In its out-of-the-box state, as well as after restoring the default values, the device has the following default register values:
|
Register Name |
Default Value |
|---|---|
|
COUNTER 1-12 |
0 |
|
COUNTER 12-24 (24I and 24I-IP) |
0 |
|
USER BAUD RATE |
7680 (76800 bps) |
|
STOP BITS |
1 |
|
DATA BITS |
8 |
|
PARITY BITS |
0 |
|
RESPONSE DELAY |
0 |
|
WATCHDOG TIME |
0 (disabled) |
|
DEFAULT STATE OF DIGITAL OUTPUTS (1-12) |
0 |
|
DEFAULT STATE OF THE ANALOG OUTPUTS (DIGITAL 1-6) |
0 |
|
DEFAULT STATE OF THE ANALOG OUTPUTS (1-6) |
0 |
|
UNIVERSAL INPUT CONFIGURATION (1-8) |
3 (10K3A1 NTC (°C)) |
|
INPUT FILTER TIME CONSTANT (1-8) |
2 |
|
UNIVERSAL INPUT RESOLUTION (1-8) |
1 (12-bit) |
|
ANALOG OUTPUT CONFIGURATION (1-6) |
1 (voltage) |
|
Only for IP Modules |
|
|
USERNAME |
admin |
|
PASSWORD |
1000 |
|
IP ADDRESS |
192.168.1.123 |
|
MASK |
255.255.255.0 |
|
GATEWAY |
192.168.1.1 |
|
DHCP |
Disabled |
|
HTTP PORT |
80 |
|
MODBUS TCP PORT |
502 |
|
MODBUS TCP TIMEOUT |
60 s |
|
RS485 TIMEOUT |
500 ms |
|
RS485 BIASING RESISTORS (MINI only) |
DISABLED |
|
SEND MODBUS ERRORS |
ENABLED |
Default values
Restoring Default Settings
To restore the default configuration of all registers, follow the steps below:
-
turn off the power supply;
-
set section 6 of the S3 switch to on;
-
turn on the power supply, the power LED will start blinking;
-
switch section 6 of the S3 switch to off to restore the default settings. To cancel the reset, turn off the power, and switch section 6 of the S3 switch to the off position.