Balancing actions in the iSMA Configurator are available in the last tab of the VAV Configurator, the Balancing tab. Here, it is possible to perform actions of the balancing process.
The available actions are:
-
Set K-Factor: sets the K-factor value to the airflow calculations (AV61, 40289);
-
Max Flow Calibration: executes a calibration action according to a new maximum airflow value (AV66, 40294);
-
Max + Min Calibration: executes a calibration action according to a new maximum and minimum airflow values (AV66, 40294);
-
Zeroing: performs the pressure sensor zeroing action (BV13, 00014);
-
Mode Override: allows to force the device to operate in one of the available modes (MSV7, 40068):
-
Available settings: Auto, Max. Flow, Min. Flow, User Flow, User Position, Full Open, Full Close, Calibrate;
-
-
Set all In auto: forces all dampers to the Auto mode (MSV7, 40068).
For more information on the VAV balancing parameters that are available to configure in the iSMA Configurator, please see the VAV Software user manual.