Device Objects

Device BACnet Object Description

Dynamically creatable: no, dynamically deletable: no.

Property Name

Required

Proprietary

Writable

Property ID

Data Type

Description

OBJECT_IDENTIFIER

Yes

OBJECT_NAME

Yes

OBJECT_TYPE

Yes

SYSTEM_STATUS

Yes

VENDOR_NAME

Yes

VENDOR_IDENTIFIER

Yes

MODEL_NAME

Yes

FIRMWARE_REVISION

Yes

APPLICATION_SOFTWARE_VERSION

Yes

PROTOCOL_VERSION

Yes

PROTOCOL_REVISION

Yes

PROTOCOL_SERVICES_SUPPORTED

Yes

PROTOCOL_OBJECT_TYPES_SUPPORTED

Yes

OBJECT_LIST

Yes

MAX_APDU_LENGTH_ACCEPTED

Yes

SEGMENTATION_SUPPORTED

Yes

APDU_TIMEOUT

Yes

NUMBER_OF_APDU_RETRIES

Yes

MAX_MASTER

Yes

Yes

MAX_INFO_FRAMES

Yes

DEVICE_ADDRESS_BINDING

Yes

DATABASE_REVISION

Yes

ACTIVE COV SUBSCRIPTION

Yes

HW_VERSION

Yes

3020

Unsigned

VERSION_TYPE

Yes

Yes

3030

Unsigned

RS485_BIASING

Yes

Yes

3045

Unsigned

MINI IP modules only with HW_VERSION>=2.0

BAUD_RATE

Yes

3084

Unsigned

USER_BAUD_RATE

Yes

Yes

3085

Unsigned

IP_ADDRESS

Yes

Yes

3101

Unsigned

SUBNET_MASK

Yes

Yes

3102

Unsigned

DEFAULT_GATEWAY

Yes

Yes

3103

Unsigned

HTTP_PORT

Yes

Yes

3104

Unsigned

UDP_PORT

Yes

Yes

3105

Unsigned

DHCP

Yes

Yes

3106

Unsigned

Applicable to firmware 7.0 and later

WATCHDOG

Yes

Yes

5001

Unsigned

VALID_FRAMES_FOR_US_CNT

Yes

5101

Unsigned

VALID_FRAMES_NOT_FOR_US_CNT

Yes

5102

Unsigned

ERROR_FRAMES_CNT

Yes

5103

Unsigned

TRANSMITTED_FRAMES_CNT

Yes

5104

Unsigned

Device BACnet objects

VALID_FRAMES_FOR_US_CNT Property 5101

The property contains the number of valid frames (on the MS/TP layer) addressed to this module.

VALID_FRAMES_FOR_NOT_US_CNT Property 5102

The property contains the number of valid frames (on the MS/TP layer), which are not addressed to this module.

ERROR_FRAMES_CNT Property 5103

The property contains the number of invalid frames on the MS/TP layer.

TRANSMITTED_FRAMES_CNT Property 5104

The property contains the number of transmitted frames.

UP_TIME Object (Analog Value: 0)

The object shows the time of module operation module (expressed in seconds) from the last power-up or the module reset.

WATCHDOG Object (Analog Value: 1)

The object specifies the time (expressed in seconds) to watchdog reset. If the module does not receive any valid BACnet message within that time, all PRIORITY_ARRAYs will be set to null, and the PRESENT_VALUE for outputs will be set to the RELINQUISH_DEFAULT value.

This feature is useful in case of an interruption in data transmission, and if, for security reasons, output states must be set to the appropriate state in order to avoid endangering the safety of persons or the property.

The default value is 0 seconds, which means the watchdog function is disabled. To maintain the compatibility, this object is also available as the Device object property 5001.

If the watchdog is triggered, the power LED blinks with the specified sequence (3 blinks with 20 Hz frequency and 1-second pause).

FIRMWARE VERSION AND MODULE TYPE Property 3030

The property contains the type and firmware version of a module.

The low byte contains information about a type of a module in accordance with the table below:

Value

Type

8110 (0x5116)

8I

9110 (0x5B16)

8I-IP

8410 (0x5416)

8U

9410 (0x5E16)

8U-IP

8310 (0x5316)

4I4O-H

9310 (0x5D16)

4I4O-H-IP

8510 (0x5516)

4U4O-H

9510 (0x5F16)

4U4O-H-IP

8610 (0x5616)

4U4A-H

9610 (0x6016)

4U4A-H-IP

8210 (0x5216)

4O-H

9210 (0x5C16)

4O-H-IP

8710 (0x5716)

4TO-H

9710 (0x6116)

4TO-H-IP

5010 (0x3216)

MIX18

5110 (0x3316)

MIX38

5210 (0x3416)

MIX18-IP

5310 (0x3516)

MIX38-IP

8810 (0x5816)

12O-H

9810 (0x6216)

12O-H-IP

8910 (0x5916)

24I

9910 (0x6316)

24I-IP

Module type value assignement

The high byte contains a module firmware version multiplied by 10.

Example:

The property 3030 has a value of 1281010 = 0x320A16. It means that it is a MIX18 module (0x32) with a firmware version 1.0 (0x0A16 = 1010).

Setting the property 3030 according to the table below enables 1 of 4 available actions: reset module, reload settings, set to default, and enter the bootloader.

Value

Action

511

Reset

767

Reload settings

1023

Set to default

1279

Enter the bootloader

Device actions

RS485_BIASING Property 3045

The property allows activating RS485 biasing resistors in order to pull up voltage on the RS485 bus. The function is only available in MINI IP modules with a hardware version >= 2.0. MIX and MAX IP modules with hardware version 3.0 and up have a hardware switch for RS485 biasing under the bottom cover. For more information see installation instructions available at ismacontrolli.com.

The biasing resistors are useful in case when iSMA modules are connected to third party devices with the same RS485 bus and communication errors appear on the network.

Warning!

Only one device in the network can have biasing resistors activated!

DHCP Property 3106

The property allows to enable or disable setting an IP address by the DHCP server.

Value

Action

2

DHCP enabled

Other

DHCP disabled

The DHCP property

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.