MAC36NL - KNX - Not possible to import ETS 6 project to the controller's station

Issue

It is not possible to import the KNX network project, created in the ETS6/ETS6.1 program, using the knxnetIp module in Niagara 4.12.

Possible causes and solutions

The knxnetIp module, which is by default added to the Niagara 4.12, is incompatible with the ETS6/ETS6.1 projects.

Solutions

To solve the problem, follow the below steps:

Workbench_Options_KNX.png
  • save the KNX project from ETS6/ETS6.1 in ETS5 and import the ETS5 project to the MAC36NL controller;

  • for ETS6/ETS6.1 projects in MAC36NL controllers, it is possible to install the knxnetIp module in version 4.10.9.8 or higher 4.10 version.