Light Submenu Objects

BACnet ID

Object property

Object name

Access

Description

AV24

Present value

LIGHT_NUMERIC1:Present Value

Read/write, memory

Current value of the parameter

AV24

Description

LIGHT_NUMERIC1:Description

Read/write, memory

User-defined name of the parameter

AV24

4206

LIGHT_NUMERIC1:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV24

Low limit

LIGHT_NUMERIC1:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV24

High limit

LIGHT_NUMERIC1:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV24

4201

LIGHT_NUMERIC1:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV24

Out of service

LIGHT_NUMERIC1:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV24

4200

LIGHT_NUMERIC1:Editability

Read/write, memory

Enabling editability of the parameter

AV24

4202

LIGHT_NUMERIC1:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV24

Units

LIGHT_NUMERIC1:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV25

Present value

LIGHT_NUMERIC2:Present Value

Read/write, memory

Current value of the parameter

AV25

Description

LIGHT_NUMERIC2:Description

Read/write, memory

User-defined name of the parameter

AV25

4206

LIGHT_NUMERIC2:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV25

Low limit

LIGHT_NUMERIC2:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV25

High limit

LIGHT_NUMERIC2:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV25

4201

LIGHT_NUMERIC2:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV25

Out of service

LIGHT_NUMERIC2:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV25

4200

LIGHT_NUMERIC2:Editability

Read/write, memory

Enabling editability of the parameter

AV25

4202

LIGHT_NUMERIC2:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV25

Units

LIGHT_NUMERIC2:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV26

Present value

LIGHT_NUMERIC3:Present Value

Read/write, memory

Current value of the parameter

AV26

Description

LIGHT_NUMERIC3:Description

Read/write, memory

User-defined name of the parameter

AV26

4206

LIGHT_NUMERIC3:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV26

Low limit

LIGHT_NUMERIC3:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV26

High limit

LIGHT_NUMERIC3:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV26

4201

LIGHT_NUMERIC3:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV26

Out of service

LIGHT_NUMERIC3:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV26

4200

LIGHT_NUMERIC3:Editability

Read/write, memory

Enabling editability of the parameter

AV26

4202

LIGHT_NUMERIC3:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV26

Units

LIGHT_NUMERIC3:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV27

Present value

LIGHT_NUMERIC4:Present Value

Read/write, memory

Current value of the parameter

AV27

Description

LIGHT_NUMERIC4:Description

Read/write, memory

User-defined name of the parameter

AV27

4206

LIGHT_NUMERIC4:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV27

Low limit

LIGHT_NUMERIC4:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV27

High limit

LIGHT_NUMERIC4:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV27

4201

LIGHT_NUMERIC4:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV27

Out of service

LIGHT_NUMERIC4:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV27

4200

LIGHT_NUMERIC4:Editability

Read/write, memory

Enabling editability of the parameter

AV27

4202

LIGHT_NUMERIC4:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV27

Units

LIGHT_NUMERIC4:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV28

Present value

LIGHT_NUMERIC5:Present Value

Read/write, memory

Current value of the parameter

AV28

Description

LIGHT_NUMERIC5:Description

Read/write, memory

User-defined name of the parameter

AV 20

4206

LIGHT_NUMERIC5:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV28

Low limit

LIGHT_NUMERIC5:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV28

High limit

LIGHT_NUMERIC5:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV28

4201

LIGHT_NUMERIC5:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV28

Out of service

LIGHT_NUMERIC5:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV28

4200

LIGHT_NUMERIC5:Editability

Read/write, memory

Enabling editability of the parameter

AV28

4202

LIGHT_NUMERIC5:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV28

Units

LIGHT_NUMERIC5:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV29

Present value

LIGHT_NUMERIC6:Present Value

Read/write, memory

Current value of the parameter

AV29

Description

LIGHT_NUMERIC6:Description

Read/write, memory

User-defined name of the parameter

AV29

4206

LIGHT_NUMERIC6:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV29

Low limit

LIGHT_NUMERIC6:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV29

High limit

LIGHT_NUMERIC6:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV29

4201

LIGHT_NUMERIC6:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV29

Out of service

LIGHT_NUMERIC6:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV29

4200

LIGHT_NUMERIC6:Editability

Read/write, memory

Enabling editability of the parameter

AV29

4202

LIGHT_NUMERIC6:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV29

Units

LIGHT_NUMERIC6:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV30

Present value

LIGHTNUMERIC7:Present Value

Read/write, memory

Current value of the parameter

AV30

Description

LIGHT_NUMERIC7:Description

Read/write, memory

User-defined name of the parameter

AV30

4206

LIGHT_NUMERIC7:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV30

Low limit

LIGHT_NUMERIC7:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV30

High limit

LIGHT_NUMERIC7:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV30

4201

LIGHT_NUMERIC7:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV30

Out of service

LIGHT_NUMERIC7:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV30

4200

LIGHT_NUMERIC7:Editability

Read/write, memory

Enabling editability of the parameter

AV30

4202

LIGHT_NUMERIC7:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV30

Units

LIGHT_NUMERIC7:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV31

Present value

LIGHT_NUMERIC8:Present Value

Read/write, memory

Current value of the parameter

AV31

Description

LIGHT_NUMERIC8:Description

Read/write, memory

User-defined name of the parameter

AV31

4206

LIGHT_NUMERIC8:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV31

Low limit

LIGHT_NUMERIC8:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV31

High limit

LIGHT_NUMERIC8:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV31

4201

LIGHT_NUMERIC8:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV31

Out of service

LIGHT_NUMERIC8:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV31

4200

LIGHT_NUMERIC8:Editability

Read/write, memory

Enabling editability of the parameter

AV31

4202

LIGHT_NUMERIC8:Deciamal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV31

Units

LIGHT_NUMERIC8:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

BV24

Present value

LIGHT_BOOLEAN1:Present Value

Read/write, memory

Current value of the parameter

BV24

Description

LIGHT_BOOLEAN1:Description

Read/write, memory

User-defined name of the parameter

BV24

4203

LIGHT_BOOLEAN1:True Text

Read/write, memory

Text for the parameter’s true value

BV24

4204

LIGHT_BOOLEAN1:False Text

Read/write, memory

Text for the parameter’s false value

BV24

4201

LIGHT_BOOLEAN1:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV24

Out of service

LIGHT_BOOLEAN1:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV24

4200

LIGHT_BOOLEAN1:Editability

Read/write, memory

Enabling editability of the parameter

BV25

Present value

LIGHT_BOOLEAN2:Present Value

Read/write, memory

Current value of the parameter

BV25

Description

LIGHT_BOOLEAN2:Description

Read/write, memory

User-defined name of the parameter

BV25

4203

LIGHT_BOOLEAN2:True Text

Read/write, memory

Text for the parameter’s true value

BV25

4204

LIGHT_BOOLEAN2:False Text

Read/write, memory

Text for the parameter’s false value

BV25

4201

LIGHT_BOOLEAN2:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV25

Out of service

LIGHT_BOOLEAN2:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV25

4200

LIGHT_BOOLEAN2:Editability

Read/write, memory

Enabling editability of the parameter

BV26

Present value

LIGHT_BOOLEAN3:Present Value

Read/write, memory

Current value of the parameter

BV26

Description

LIGHT_BOOLEAN3:Description

Read/write, memory

User-defined name of the parameter

BV26

4203

LIGHT_BOOLEAN3:True Text

Read/write, memory

Text for the parameter’s true value

BV26

4204

LIGHT_BOOLEAN3:False Text

Read/write, memory

Text for the parameter’s false value

BV26

4201

LIGHT_BOOLEAN3:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV26

Out of service

LIGHT_BOOLEAN3:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV26

4200

LIGHT_BOOLEAN3:Editability

Read/write, memory

Enabling editability of the parameter

BV27

Present value

LIGHT_BOOLEAN4:Present Value

Read/write, memory

Current value of the parameter

BV27

Description

LIGHT_BOOLEAN4:Description

Read/write, memory

User-defined name of the parameter

BV27

4203

LIGHT_BOOLEAN4:True Text

Read/write, memory

Text for the parameter’s true value

BV27

4204

LIGHT_BOOLEAN4:False Text

Read/write, memory

Text for the parameter’s false value

BV27

4201

LIGHT_BOOLEAN4:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV27

Out of service

LIGHT_BOOLEAN4:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV27

4200

LIGHT_BOOLEAN4:Editability

Read/write, memory

Enabling editability of the parameter

BV28

Present value

LIGHT_BOOLEAN5:Present Value

Read/write, memory

Current value of the parameter

BV28

Description

LIGHT_BOOLEAN5:Description

Read/write, memory

User-defined name of the parameter

BV28

4203

LIGHT_BOOLEAN5:True Text

Read/write, memory

Text for the parameter’s true value

BV28

4204

LIGHT_BOOLEAN5:False Text

Read/write, memory

Text for the parameter’s false value

BV28

4201

LIGHT_BOOLEAN5:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV28

Out of service

LIGHT_BOOLEAN5:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV28

4200

LIGHT_BOOLEAN5:Editability

Read/write, memory

Enabling editability of the parameter

BV29

Present value

LIGHT_BOOLEAN6:Present Value

Read/write, memory

Current value of the parameter

BV29

Description

LIGHT_BOOLEAN6:Description

Read/write, memory

User-defined name of the parameter

BV29

4203

LIGHT_BOOLEAN6:True Text

Read/write, memory

Text for the parameter’s true value

BV29

4204

LIGHT_BOOLEAN6:False Text

Read/write, memory

Text for the parameter’s false value

BV29

4201

LIGHT_BOOLEAN6:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV29

Out of service

LIGHT_BOOLEAN6:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV29

4200

LIGHT_BOOLEAN6:Editability

Read/write, memory

Enabling editability of the parameter

BV30

Present value

LIGHT_BOOLEAN7:Present Value

Read/write, memory

Current value of the parameter

BV30

Description

LIGHT_BOOLEAN7:Description

Read/write, memory

User-defined name of the parameter

BV30

4203

LIGHT_BOOLEAN7:True Text

Read/write, memory

Text for the parameter’s true value

BV30

4204

LIGHT_BOOLEAN7:False Text

Read/write, memory

Text for the parameter’s false value

BV30

4201

LIGHT_BOOLEAN7:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV30

Out of service

LIGHT_BOOLEAN7:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV30

4200

LIGHT_BOOLEAN7:Editability

Read/write, memory

Enabling editability of the parameter

BV31

Present value

LIGHT_BOOLEAN8:Present Value

Read/write, memory

Current value of the parameter

BV31

Description

LIGHT_BOOLEAN8:Description

Read/write, memory

User-defined name of the parameter

BV31

4203

LIGHT_BOOLEAN8:True Text

Read/write, memory

Text for the parameter’s true value

BV31

4204

LIGHT_BOOLEAN8:False Text

Read/write, memory

Text for the parameter’s false value

BV31

4201

LIGHT_BOOLEAN8:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV31

Out of service

LIGHT_BOOLEAN8:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV31

4200

LIGHT_BOOLEAN8:Editability

Read/write, memory

Enabling editability of the parameter


Light submenu objects