Blind Submenu Objects

BACnet ID

Object Property

Object Name

Access

Description

AV 31

Present value

BLIND_NUMERIC1

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 31

Description

BLIND_NUMERIC1

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 31

Step increment

BLIND_NUMERIC1

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 31

Low limit

BLIND_NUMERIC1

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 31

High limit

BLIND_NUMERIC1

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 31

4201

BLIND_NUMERIC1

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

AV 31

Out of service

BLIND_NUMERIC1

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 31

4200

BLIND_NUMERIC1

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 31

4202

BLIND_NUMERIC1

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 31

Units

BLIND_NUMERIC1

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 32

Present value

BLIND_NUMERIC2

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 32

Description

BLIND_NUMERIC2

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 32

Step increment

BLIND_NUMERIC2

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 32

Low limit

BLIND_NUMERIC2

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 32

High limit

BLIND_NUMERIC2

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 32

4201

BLIND_NUMERIC2

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying  in the submenu

AV 32

Out of service

BLIND_NUMERIC2

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 32

4200

BLIND_NUMERIC2

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 32

4202

BLIND_NUMERIC2

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 32

Units

BLIND_NUMERIC2

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 33

Present value

BLIND_NUMERIC3

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 33

Description

BLIND_NUMERIC3

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 33

Step increment

BLIND_NUMERIC3

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 33

Low limit

BLIND_NUMERIC3

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 33

High limit

BLIND_NUMERIC3

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 33

4201

BLIND_NUMERIC3

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying  n the Submenu

AV 33

Out of service

BLIND_NUMERIC3

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 33

4200

BLIND_NUMERIC3

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 33

4202

BLIND_NUMERIC3

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 33

Units

BLIND_NUMERIC3

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 35

Present value

BLIND_NUMERIC4

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 35

Description

BLIND_NUMERIC4

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 35

Step increment

BLIND_NUMERIC4

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 35

Low limit

BLIND_NUMERIC4

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 35

High limit

BLIND_NUMERIC4

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 35

4201

BLIND_NUMERIC4

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 35

Out of service

BLIND_NUMERIC4

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 35

4200

BLIND_NUMERIC4

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 35

4202

BLIND_NUMERIC4

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 35

Units

BLIND_NUMERIC4

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 36

Present value

BLIND_NUMERIC5

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 36

Description

BLIND_NUMERIC5

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 36

Step increment

BLIND_NUMERIC5

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 36

Low limit

BLIND_NUMERIC5

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 36

High limit

BLIND_NUMERIC5

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 36

4201

BLIND_NUMERIC5

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in the submenu

AV 36

Out of service

BLIND_NUMERIC5

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 36

4200

BLIND_NUMERIC5

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 36

4202

BLIND_NUMERIC5

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 36

Units

BLIND_NUMERIC5

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 37

Present value

BLIND_NUMERIC6

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 37

Description

BLIND_NUMERIC6

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 37

Step increment

BLIND_NUMERIC6

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 37

Low limit

BLIND_NUMERIC6

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 37

High limit

BLIND_NUMERIC6

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 37

4201

BLIND_NUMERIC6

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the Submenu

AV 37

Out of service

BLIND_NUMERIC6

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 37

4200

BLIND_NUMERIC6

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 37

4202

BLIND_NUMERIC6

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 37

Units

BLIND_NUMERIC6

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 38

Present value

BLINDNUMERIC7

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 38

Description

BLIND_NUMERIC7

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 38

Step increment

BLIND_NUMERIC7

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 38

Low limit

BLIND_NUMERIC7

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 38

High limit

BLIND_NUMERIC7

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 38

4201

BLIND_NUMERIC7

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

AV 38

Out of service

BLIND_NUMERIC7

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 38

4200

BLIND_NUMERIC7

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 38

4202

BLIND_NUMERIC7

POINT_ACTIVE

Read / write

Memory

Number of decimal places from 0 to 3

AV 38

Units

BLIND_NUMERIC7

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV 39

Present value

BLIND_NUMERIC8

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

AV 39

Description

BLIND_NUMERIC8

NAME

Read / write

Memory

Displayed user-defined parameter name

AV 39

Step increment

BLIND_NUMERIC8

STEP

Read / write

Memory

Step of the parameter value change.

The default value is 0

AV 39

Low limit

BLIND_NUMERIC8

LOW_LIMIT

Read / write

Memory

Minimum value of the parameter.

The default value is 0

AV 39

High limit

BLIND_NUMERIC8

HIGH_LIMIT

Read / write

Memory

Maximum value of the parameter.

The default value is 0

AV 39

4201

BLIND_NUMERIC8

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying  in the submenu

AV 39

Out of service

BLIND_NUMERIC8

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

AV 39

4200

BLIND_NUMERIC8

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

AV 39

4202

BLIND_NUMERICE8

POINT ACTIV

Read / write

Memory

Number of decimal places from 0 to 3

AV 39

Units

BLIND_NUMERIC8

UNITS

Read / write

Memory

Supported units:

° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

BV 32

Present value

BLIND_BOOLEAN1

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 32

Description

BLIND_BOOLEAN1

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 32

True text

BLIND_BOOLEAN1

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 32

False text

BLIND_BOOLEAN1

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 32

4201

BLIND_BOOLEAN1

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying  in the submenu

BV 32

Out of

service

BLIND_BOOLEAN8

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 32

4200

BLIND_BOOLEAN8

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 33

Present value

BLIND_BOOLEAN2

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 33

Description

BLIND_BOOLEAN2

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 33

True text

BLIND_BOOLEAN2

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 33

False text

BLIND_BOOLEAN2

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 33

4201

BLIND_BOOLEAN2

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 33

Out of service

BLIND_BOOLEAN2

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 33

4200

BLIND_BOOLEAN2

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 34

Present value

BLIND_BOOLEAN3

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 34

Description

BLIND_BOOLEAN3

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 34

True text

BLIND_BOOLEAN3

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 34

False text

BLIND_BOOLEAN3

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 34

4201

BLIND_BOOLEAN3

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying  in the submenu

BV 34

Out of service

BLIND_BOOLEAN3

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 34

4200

BLIND_BOOLEAN3

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 35

Present value

BLIND_BOOLEAN4

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 35

Description

BLIND_BOOLEAN4

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 35

True text

BLIND_BOOLEAN4

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 35

False text

BLIND_BOOLEAN4

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 35

4201

BLIND_BOOLEAN4

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 35

Out of service

BLIND_BOOLEAN4

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 35

4200

BLIND_BOOLEAN4

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 36

Present value

BLIND_BOOLEAN5

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 36

Description

BLIND_BOOLEAN5

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 36

True text

BLIND_BOOLEAN5

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 36

False text

BLIND_BOOLEAN5

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 36

4201

BLIND_BOOLEAN5

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of  displaying in submenu

BV 36

Out of service

BLIND_BOOLEAN5

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 36

4200

BLIND_BOOLEAN5

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 37

Present value

BLIND_BOOLEAN6

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 37

Description

BLIND_BOOLEAN6

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 37

True text

BLIND_BOOLEAN6

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 37

False text

BLIND_BOOLEAN6

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 37

4201

BLIND_BOOLEAN6

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 37

Out of service

BLIND_BOOLEAN6

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 37

4200

BLIND_BOOLEAN6

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 38

Present value

BLIND_BOOLEAN7

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 38

Description

BLIND_BOOLEAN7

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 38

True text

BLIND_BOOLEAN7

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 38

False text

BLIND_BOOLEAN7

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 38

4201

BLIND_BOOLEAN7

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 38

Out of service

BLIND_BOOLEAN7

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 38

4200

BLIND_BOOLEAN7

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

BV 39

Present value

BLIND_BOOLEAN8

PRESENT_VALUE

Read / write

Memory

Present value of the parameter

BV 39

Description

BLIND_BOOLEAN8

NAME

Read / write

Memory

Displayed user-defined parameter name

BV 39

True text

BLIND_BOOLEAN8

TRUE_TEXT

Read / write

Memory

Text for the parameter true state value

BV 39

False text

BLIND_BOOLEAN8

FALSE_TEXT

Read / write

Memory

Text for the parameter false state value

BV 39

4201

BLIND_BOOLEAN8

PRIORITY

Read / write

Memory

Priority of the parameter for sequence of displaying in the submenu

BV 39

Out of service

BLIND_BOOLEAN8

ACTIVE

Read / write

Memory

False = Inactive(def)

True = Active

BV 39

4200

BLIND_BOOLEAN8

EDITABLE

Read / write

Memory

False = Non-editable

True = Editable

List of blind submenu objects