Address |
Modbus Register |
Description |
Access |
Persistence |
Group |
|---|---|---|---|---|---|
|
6678 6679 6680 |
Firmware version |
Firmware version (composed of 3 bytes): 1st byte: major version 2nd byte: minor version 3rd byte: revision version |
Read |
YES |
Configuration |
|
6681 |
First power up |
Represents the first power up event. After this event the value is 0xCF. |
Read |
YES |
Configuration |
|
6682 |
Calibration error |
Represents the number of times a stroke error has occurred down the minimum allowed. Range 0-254 |
Read/ Write |
YES |
Diagnostic/ Alarms |
|
6683 |
Calibration error |
Represents the number of times a stroke error has occurred up the maximum allowed. Range 0-254 |
Read/ Write |
YES |
Diagnostic/ Alarms |
|
6684 |
Low voltage anomaly |
Represents the number of times a low voltage event has occurred. Range 0-254 |
Read/ Write |
YES |
Diagnostic/ Alarms |
|
6685 |
High voltage anomaly |
Represents the number of times a high voltage event has occurred. Range 0-254 |
Read/ Write |
YES |
Diagnostic/ Alarms |
|
6686 |
Unexpected stalls within the stroke |
Represents the number of times a stall has occurred within the stroke. Range 0-254 |
Read/ Write |
YES |
Diagnostic/ Alarms |
|
6687 |
Extra stroke in normal operation |
Represents the number of times that an extra stroke error has occurred compared to that calculated during the calibration phase (stroke out of range). Range 0-254 |
Read/ Write |
YES |
Diagnostic/ Alarms |
|
6688 |
Actuator stroke |
Identifies the value read by the actuator after the calibration phase. It is possible to set the stroke value but requires restarting the actuator. The value must be stored multiplied by 10. Range 20-120 (2-12mm) |
Read/ Write |
YES |
Configuration |
|
6689
|
Actuator setting
|
Direct/reverse action setting. (default: direct action (bit0=1)) |
Read/ Write
|
YES
|
Configuration
|
|
Emergency return direction selection (up or down). (default: down (bit1=1)) |
|||||
|
Fixed stroke (default: fixed stroke not enabled (bit2=1) |
|||||
|
6690 |
Actuator speed |
Allows you to set the speed of the actuator (207 = 5 s/mm o 140 = 3 s/mm). (default: 207 = 5 s/mm) |
Read/ Write |
YES |
Configuration |
|
6691 |
LIBRA valve type configuration |
By selecting the type of PICV LIBRA valve, the stroke value is automatically set to 4 mm and reverse action. (default: 0 = NO PICV) |
Read/ Write |
YES |
Configuration |
|
6692 |
Characteristic configuration of the valve (β) |
It represents the characteristic of the valve (β=0 linear valve, β=1 equal percentage valve). (default: 0 = linear) |
Read/ Write |
YES |
Configuration |
|
6693 |
Baud rate |
Represents the communication speed of the Modbus protocol (9600, 19200). (default: 9600) |
Read/ Write |
YES |
Configuration |
|
6694 |
Parity bit and stop bit |
2 least significant bits (bits 0 and 1): parity bit (0 = none, 1 = even, 2 = odd) bit 4: stop bit (0 = 1 stop bit, 1 = 2 stop bit) (default: 16 = none and 2 stop bits) |
Read/ Write |
YES |
Configuration |
|
6146 |
Opening phase |
It is the number of times the actuator has been in the total opening position Range 0-65279 |
Read |
YES |
Diagnostic/ Alarms |
|
6147 |
Closing phase |
It is the number of times the actuator has been in the total closing position. Range 0-65279 |
Read |
YES |
Diagnostic/ Alarms |
|
8840 |
Actuator control |
Represents the percentage of control of the actuator (by setting a value between 0 and 100% it allows to drive the motor in any position). Range 0-100% |
Read/ Write |
NO |
Input/ Output |
|
8841 |
Actuator operating status |
Represents the current operating status of the actuator (based on the status of the LEDs). Range 0-16 |
Read |
NO |
Diagnostic/ Alarms |
|
8842 |
Reset actuator |
Allows you to perform a software reset of the actuator. Writing 1 performs a reset. (default: 0 = no reset) |
Read/ Write |
NO |
Configuration |
|
8843 |
Actuator calibration |
Forcing calibration phase (Generic valve) or initial positioning (PICV valve) |
Read/ Write |
NO |
Configuration |
|
8288 |
Valve position (feeback) |
Represents the position of the actuator. (0-1000 normal function, 1100 emergency return, 1200 calibration) (divide by 10 to have % value) |
Read |
NO |
Input/ Output |
|
8289 |
Valve flow rate |
In the case of selection of the PICV, it represents the percentage flow rate value (the value of the feedback register is not available). Range 0-1000 (divide by 10 to have % value) |
Read |
NO |
Input/ Output |