of decimal places from 0 to 3

AV 55

Units

SETTINGS_NUMERIC8

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

BV 48

Present value

SETTINGS_BOOLEAN1

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 48

Description

SETTINGS_BOOLEAN1

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 48

True text

SETTINGS_BOOLEAN1

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 48

False text

SETTINGS_BOOLEAN1

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 48

4201

SETTINGS_BOOLEAN1

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 48

Out of

service

SETTINGS_BOOLEAN8

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 48

4200

SETTINGS_BOOLEAN8

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 49

Present value

SETTINGS_BOOLEAN2

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 49

Description

SETTINGS_BOOLEAN2

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 49

True text

SETTINGS_BOOLEAN2

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 49

False text

SETTINGS_BOOLEAN2

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 49

4201

SETTINGS_BOOLEAN2

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 49

Out of service

SETTINGS_BOOLEAN2

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 49

4200

SETTINGS_BOOLEAN2

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 50

Present value

SETTINGS_BOOLEAN3

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 50

Description

SETTINGS_BOOLEAN3

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 50

True text

SETTINGS_BOOLEAN3

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 50

False text

SETTINGS_BOOLEAN3

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 50

4201

SETTINGS_BOOLEAN3

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 50

Out of service

SETTINGS_BOOLEAN3

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 50

4200

SETTINGS_BOOLEAN3

EDITABLE

Read / write

Memory

False = Non-e Editable

True = Editable

BV 51

Present value

SETTINGS_BOOLEAN4

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 51

Description

SETTINGS_BOOLEAN4

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 51

True text

SETTINGS_BOOLEAN4

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 51

False text

SETTINGS_BOOLEAN4

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 51

4201

SETTINGS_BOOLEAN4

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 51

Out of service

SETTINGS_BOOLEAN4

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 51

4200

SETTINGS_BOOLEAN4

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 52

Present value

SETTINGS_BOOLEAN5

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 52

Description

SETTINGS_BOOLEAN5

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 52

True text

SETTINGS_BOOLEAN5

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 52

False text

SETTINGS_BOOLEAN5

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 52

4201

SETTINGS_BOOLEAN5

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

BV 52

Out of service

SETTINGS_BOOLEAN5

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 52

4200

SETTINGS_BOOLEAN5

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 53

Present value

SETTINGS_BOOLEAN6

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 53

Description

SETTINGS_BOOLEAN6

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 53

True text

SETTINGS_BOOLEAN6

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 53

False text

SETTINGS_BOOLEAN6

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 53

4201

SETTINGS_BOOLEAN6

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 53

Out of service

SETTINGS_BOOLEAN6

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 53

4200

SETTINGS_BOOLEAN6

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 54

Present value

SETTINGS_BOOLEAN7

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 54

Description

SETTINGS_BOOLEAN7

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 54

True text

SETTINGS_BOOLEAN7

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 54

False text

SETTINGS_BOOLEAN7

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 54

4201

SETTINGS_BOOLEAN7

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 54

Out of service

SETTINGS_BOOLEAN7

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 54

4200

SETTINGS_BOOLEAN7

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 55

Present value

SETTINGS_BOOLEAN8

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 55

Description

SETTINGS_BOOLEAN8

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 55

True text

SETTINGS_BOOLEAN8

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 55

False text

SETTINGS_BOOLEAN8

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 55

4201

SETTINGS_BOOLEAN8

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 55

Out of service

SETTINGS_BOOLEAN8

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 55

4200

SETTINGS_BOOLEAN8

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

List of occupancy submenu objects