Breadcrumbs

Modbus Registers

The list of Modbus registers is applicable for the following actuators family:

  • MVE-2-RS

  • MVC-2-RS

  • EBV

If the functionality does not apply to the selected actuator the connected register is not applicable.

The database is divided into the following sections:

  • Common Registers Section: It contains general information about the actuators.

  • Configuration Section: it contains the configuration registers area.

  • Diagnostic Section: it contains registers useful for diagnostics and error check.

  • Input/Output Section : it contains registers for command and feedback position.

  • Flow Rate Section: it contains registers for flow rate functions.

  • Setpoints Section: it contains registers for Temperature sensors setpoint.

  • Power Limit/Control Section: it contains registers for power control and limits loop.

  • Temperature Sensors Section: it contains registers for Temperature sensors reading.

  • Energy Heating/Cooling Section: it contains registers for the Energy function.

  • Clock Function Section: it contains registers for clock setting.

  • Output Loops Section: it contains registers for the main loop output value.

  • Power Section: it contains registers for the power function.

  • Loop Parameters Section: it contains registers for main loop parameters.

All registers and values are described in the following table:

Modbus Address

Decimal Address

Hex Address

Register Name

Access

Description

Persistence

Group

40001

0

0x0

VERSION AND MODULE TYPE

Read/write

LSB – type (device ID), MSB - FW version / 10

YES

Common registers

30002

1

0x1

MODULE ADDRESS

Read/write

Modbus address setting via Modbus from 1 to 255

YES

30004

3

0x3

COUNTER OF RECEIVED FRAMES (32-Bit)

Read-only

Default state is 0. Counting the received Modbus frames from the last powering up or module reset.

NO

30005

4

0x4

30006

5

0x5

COUNTER OF FRAMES WITH ERROR (32-Bit)

Read-only

Default state is 0. Counting the incorrect received Modbus frames from the last powering up or module reset.

NO

30007

6

0x6

30008

7

0x7

COUNTER OF SENT FRAMES (32-Bit)

Read-only

Default state is 0. Counting the sent Modbus frames from the last powering up or module reset.

NO

30009

8

0x8

30012

11

0xB

UP TIME

Read-only

This 32-bit register contains module counting time in seconds from the last powering up or module reset

NO

30013

12

0xC

30014

13

0xD

SOURCE OF LAST DEVICE RESET

Read-only

Select the source of the last reset
1: power-on reset (POR)
2: brown-out detector (BOD12)
4: brown-out detector (BOD33)
16: ext. reset pin
32: watchdog (WDT)
64: system reset (SYST)

YES

40134

133

0x85

BACNET_DEVICEID

Read/write

Device BACnet ID

YES

40135

134

0x86

40136

135

0x87

BAUD RATE

Read/write

Transmission speed is defined by the user calculated using the formula: baud rate = register value x 10. The default value is 115200 bps.

YES

40137

136

0x88

STOP Bits

Read/write

Supported values are 1 and 2. The default value is 1.

YES

40138

137

0x89

DATA Bits

Read/write

Supported value is only 8.

YES

40139

138

0x8A

PARITY Bit

Read/write

Parity bit. The default value is 0 (no parity). Allowed values: 0 (default): none, 1: odd, 2: even

YES

40140

139

0x8B

RESPONSE DELAY

Read/write

Delay in ms before sending the response. The default value is 0.

YES

30190

190

0xBE

-

Read-only

Auxiliary register (used for detecting first device activation, 0x5555=device activated)

YES

30301

300

0x12C

DEVICE VERSION DESIGNATION

Read-only

Select the device version designation
Bit 5: Emergency return (0 not available, 1 available)
Bit 6: Long/short yoke (0 Long, 1 Short) for MVE-2-RS
For EBV, it indicates Modbus/BACnet model (1)
Bit 7: Temp sensor (0 not available, 1 available)

YES

Configuration

30302

301

0x12D

HARDWARE VERSION

Read-only

Hardware version

YES

30303

302

0x12E

BOOTLOADER VERSION

Read-only

Bootloader version

YES

30304

303

0x12F

FIRMWARE VERSION

Read-only

Firmware version

YES

30305

304

0x130

SERIAL NUMBER 1

Read-only

It’s configured in production

YES

30306

305

0x131

SERIAL NUMBER 2

Read-only

It’s configured in production

YES

30307

306

0x132

SERIAL NUMBER 3

Read-only

It’s configured in production

YES

30308

307

0x133

SERIAL NUMBER 4

Read-only

It’s configured in production

YES

41005

1004

0x3EC

MAXIMUM FLOW SETTING

Read/write

Select the caliber position:
0: Max flow setting 1
1: Max flow setting 1,25
2: Max flow setting 1,5
3: Max flow setting 1,75
4: Max flow setting 2
5: Max flow setting 2,25
6: Max flow setting 2,5
7: Max flow setting 2,75
8: Max flow setting 3
9: Max flow setting 3,25
10: Max flow setting 3,5
11: Max flow setting 3,75
12: Max flow setting 4
13: Max flow setting 4,25
14: Max flow setting 4,5
15: Max flow setting 4,75
16: Max flow setting 5

YES

41006

1005

0x3ED

TYPE OF CONTROL

Read/write

Select the actuator type of control:
0: Modbus (DIP switch disabled)
1: 10 V (DIP switch disabled)
2: 2-10 V (DIP switch disabled)
3: 0 5 V (DIP switch disabled)
4: 5-10 V (DIP switch disabled)
5: 2-6 V (DIP switch disabled)
6: 6-10 V (DIP switch disabled)
7 (default): selected by DIP switch

YES

41007

1006

0x3EE

DIRECT/REVERSE & FAILSAFE DIRECTION SETTING

Read/write

Select the actuator's action (direct or reverse) and fail-safe direction:
Bit 0: direct action (1-default); reverse action (0)
Bit 1: fail-safe DOWN (1); fail-safe UP (0-default)

YES

41008

1007

0x3EF

FORCE CALIBRATION

Read/write

Force calibration (valve stroke learning); 1 - force calibration (automatic reset of value after calibration)

NO

41009

1008

0x3F0

JUMPER ENABLE (ER board)

Read/write

Fail-safe jumper enable setting: 0 (default) - jumper enabled, 1 - jumper disabled
MVC-2-RS and EBV only

YES

41010

1009

0x3F1

CHANGEOVER SETTING

Read/write

Temperature loops action selection:
0 (default): heating
1: cooling
2: automatic (according ∆T)

YES

41011

1010

0x3F2

TEMPERATURE PROBE SELECTION

Read/write

Temperature probe selection:
0 (default): supply temperature (T1)
1: return temperature (T2)
2: ∆T

YES

41013

1012

0x3F4

VALVE CHARACTERISTIC CONFIGURATION

Read/write

Select type of movement of the valve: Linear-0, EQP-1

YES

41014

1013

0x3F5

FUNCTIONS ENABLE

Read/write

Actuator function setting (bit0 = 1-BMS - default):
Bit 0: BMS
Bit 1: enable temperature control function
Bit 2: enable min. ΔT limitation function
Bit 3: enable function max. temperature limitation function
Bit 4: enable function min. temperature limitation function
Bit 5: enable power control function
Bit 6: enable power limit function
Bit 7: enable energy function

YES

31015

1014

0x3F6

FUNCTIONS STATUS

Read-only

Actuator function setting:
Bit 0: BMS control
Bit 1: function temperature control activated (1-active)
Bit 2: function temperature min. ΔT limit activated
Bit 3: function temperature max. limit activated
Bit 4: function temperature min. limit activated
Bit 5: function power control activated
Bit 6: function power limit activated

NO

41016

1015

0x3F7

% MINIMUM OPENING VALVE

Read/write

Set minimum opening valve when the temperature loops and limits are active.

YES

31017

1016

0x3F8

DIP SWITCH & PUSH BUTTON & JUMPER STATUS

Read-only

DIP switches and jumper status:
Bit 0: DIP1 status: "Direct Action” (OFF) – “Reverse Action” (ON)
Bit 1: DIP2 status: "0-10V” (OFF) - “BUS” (ON)
Bit 2: DIP3 status: "Normal” (OFF) – “Default setting” (ON)
Bit 3: DIP4 status: "Modbus" (OFF) - "BACnet" (ON)

Bit 4: DIP5 status: “No action” (OFF), “Set and EBV” (ON)
Bit 5:  DIP6 status: “Voltage control” (OFF)- “curr. control (4-20 mA)” (ON)
Bit 6: Push button: status: "Active" (Pressed) - Not Active (Released)
Bit 7: Jumper status: "Fail-safe Down" (Jumper Insert) -" Fail-safe UP"

NO

41018

1017

0x3F9

VALVE TYPE

Read/write

Select valve model
0: Generic valve
4: Custom Energy Valve (MVE-2-RS only)
5: VLX6P (MVE-2-RS only)
6: VLX8P (MVE-2-RS only)
12: Custom PICV valve (MVE/MVC-2-RS only)
13: 2FGB65B-EBV
14: 2FGB80B-EBV
15: 2FGB100B-EBV
16: 2FGB125B-EBV
17: 2FGB150B-EBV

YES

41019

1018

0x3FA

VALVE STROKE (mm*100)

Read/write

Valve stroke (mm*100) - after calibration phase

YES

41020

1019

0x3FB

OVERVOLTAGE EVENTS (24 V AC > 20%) (230 V > 10%)

Read/write

Overvoltage events (24 V AC > 20%) (230 V > 20%)

YES

Diagnostic

41021

1020

0x3FC

UNDERVOLTAGE EVENTS (V AC < 20%) (230 V < 10%)

Read/write

Undervoltage events (V AC < 20%) (230 V < 20%)

YES

41022

1021

0x3FD

FULLY OPEN EVENTS

Read/write

Fully opened events

YES

41023

1022

0x3FE

FULLY CLOSE EVENTS

Read/write

Fully closes events

YES

41024

1023

0x3FF

UNEXPECTED STALL CONDITION EVENTS (within calculated stroke)

Read/write

Unexpected stall condition events (within calculated stroke)

YES

41025

1024

0x400

UNEXPECTED STALL CONDITION EVENTS (outside calculated stroke)

Read/write

Unexpected stall condition events (outside calculated stroke)

YES

41026

1025

0x401

VALVE STROKE ERROR > max. (60 mm for EMV/MVE-2-RS and 12mm for MVC-2-RS)

Read/write

Valve stroke error > max. (60 mm for EMV/MVE-2-RS and 12mm for MVC-2-RS))

YES

41027

1026

0x402

VALVE STROKE ERROR < min. (5 mm for EMV/MVE-2-RS and 2mm for MVC-2-RS)

Read/write

Valve stroke error < min. (5 mm for EMV/MVE-2-RS and 12mm for MVC-2-RS))

YES

31028

1027

0x403

ACTUATOR OPERATING MODE

Read-only

Actuator operating mode (0 - not active) (1- active):
Bit 0: Normal Running
Bit 1: Initial Positioning
Bit 2: Stroke calibration
Bit 3: Fail Safe Phase
Bit 4: Manual Override Phase
Bit 5: Error Phase

NO

31029

1028

0x404

ERROR TYPE

Read-only

Error type: (0- no error) (1- error):
Bit 0: T1 temperature sensor error (out of range)
Bit 1: T2 temperature sensor error (out of range)
Bit 4: valve stroke < 5 mm
Bit 5: valve stroke > 60 mm
Bit 6: unexpected stall condition events (within calculated stroke)
Bit 7: unexpected stall condition events (outside calculated stroke
Bit 8: undervoltage error
Bit 9: overvoltage error
Bit 10: clock error

YES

41034

1033

0x409

ACTUATOR RESET

Read/write

Force actuator reset (1)

NO

Configuration

41035

1034

0x40A

BMS COMMAND

Read/write

BMS command (0-100%) *10

NO

Input/

Output

31038

1037

0x40D

FEEDBACK

Read-only

Valve position (0-100%) *10

NO

41044

1043

0x413

MAX FLOW RATE

Read/write

Select Nominal flow rate (m3/h)
MVE-2-RS:
0: VLX6P (2,1)- VLX8P (3,2)
1: VLX6P (2,5)-VLX8P (3,9)
2: VLX6P (2,9)-VLX8P (4,5)
3: VLX6P (3,3)-VLX8P (5,2)
4: VLX6P (3,8)-VLX8P (5,8)
5: VLX6P (4,3)-VLX8P (6,3)
6: VLX6P (4,8)-VLX8P (6,7)
7: VLX6P (5,3)- VLX8P (7,1)
8: VLX6P (5,8)-VLX8P (7,5)
9: VLX6P (6,4)-VLX8P (8,1)
10: VLX6P (6,9)-VLX8P (8,8)
11: VLX6P (7,5)-VLX8P (9,4)
12: VLX6P (8)-VLX8P (10)
13: VLX6P (8,8)-VLX8P (10,9)
14: VLX6P (9,5)-VLX8P (11,8)
15: VLX6P (10,3)-VLX8P (12,3)
16: VLX6P (11)-VLX8P (13,5)

 EBV (m3/h):
2FGB65B-EBV (37)
2FGB80B-EBV (59)
2FGB100B-EBV (77)
2FGB125B-EBV (118)
2FGB150B-EBV (177) 

MVC-2-RS (l/h):
0: VLX1 (100)- VLX2 (145)-VLX3 (200)-VLX4 (200)-VLX5 (400)
1: VLX1 (113)- VLX2 (163)-VLX3 (225)-VLX4 (270)-VLX5 (500)
2: VLX1 (125)- VLX2 (180)-VLX3 (250)-VLX4 (340)-VLX5 (600)
3: VLX1 (138)- VLX2 (198)-VLX3 (275)-VLX4 (410)-VLX5 (700)
4: VLX1 (150)- VLX2 (215)-VLX3 (300)-VLX4 (480)-VLX5 (800)
5: VLX1 (173)- VLX2 (251)-VLX3 (345)-VLX4 (570)-VLX5 (1000)
6: VLX1 (195)- VLX2 (288)-VLX3 (390)-VLX4 (660)-VLX5 (1200)
7: VLX1 (218)- VLX2 (324)-VLX3 (435)-VLX4 (750)-VLX5 (1400)
8: VLX1 (240)- VLX2 (360)-VLX3 (480)-VLX4 (840)-VLX5 (1600)
9: VLX1 (255)- VLX2 (414)-VLX3 (548)-VLX4 (980)-VLX5 (1950)
10: VLX1 (270)- VLX2 (468)-VLX3 (615)-VLX4 (1120)-VLX5 (2300)
11: VLX1 (285)- VLX2 (521)-VLX3 (683)-VLX4 (1260)-VLX5 (2650)
12: VLX1 (300)- VLX2 (575)-VLX3 (750)-VLX4 (1400)-VLX5 (3000)
13: VLX1 (319)- VLX2 (631)-VLX3 (813)-VLX4 (1550)-VLX5 (3250)
14 VLX1 (338)- VLX2 (688)-VLX3 (875)-VLX4 (1700)-VLX5 (3500)
15: VLX1 (356)- VLX2 (744)-VLX3 (938)-VLX4 (1850)-VLX5 (3750)
16: VLX1 (375)- VLX2 (800)-VLX3 (1000)-VLX4 (2000)-VLX5 (4000)

YES

Flow rate

41045

1044

0x414

DESIGN FLOW RATE

Read/write

Design flow rate must be between ¼ of Qnom and Qnom (*10)

YES

31047

1046

0x416

INPUT PRESSURE (P1)

Read-only

Input pressure value (bar*100)

NO

31048

1047

0x417

OUTPUT PRESSURE (P2)

Read-only

Output pressure value (bar*100)

NO

31049

1048

0x418

DIFFERENTIAL PRESSURE

Read-only

∆P value (P1 – P2) (bar*100)

NO

41080

1079

0x437

FLOW RATE SP X1

Read/write

Flow rate X1 (custom valve)*10

YES

41081

1080

0x438

VALVE POSITION Y1

Read/write

Valve Position Y1 (custom valve)*10

YES

41082

1081

0x439

FLOW RATE SP X2

Read/write

Flow rate X2 (custom valve)*10

YES

41083

1082

0x43A

VALVE POSITION Y2

Read/write

Valve position Y2 (custom valve)*10

YES

41084

1083

0x43B

FLOW RATE SP X3

Read/write

Flow rate X3 (custom valve)*10

YES

41085

1084

0x43C

VALVE POSITION Y3

Read/write

Valve position Y3 (custom valve)*10

YES

41086

1085

0x43D

FLOW RATE SP X4

Read/write

Flow rate X4 (custom valve)*10

YES

41087

1086

0x43E

VALVE POSITION Y4

Read/write

Valve position Y4 (custom valve)*10

YES

41088

1087

0x43F

FLOW RATE SP X5

Read/write

Flow rate X5 (custom valve)*10

YES

41089

1088

0x440

VALVE POSITION Y5

Read/write

Valve position Y5 (custom valve)*10

YES

41090

1089

0x441

FLOW RATE SP X6

Read/write

Flow rate X6 (custom valve)*10

YES

41091

1090

0x442

VALVE POSITION Y6

Read/write

Valve position Y6 (custom valve)*10

YES

41092

1091

0x443

FLOW RATE SP X7

Read/write

Flow rate X7 (custom valve)*10

YES

41093

1092

0x444

VALVE POSITION Y7

Read/write

Valve position Y7 (custom valve)*10

YES

41094

1093

0x445

FLOW RATE SP X8

Read/write

Flow rate X8 (custom valve)*10

YES

41095

1094

0x446

VALVE POSITION Y8

Read/write

Valve position Y8 (custom valve)*10

YES

41096

1095

0x447

FLOW RATE SP X9

Read/write

Flow rate X9 (custom valve)*10

YES

41097

1096

0x448

VALVE POSITION Y9

Read/write

Valve position Y9 (custom valve)*10

YES

41098

1097

0x449

FLOW RATE SP X10

Read/write

Flow rate X10 (custom valve)*10

YES

41099

1098

0x44A

VALVE POSITION Y10

Read/write

Valve position Y10 (custom valve)*10

YES

31100

1099

0x44B

INDICATED FLOW RATE

Read-only

Calculated flow rate (m3/h)*100 (for EBV/MVE-2-RS) and l/h (MVC-2-RS)

NO

41101

1100

0x44C

SETPOINT ∆T CONTROL HEATING

Read/write

Set heating ∆T control (°C*10)

YES

Setpoints

41102

1101

0x44D

SETPOINT ∆T CONTROL COOLING

Read/write

Set cooling ∆T control (°C*10)

YES

41103

1102

0x44E

SETPOINT SUPPLY TEMPERATURE CONTROL HEATING

Read/write

Set heating supply temperature (°C*10)

YES

41104

1103

0x44F

SETPOINT SUPPLY TEMPERATURE CONTROL COOLING

Read/write

Set cooling supply temperature (°C*10)

YES

41105

1104

0x450

SETPOINT RETURN TEMPERATURE CONTROL HEATING

Read/write

Set heating return temperature (°C*10)

YES

41106

1105

0x451

SETPOINT RETURN TEMPERATURE CONTROL COOLING

Read/write

Set cooling return temperature (°C*10)

YES

41107

1106

0x452

SETPOINT MINIMUM ∆T HEATING

Read/write

Set heating ∆T limitation (°C*10)

YES

41108

1107

0x453

SETPOINT MINIMUM ∆T COOLING 

Read/write

Set cooling ∆T limitation (°C*10)

YES

41109

1108

0x454

SETPOINT MAX. SUPPLY TEMPERATURE HEATING

Read/write

Set heating supply temperature limit (°C*10)

YES

41110

1109

0x455

SETPOINT MIN. SUPPLY TEMPERATURE COOLING

Read/write

Set cooling supply temperature limit (°C*10)

YES

41111

1110

0x456

SETPOINT MAX. RETURN TEMPERATURE HEATING

Read/write

Set heating return temperature limit (°C*10)

YES

41112

1111

0x457

SETPOINT MIN. RETURN TEMPERATURE COOLING

Read/write

Set cooling return temperature limit (°C*10)

YES

41113

1112

0x458

DESIGN POWER

Read/write

Set maximum power (control) (kW*10)

YES

Power control/limit

41114

1113

0x459

SET MAX. POWER LIMIT

Read/write

Set max power (limit) (kW*10)

YES

31115

1114

0x45A

SUPPLY TEMPERATURE VALUE

Read-only

Supply temperature value (°C*10)

NO

Temperature Sensors

31116

1115

0x45B

RETURN TEMPERATURE VALUE

Read-only

Return temperature value (°C*10)

NO

31117

1116

0x45C

∆T VALUE (S1 – S2)

Read-only

∆T value (T1 – T2) (°C*10)

NO

31120

1119

0x45F

INSTANT POWER

Read-only

Instant power (kW*10)

YES

Energy Heating/Cooling

31121

1120

0x460

HEATING ENERGY LSR

Read-only

Total heating energy (kWh*10) less significant word

YES

31122

1121

0x461

HEATING ENERGY MSR

Read-only

Total heating energy (kWh*10) more significant word

YES

31123

1122

0x462

COOLING ENERGY LSR

Read-only

Total cooling energy (kWh*10) less significant word

YES

31124

1123

0x463

COOLING ENERGY MSR

Read-only

Total cooling energy (kWh*10) more significant word

YES

31139

1138

0x472

HEATING ENERGY AT 31/12 LSR

Read-only

Energy (Heating) at the end of the year (kWh*10) less significant word

YES

31140

1139

0x473

HEATING ENERGY AT 31/12 MSR

Read-only

Energy (Heating) at the end of the year (kWh*10) more significant word

YES

31141

1140

0x474

HEATING ENERGY AT VALUE 1

Read-only

Energy (Heating) value 1 (MWh*10)

YES

31142

1141

0x475

HEATING ENERGY AT VALUE 2

Read-only

Energy (Heating) value 2 (MWh*10)

YES

31143

1142

0x476

HEATING ENERGY AT VALUE 3

Read-only

Energy (Heating) value 3 (MWh*10)

YES

31144

1143

0x477

HEATING ENERGY AT VALUE 4

Read-only

Energy (Heating) value 4 (MWh*10)

YES

31145

1144

0x478

HEATING ENERGY AT VALUE 5

Read-only

Energy (Heating) value 5 (MWh*10)

YES

31146

1145

0x479

HEATING ENERGY AT VALUE 6

Read-only

Energy (Heating) value 6 (MWh*10)

YES

31147

1146

0x47A

HEATING ENERGY AT VALUE 7

Read-only

Energy (Heating) value 7 (MWh*10)

YES

31148

1147

0x47B

HEATING ENERGY AT VALUE 8

Read-only

Energy (Heating) value 8 (MWh*10)

YES

31149

1148

0x47C

HEATING ENERGY AT VALUE 9

Read-only

Energy (Heating) value 9 (MWh*10)

YES

31150

1149

0x47D

HEATING ENERGY AT VALUE 10

Read-only

Energy (Heating) value 10 (MWh*10)

YES

31151

1150

0x47E

HEATING ENERGY AT VALUE 11

Read-only

Energy (Heating) value 11 (MWh*10)

YES

31152

1151

0x47F

HEATING ENERGY AT VALUE 12

Read-only

Energy (Heating) value 12 (MWh*10)

YES

31153

1152

0x480

COOLING ENERGY AT 31/12 LSR

Read-only

Energy (Cooling) at the end of the year (kWh*10)

YES

31154

1153

0x481

COOLING ENERGY AT 31/12 MSR

Read-only

YES


31155

1154

0x482

COOLING ENERGY VALUE 1

Read-only

Energy (Cooling) value 1 (MWh*10)

YES

31156

1155

0x483

COOLING ENERGY VALUE 2

Read-only

Energy (Cooling) value 2 (MWh*10)

YES

31157

1156

0x484

COOLING ENERGY VALUE 3

Read-only

Energy (Cooling) value 3 (MWh*10)

YES

31158

1157

0x485

COOLING ENERGY VALUE 4

Read-only

Energy (Cooling) value 4 (MWh*10)

YES

31159

1158

0x486

COOLING ENERGY VALUE 5

Read-only

Energy (Cooling) value 5 (MWh*10)

YES

31160

1159

0x487

COOLING ENERGY VALUE 6

Read-only

Energy (Cooling) value 6 (MWh*10)

YES

31161

1160

0x488

COOLING ENERGY VALUE 7

Read-only

Energy (Cooling) value 7 (MWh*10)

YES

31162

1161

0x489

COOLING ENERGY VALUE 8

Read-only

Energy (Cooling) value 8 (MWh*10)

YES

31163

1162

0x48A

COOLING ENERGY VALUE 9

Read-only

Energy (Cooling) value 9 (MWh*10)

YES

31164

1163

0x48B

COOLING ENERGY VALUE 10

Read-only

Energy (Cooling) value 10 (MWh*10)

YES

31165

1164

0x48C

COOLING ENERGY VALUE 11

Read-only

Energy (Cooling) value 11 (MWh*10)

YES

31166

1165

0x48D

COOLING ENERGY VALUE 12

Read-only

Energy (Cooling) value 12 (MWh*10)

YES

41182

1181

0x49D

CLOCK MINUTES

Read/write

Clock minutes

YES

Clock function

41183

1182

0x49E

CLOCK HOURS

Read/write

Clock hours

YES

41184

1183

0x49F

CLOCK DAY

Read/write

Clock day

YES

41185

1184

0x4A0

CLOCK MONTH

Read/write

Clock month

YES

41186

1185

0x4A1

CLOCK YEAR

Read/write

Clock year

YES

41187

1186

0x4A2

RESTORE FACTORY SETTING

Read/write

Set 1 to load default setting to the device and to EEPROM MEMORY

NO

Configuration

41188

1187

0x4A3

FORCE FULLY CLOSE

Read/write

Allow to fully close the valve (overwrites the output from any function/loop)

NO

41189

1188

0x4A4

FORCE FULLY OPEN

Read/write

Allow to fully open the valve (overwrites the output from any function/loop)

NO

41190

1189

0x4A5

TEMPERATURE TEST MODE

Read/write

Set to 1, it’s possible to write the desired temperature value into supply and return temperature  register (addr. 1114 and 1115). The values will not be read from temperature sensors.

NO

31192

1191

0x4A7

OUT LOOP ∆P

Read-only

Output loop ∆P (*10)

NO

Loop outputs

31193

1192

0x4A8

OUT LOOP BMS

Read-only

Output loop BMS (*10)

NO

31194

1193

0x4A9

OUT LOOP FLOW RATE CONTROL

Read-only

Output loop flow rate control (*10)

NO

31196

1195

0x4AB

OUT LOOP POWER

Read-only

Output loop power (*10)

NO

31197

1196

0x4AC

OUT LOOP POWER LIMIT

Read-only

Output loop power limit (*10)

NO

31198

1197

0x4D

OUT LOOP T CONTROL

Read-only

Output loop T control (*10)

NO

31199

1198

0x4AE

OUT LOOP T LIMITS

Read-only

Output loop T limits (*10)

NO

31200

1199

0x4AF

OUT LOOP "ACTIVE"

Read-only

Output loop "active" (*10)

NO

41207

1206

0x4B6

MAX. POWER

Read/write

Valve nominal power (kW)*10

YES

Power

41208

1207

0x4B7

MEDIA DENSITY

Read/write

Media density (*10): default value is for water at 20°C (Kg/m3)

YES

41209

1208

0x4B8

MEDIA SPECIFIC HEAT

Read/write

Media specific heat (*10): default value is for water (J/Kg°C)

YES

31213

1212

0x4BC

CUSTOM NOMINAL POWER ΔT 20K

Read-only

Valve nominal power at 20°C (kW) (max.val)

YES

41231

1230

0x4CE

LOOP TYPE P, P+I, P+I+D

Read/write

Loop type P, P+I, P+I+D

YES

Loop parameters

41232

1231

0x4CF

DERIVATIVE TIME (gain)

Read/write

Derivative time (gain)

YES

41233

1232

0x4D0

INTEGRAL TIME (min.)

Read/write

Integral time (min.)

YES

41234

1233

0x4D1

PROPORTIONAL BANDWIDTH ∆T (°C*10)

Read/write

Proportional bandwidth ∆T (°C*10)

YES

31241

1240

0x4D8

MONTH TIMESTAMP OF 31ST DECEMBER

Read-only

Month timestamp for energy at 31st December

YES

31242

1241

0x4D9

YEAR TIMESTAMP OF 31ST DECEMBER

Read-only

Year timestamp for energy at 31st December

YES

31243

1242

0x4DA

MONTH TIMESTAMP OF VALUE 1

Read-only

Month timestamp for value 1

YES

31244

1243

0x4DB

YEAR TIMESTAMP OF VALUE 1

Read-only

Year timestamp for value 1

YES

31245

1244

0x4DC

MONTH TIMESTAMP OF VALUE 2

Read-only

Month timestamp for value 2

YES

31246

1245

0x4DD

YEAR TIMESTAMP OF VALUE 2

Read-only

Year timestamp for value 2

YES

31247

1246

0x4DE

MONTH TIMESTAMP OF VALUE 3

Read-only

Month timestamp for value 3

YES

31248

1247

0x4DF

YEAR TIMESTAMP OF VALUE 3

Read-only

Year timestamp for value 3

YES

31249

1248

0x4E0

MONTH TIMESTAMP OF VALUE 4

Read-only

Month timestamp for value 4

YES

31250

1249

0x4E1

YEAR TIMESTAMP OF VALUE 4

Read-only

Year timestamp for value 4

YES

31251

1250

0x4E2

MONTH TIMESTAMP OF VALUE 5

Read-only

Month timestamp for value 5

YES

31252

1251

0x4E3

YEAR TIMESTAMP OF VALUE 5

Read-only

Year timestamp for value 5

YES

31253

1252

0x4E4

MONTH TIMESTAMP OF VALUE 6

Read-only

Month timestamp for value 6

YES

31254

1253

0x4E5

YEAR TIMESTAMP OF VALUE 6

Read-only

Month timestamp for value 6

YES

31255

1254

0x4E6

MONTH TIMESTAMP OF VALUE 7

Read-only

Year timestamp for value 7

YES

31256

1255

0x4E7

YEAR TIMESTAMP OF VALUE 7

Read-only

Month timestamp for value 7

YES

31257

1256

0x4E8

MONTH TIMESTAMP OF VALUE 8

Read-only

Year timestamp for value 8

YES

31258

1257

0x4E9

YEAR TIMESTAMP OF VALUE 8

Read-only

Month timestamp for value 8

YES

31259

1258

0x4EA

MONTH TIMESTAMP OF VALUE 9

Read-only

Year timestamp for value 9

YES

31260

1259

0x4EB

YEAR TIMESTAMP OF VALUE 9

Read-only

Month timestamp for value 9

YES

31261

1260

0x4EC

MONTH TIMESTAMP OF VALUE 10

Read-only

Year timestamp for value 10

YES

31262

1261

0x4ED

YEAR TIMESTAMP OF VALUE 10

Read-only

Month timestamp for value 10

YES

31263

1262

0x4EE

MONTH TIMESTAMP OF VALUE 11

Read-only

Year timestamp for value 11

YES

31264

1263

0x4EF

YEAR TIMESTAMP OF VALUE 11

Read-only

Month timestamp for value 11

YES

31265

1264

0x4F0

MONTH TIMESTAMP OF VALUE 12

Read-only

Year timestamp for value 12

YES

31266

1265

0x4F1

YEAR TIMESTAMP OF VALUE 12

Read-only

Month timestamp for value 12

YES

Common Registers Section

Version and module type

This register shows the firmware version (Most Significant Byte) and the device ID of the actuator (Least Significant Byte).

Modbus register: 40001

Module Address

Defines the Modbus address of the device from 1 to 255.

Modbus register: 30002

BACnet object: Network port, object ID: 0, properties: MAC address.

Counter of Received Frames (LSW)

This register contains the least significant word of the counter of received frames from the last powering-up or module reset.

Modbus register: 30004

Counter of Received Frames (MSW)

This register contains the most significant word of the counter of received frames from the last powering-up or module reset.

Modbus register: 30005

Counter of Frames with Error (LSW)

This register contains the least significant word of the counter of frames with error from the last powering-up or module reset.

Modbus register: 30006

Counter of Frames with Error (MSW)

This register contains the most significant word of the counter of frames with error from the last powering-up or module reset.

Modbus register: 30007

Counter of Sent Frames (LSW)

This register contains the least significant word of the counter of sent frames from the last powering-up or module reset.

Modbus register: 30008

Counter of Sent Frames (MSW)

This register contains the most significant word of the counter of sent frames from the last powering-up or module reset.

Modbus register: 30009

Up Time (LSW)

This register contains the least significant word of the uptime counter from the last powering-up or module reset.

Modbus register: 30012

BACnet object: type Analog value, object ID: 0, properties: Present value.

Up Time (MSW)

This register contains the most significant word of the uptime counter from the last powering-up or module reset.

Modbus register: 30013

BACnet object: type Analog value, object ID: 0, properties: Present value.

Source of last device reset

Source of last device reset

This register shows the source of the last reset, according to the table below:

Addr. value

Source of the reset

1

Power-on reset (POR)

2

Brown-out detector (BOD12)

4

Brown-out detector (BOD33)

16

Ext. reset (EXT)

32

Watchdog (WDT)

64

System reset (SYST)

Selection for source of the last reset

Modbus register: 30014

BACnet device ID

This register contains the least important two bytes of the BACnet ID value.

Modbus register: 40134

BACnet Device ID

This register contains the most important two bytes of the BACnet ID value.

Modbus register: 40135

Baud Rate

It defines the possibility to set the modbus protocol baud rate according to the following possibilities:

Addr. 1 (value)

Modbus baud rate

1

960

2

1920

3

3840

4

5760

5

7680

6

11520 (default)

Selection of the Baud rate

Modbus register: 40136

BACnet object: Network port, object ID: 0, properties: link speed.

Stop Bits

Defines the number of stop bits in the Modbus communication parameters according to the following possibilities:

Addr. 136 (value)

Number of stop bits

1

1

2

2

Stop bits configuration for Modbus communication

Modbus register: 40137

Data Bits

Defines the number of stop bits in the Modbus communication parameters according to the following possibilities:

Addr.137 (value)

Data bits

8

Data has 8 bits

Data bits configuration for Modbus communication

Parity Bit

Defines the value of parity bit in the Modbus communication parameters according to the following possibilities:

Addr.138 (value)

Parity bit

0

None

1

Odd

2

Even

Parity bit configuration for Modbus communication

Modbus register: 40139

Response delay

This register shows the delay (in ms) before sending the response to the master. The default value is 0.

Modbus register: 40140

Auxiliary register

This auxiliary register is used for detecting the first device activation, 0x5555=device activated (it’s a read-only register).

Modbus register: 30190

Configuration Section

Device version designation

Defines the device version according to the table below (for MVE-2-RS):

Bit number

Device description

Addr. value

Model

1
2
3
4

129

MVE504-2-RS

131

MVE506-2-RS

133

MVE510-2-RS

135

MVE515-2-RS

137

MVE522-2-RS

139

MVE204-2-RS

141

MVE206-2-RS

143

MVE210-2-RS

145

MVE215-2-RS

147

MVE222-2-RS

161

MVE504R-2-RS

163

MVE506R-2-RS

165

MVE510R-2-RS

167

MVE515R-2-RS

193

MVE504S-2-RS

195

MVE506S-2-RS

197

MVE510S-2-RS

199

MVE515S-2-RS

201

MVE522S-2-RS

203

MVE204S-2-RS

205

MVE206S-2-RS

207

MVE210S-2-RS

209

MVE215S-2-RS

211

MVE222S-2-RS

225

MVE504SR-2-RS

227

MVE506SR-2-RS

229

MVE510SR-2-RS

231

MVE515SR-2-RS

235

MVE204SR-2-RS

237

MVE206SR-2-RS

239

MVE210SR-2-RS

241

MVE215SR-2-RS

5

Emergency return (1 available, 0 not available)

6

Yoke (1 Short, 0 Long)

7

Temperature sensors (1 available 0 not available)

Selection for MVE-2-RS actuator model

Defines the device version according to the table below (for EBV):

Bit number

Device description

Addr. value

Model

1
2
3
4

2

EBV65-024-010

4

EBV80-024-010

6

EBV100-024-010

8

EBV125-024-010

10

EBV150-024-010

12

EBV65-230-010

14

EBV80-230-010

16

EBV100-230-010

18

EBV125-230-010

20

EBV150-230-010

34

EBV65-024-110

36

EBV80-024-110

38

EBV100-024-110

40

EBV125-024-110

42

EBV150-024-110

44

EBV65-230-110

46

EBV80-230-110

48

EBV100-230-110

50

EBV125-230-110

52

EBV150-230-110

130

EBV65-024-011

132

EBV80-024-011

134

EBV100-024-011

136

EBV125-024-011

138

EBV150-024-011

140

EBV65-230-011

142

EBV80-230-011

144

EBV100-230-011

146

EBV125-230-011

148

EBV150-230-011

162

EBV65-024-111

164

EBV80-024-111

166

EBV100-024-111

168

EBV125-024-111

170

EBV150-024-111

172

EBV65-230-111

174

EBV80-230-111

176

EBV100-230-111

178

EBV125-230-111

180

EBV150-230-111

5

Emergency return (1 available, 0 not available)

6

Modbus/BACnet actuator version (it’s fixed to 1)

7

Temperature sensors (1 available. 0 not available)

Selection for EBV actuator model

Hardware version

Define the Hardware version of the selected actuator model (to know the hardware version, the register value must be divided by 10, e.g 1210 = 1.2).

Modbus register: 30302

Bootloader version

Define the Bootloader version of the selected actuator model (to know the bootloader version, the most significant byte must be divided by 10, the least significant byte represents the sub-version. Example: A0816 ➔ A16 = 1010 = 1.0 and 0816 = 8 ➔ 1.0.8).

Modbus register: 30303

Firmware version (extended)

Define the Firmware version of the selected actuator model (to know the extended firmware version, the most significant byte must be divided by 10, the least significant byte represents the sub-version. Example: 140116 ➔ 1416 = 2010 = 2.0 and 0116 = 1 ➔ 2.0.1).

Modbus register: 30304

Serial number 1

This value is set by production.

Modbus register: 30305

Serial number 2

This value is set by production.

Modbus register: 30306

Serial number 3

This value is set by production.

Modbus register: 30307

Serial number 4

This value is set by production.

Modbus register: 30308

Maximum flow setting

Define the caliber position according to the following values:

Addr.1004 (value)

Max. flow setting

0

1

1

1,25

2

1,5

3

1,75

4

2

5

2,25

6

2,5

7

2,75

8

3

9

3,25

10

3,5

11

3,75

12

4

13

4,25

14

4,5

15

4,75

16

5

Selection for Max flow setting

Modbus register: 41005

BACnet object: multi state value, object ID: 9, properties: present value.

Type of Control

Defines the type of actuator command signal (selectable via Modbus/BACnet only if dip switches are disabled):

Addr.1005 (value)

Type of Control

0

Modbus (the command of the actuator is set via the Modbus command into the range 0-100%). Dipswitches are disabled.

1

0 - 10 V (the Modbus connection can be present to configure and monitor the system). Dipswitches are disabled.

2

2 - 10 V (the Modbus connection can be present to configure and monitor the system). Dipswitches are disabled.

3

0 - 5 V (the Modbus connection can be present to configure and monitor the system). Dipswitches are disabled.

4

5 - 10 V (the Modbus connection can be present to configure and monitor the system). Dipswitches are disabled.

5

2 - 6 V (the Modbus connection can be present to configure and monitor the system). Dipswitches are disabled.

6

6 - 10 V (the Modbus connection can be present to configure and monitor the system). Dipswitches are disabled.

7

It indicates that the command signal is selected from dip switches (default value).

Type of control

The 4-20mA command can only be set via dip switches.

Modbus register: 41006

BACnet object: multi state value, object ID: 0, properties: present value.

Command signal action and setting of the emergency return direction

Defines the action type of the command signal (direct or reverse action) and the direction of the actuator in case of emergency return (function present only for models with emergency return).

Addr.1006 (value)

Configuration of the actuator action and Failsafe direction

bit0

Direct action (bit0=1); reverse (bit0=0)

bit1

Failsafe DOWN (bit1=1); Failsafe UP (bit1=0)

bit2

Type of stroke (0 = fixed, 1 = automatic). For EBV/MVE-2-RS this bit is fixed to 1

Selection of the action and failsafe direction of the actuator (if dip switches are disabled) via Modbus

Modbus register: 41007

BACnet object:

Bit

Object type

Object ID

Properties

Type of action

Binary value

0

Present value

Emergency return

Binary value

1

Present value

Selection of the action and failsafe direction of the actuator (if dip switches are disabled) via BACnet

Forced Calibration of the stroke

Defines the possibility of performing forced calibration of the stroke (by writing the bit0 to 1). At the end of the calibration the bit is automatically reset.

Modbus register: 41008

BACnet object: binary value, object ID: 2, properties: present value.

Enable Jumper for emergency return

Defines the enabling of the jumper for selecting the direction in case of emergency return according to the following table:

Addr.1008 (value)

Enabling

0

Jumper Disabled

1

Jumper Enabled

Enabling of the jumper of the emergency return board

Modbus register: 41009

BACnet object: binary value, object ID: 3, properties: present value.

Changeover setting

This register defines the temperature loop action according to the following table:

Addr.1009 (value)

Changeover

0

Heating (default)

1

Cooling

2

Automatic (according ΔT)

Changeover setting

Modbus register: 41010

BACnet object: binary value, object ID: 1, properties: present value.

Temperature Probe Selection

This register defines the temperature sensor to use in the loops according to the following table:

Addr.1010 (value)

Temperature probe selection

0

Supply temperature (T1) (default)

1

Return temperature (T2)

2

ΔT

Temperature probe selection

Modbus register: 41011

BACnet object: multi state value, object ID: 2, properties: present value.

Valve characteristic configuration

This register allows to set the valve movement: linear (0) or equipercentage (EQP) (1).

Modbus register: 41013

BACnet object: multi state value, object ID: 3, properties: present value.

Functions enable

Defines the enabling of the IC ACTUATOR system operating loops according to the following table:

Addr.1013 (bit)

Functions enable

bit 0

BMS control

bit 1

Enable temperature control function

bit 2

Enable min. ΔT limitation function

bit3

Enable max. temperature limitation function

bit4

Enable min. temperature limitation function

bit5

Enable power control function

bit6

Enable power limit function

bit7

Enable energy function

Functions enable via Modbus

Modbus register: 41014

BACnet object:

Value

BACnet name

BACnet object type

BACnet object ID

BACnet object property

1

BMS control

Multi state value

4

Present value

2

Temperature control function

3

Min. ΔT limitation function

4

Max. temperature limitation function

5

Min. temperature limitation function

6

Power control function

7

Power limit function

-

Energy function

Binary value

14

Present value

Functions enable via BACnet

Functions status

Defines the status of the IC ACTUATOR system operating loops according to the following table:

Addr.1014 (bit)

Functions enable

bit 0

BMS control

bit 1

Temperature control function activated

bit 2

Min. ΔT limitation function activated

bit 3

Max. temperature limitation function activated

bit 4

Min. temperature limitation function activated

bit 5

Power control function activated

Functions status

Modbus register: 31015

BACnet object: multi-state value, object ID: 5, properties: present value.

Minimum Opening Valve (%)

This register contains the minimum opening valve value (expressed as a percentage) when the limit loops are active.

Modbus register: 41016

BACnet object: analog value, object ID: 1, properties: present value.

DIP Switches & Push Button & Jumper status

Defines the status of the dip switches, the push button (used for the forced calibration of the stroke) and the jumper (used to define the direction of the emergency return) according to the following table:

Addr.1016 (bit)

DIP Switch & Push Button & Jumper Status

bit 0

Direct action (OFF ➔ bit0 = 0). Reverse action (ON ➔ bit0 = 1)

bit 1

0-10V (OFF ➔ bit1 = 0). BUS (ON ➔ bit1 = 1)

bit 2

Normal (OFF ➔ bit2 = 0). Default setting (ON ➔ bit2 = 1).

bit 3

Modbus (OFF ➔ bit3 = 0). BACnet (ON ➔ bit3 = 1).

bit 4

No action (OFF ➔ bit4 = 0). Set an EBV (ON ➔ bit4 = 1)

bit 5

Voltage control (OFF ➔ bit5 = 0). Current control 4-20mA (ON ➔ bit5 = 1).

bit 6

Push Button status (for calibration). Pressed (bit6 = 1), Released (bit6 = 0)

bit 7

Jumper status. Bit7 = 1 (failsafe DOWN). Bit7 = 0 (failsafe UP).

Information about the status of dip switches, push button and the jumper on the emergency return board

Modbus register: 31017

BACnet object: analog value, object ID: 2, properties: present value.

Valve Type

Define the valve type according to the following table:

Addr.1017

Valve type

0

Generic valve

4

Custom Energy valve

5

VLX6P

6

VLX8P

12

Custom PICV valve

13

2FGB65B-EBV

14

2FGB80B-EBV

15

2FGB100B-EBV

16

2FGB125B-EBV

17

2FGB150B-EBV

Selection for valve type

Modbus register: 41018

BACnet object: multi state value, object ID: 6, properties: present value.

Valve Stroke (mm)

This register contains the calculated valve stroke value. The value stored in the register is multiplied by 100. A value of 500 corresponds to a stroke of 5mm.

Modbus register: 41019

BACnet object: analog value, object ID: 3, properties: present value (read only).

Actuator reset

Through this register it is possible to perform a forced reset of the system by forcing its value to 1. After a few seconds automatically this value is set to 0.

Modbus register: 41034

BACnet object: binary value, object ID: 20, properties: present value.

BACnet object: Device object, into property xxxx write the value 0x3FFF.

 

Restore Factory Settings

This register allows to restore the default setting and EEPROM memory setting 1.

Writing the value to 1 will reset the memory area to the default values.

Modbus register: 41187

BACnet object: Device object, into property xxxx write the value 0x3FFF.

 

Force Fully Close

This function allows to fully close the valve even if temperature or power function are active.

To do this write 1 into the register.Modbus register: 41188

BACnet object: binary value, object ID: 17, properties: present value.

 

Force Fully Open

This function allows to fully open the valve even if temperature or power function are active.

To do this write 1 into the register Modbus register: 41189

BACnet object: binary value, object ID: 18, properties: present value.

 

Test Temperature Mode

This function allows to write manually temperature values into the supply and return temperature registers. When test temperature mode is activated, the values read from temperature sensors are not stored into the registers.

To do this write 1 into the register Modbus register: 41190

BACnet object: binary value, object ID: 19, properties: present value.

 

Diagnostic Section

Over voltage Events

The system over voltage events is stored in this address, that is:

  • 24V + 20%

  • 230V + 20%

Default value is 0 and will start from 1 with the first error event.

If the value of the register reaches the maximum limit (65534 = 0xFFFE) this value will remain in memory.

Modbus register: 41020

BACnet object: analog value, object ID: 4, properties: present value.

Under voltage Events

The system under voltage events is stored in this address, that is:

  • 24V – 20%

  • 230V – 20%

Default value is 0 and will start from 1 with the first error event.

If the value of the register reaches the maximum limit (65534 = 0xFFFE) this value will remain in memory.

Modbus register: 41021

BACnet object: analog value, object ID: 5, properties: present value.

Number of full opening events

This address stores the valve full opening events. The default value is 0 and will start from 1 which corresponds to 10 total valve opening (in order to avoid continuous writing on the memory that could damage the component). If the value of the Register reaches the maximum limit (65534 = 0xFFFE) this value will remain in memory.

Modbus register: 41022

BACnet object: analog value, object ID: 6, properties: present value.

Number of full closing events

This address stores the valve full closing events. The default value is 0 and will start from 1 which corresponds to 10 total valve opening (in order to avoid continuous writing on the memory that could damage the component). If the value of the register reaches the maximum limit (65534 = 0xFFFE) this value will remain in memory.

Modbus register: 41023

BACnet object: analog value, object ID: 7, properties: present value.

Unexpected stall events within the stroke

Unexpected stall events within the valve stroke are stored in this address. The default value is 0 and will start from 1 which corresponds to 1 unexpected stall event. If the value of the register reaches the maximum limit (65534 = 0xFFFE) this value will remain in memory.

Modbus register: 41024

BACnet object: analog value, object ID: 8, properties: present value.

Unexpected stall events outside the stroke

This address stores unexpected stall events outside the stroke valve (extra stroke). The default value is 0 and will start from 1 which corresponds to 1 unexpected stall event. If the value of the register reaches the maximum limit (65534 = 0xFFFE) this value will remain in memory.

Modbus register: 41025

BACnet object: analog value, object ID: 9, properties: present value.

Stroke calculation events greater than 60mm

This address stores the calculation events of the stroke greater than 5mm (during the calibration phase). The default value is 0 and will start from 1 which corresponds to 1 calculation event of the stroke less than 5mm. If the value of the Register reaches the maximum limit (65534 = 0xFFFE) this value will remain in memory.

Modbus register: 41026

BACnet object: analog value, object ID: 10, properties: present value.

Stroke calculation events less than 5mm

This address stores the calculation events of the stroke less than 5mm (during the calibration phase). The default value is 0 and will start from 1 which corresponds to 1 calculation event of the stroke less than 5mm. If the value of the Register reaches the maximum limit (65534 = 0xFFFE) this value will remain in memory.

Modbus register: 41027

BACnet object: analog value, object ID: 11, properties: present value.

Operating states

The operating states of the system are stored in this address according to the following table:

Addr.1027

Operating states

bit 0

Normal Running (bit0 = 1).In this state the system works normally.

bit 1

Initial positioning (bit1 = 1).After switching-on or after using the manual override, the actuator performs the initial positioning in the direction defined by the action type (direct or reverse).

bit 2

Stroke calibration (bit2 = 1).In this operating state, the actuator is calculating the valve stroke.

bit 3

Fail Safe Phase (bit3 = 1).In this operating state, the actuator is performing an emergency return.

bit 4

Manual override Phase (bit4 = 1).In this operating state, the manual override is active.

bit5

Error(bit5 = 1). If the value is 1, there is an error (the error type is shown into register 1028)

Operating mode of the actuator via Modbus

Modbus register: 31028

BACnet object:

Value

BACnet object type

BACnet object ID

BACnet object properties

1

Multi state value

7

Present value

2

3

4

5

-

Binary value

4

Present value

Operating mode of the actuator via BACnet.

Type of error

The types of errors are stored in this address according to the following table:

Addr.1028

Errors

bit 0

Supply temperature sensor error (T1). This error (bit0 = 1) indicates an out-of-scale value of the supply temperature sensor (if provided).

bit 1

Return temperature sensor error (T2). This error (bit1 = 1) indicates an out-of-scale value of the return temperature sensor (if provided).

bit 2

Input pressure sensor error (P1). This error (bit = 1) indicates an anomaly of the input pressure sensor.

bit 3

Output pressure sensor error (P2). This error (bit = 1) indicates an anomaly of the output pressure sensor.

bit 4

Calculation error of the valve stroke less than 5 mm (EBV/MVE-2-RS) or 2mm (MVC-2-RS). This error (bit4 = 1) indicates that the stroke value calculated by the calibration phase is less than 5mm (or 2mm).

bit 5

Calculation error of the valve stroke greater than 60 mm (EBV/MVE-2-RS) or 12mm (MVC-2-RS). This error (bit5 = 1) indicates that the stroke value calculated by the calibration phase is greater than 60mm (or 12mm).

bit 6

Unexpected stall error within the calculated stroke. This error (bit6 = 1) indicates an unexpected stall within the calculated stroke.

bit 7

Unexpected stall error outside the calculated stroke. This error (bit7 = 1) indicates an unexpected stall outside the calculated stroke.

bit 8

Low voltage error. This error (bit8 = 1) indicates that the value of the supply voltage is below 20% of the nominal value.

bit 9

High voltage error. This error (bit9 = 1) indicates that the value of the supply voltage is above 20% of the nominal value.

bit 10

Clock error. This error (bit10 = 1) indicates that the time and date values have not been initialized from the BMS. It’s set to 0 by the firmware once the time and date have been set.

List of the error type of the actuator

Modbus register: 31029

BACnet object:

Bit number

BACnet object type

BACnet object ID

BACnet object properties

0

Binary value

5

Present value

1

6

2

21

3

22

4

7

5

8

6

9

7

10

8

11

9

12

10

13

List of the error type of the actuator via BACnet.

Input/Output Section

Command Signal from the BMS (0 – 100%)

This register contains the value of the BMS command in the range 0-100%.

The value contained in the register is multiplied by 10 (0-1000). 

Modbus register: 41035

BACnet object: analog value, object ID: 12, properties: present value.

Feedback

This register contains the value of the valve position (feedback) in the range 0-100%.

The value contained in the register is multiplied by 10. 

Modbus register: 31038

BACnet object: analog value, object ID: 13, properties: present value.

Flow Rate Section

Max Flow Rate

Define the nominal flow rate according to the following table (for MVE-2-RS):


Define the nominal flow rate according to the following table (for MVC-2-RS):


For EBV the nominal flow rate is defined as:

Valve

Flow rate (m3/h)

2FGB65B-EBV

37

2FGB80B-EBV

59

2FGB100B-EBV

77

2FGB125B-EBV

118

2FGB150B-EBV

177

Max flow rate for EBV actuator

Modbus register: 41044

BACnet object: analog value, object ID: 14, properties: present value.

Design flow rate

Defining the design flow rate,which has to be between 25% of Qnom and Qnom (for MVE/MVC-2-RS).

For EBV, the minimum design flow rate is defined as:

Valve

Flow rate (m3/h)

2FGB65B-EBV

12

2FGB80B-EBV

25

2FGB100B-EBV

45

2FGB125B-EBV

61

2FGB150B-EBV

80

Min. flow rate for EBV actuator

BACnet object: analog value, object ID: 15, properties: present value.

Modbus register: 41045

Flow rate SP X1

This register is used only if the actuator is assembled with a custom valve and set the first value of the flow rate at 0 (fixed value). This parameter with the following ones allows to building the custom valve characteristic curve.

Modbus register: 41080

BACnet object: analog value, object ID: 16, properties: present value.

Valve position Y1

This register is used only if the actuator is assembled with a custom valve and set the first value of the valve position at 0 (fixed value). This parameter with the following ones allows to building the custom valve characteristic curve.

Modbus register: 41081

BACnet object: analog value, object ID: 17, properties: present value.

Flow rate SP X2

This register is used only if the actuator is assembled with a custom valve and allow to set the second value of the flow rate (in percent) multiplied by ten. This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41082

BACnet object: analog value, object ID: 18, properties: present value.

Valve position Y2

This register is used only if the actuator is assembled with a custom valve and allow to set the second value of the valve position (in percent) multiplied by ten. This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41083

BACnet object: analog value, object ID: 19, properties: present value.

Flow rate SP X3

This register is used only if the actuator is assembled with a custom valve and allow to set the third value of the flow rate (in percent) multiplied by ten. This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41084

BACnet object: analog value, object ID: 20, properties: present value.

Valve position Y3

This register is used only if the actuator is assembled with a custom valve and allow to set the third value of the valve position (in percent) multiplied by ten. This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41085

BACnet object: analog value, object ID: 21, properties: present value.

Flow rate SP X4

This register is used only if the actuator is assembled with a custom valve and allow to set the fourth value of the flow rate (in percent) multiplied by ten. This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41086

BACnet object: analog value, object ID: 22, properties: present value.

Valve position Y4

This register is used only if the actuator is assembled with a custom valve and allow to set the fourth value of the valve position (in percent) multiplied by ten. This parameter with the other ones, allows to building the custom valve characteristic curve.

Modbus register: 41087

BACnet object: analog value, object ID: 23, properties: present value.

Flow rate SP X5

This register is used only if the actuator is assembled with a custom valve and allow to set the fifth value of the flow rate (in percent) multiplied by ten. This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41088

BACnet object: analog value, object ID: 24, properties: present value.

Valve position Y5

This register is used only if the actuator is assembled with a custom valve and allow to set the fifth value of the valve position (in percent) multiplied by ten. This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41089

BACnet object: analog value, object ID: 25, properties: present value.

Flow rate SP X6

This register is used only if the actuator is assembled with a custom valve and allow to set the sixth value of the flow rate (in percent) multiplied by ten. This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41090

BACnet object: analog value, object ID: 26, properties: present value.

Valve position Y6

This register is used only if the actuator is assembled with a custom valve and allow to set the sixth value of the valve position (in percent) multiplied by ten. This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41091

BACnet object: analog value, object ID: 27, properties: present value.

Flow rate SP X7

This register is used only if the actuator is assembled with a custom valve and allow to set the seventh value of the flow rate (in percent) multiplied by ten. This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41092

BACnet object: analog value, object ID: 28, properties: present value.

Valve position Y7

This register is used only if the actuator is assembled with a custom valve and allow to set the seventh value of the valve position (in percent) multiplied by ten. This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41093

BACnet object: analog value, object ID: 29, properties: present value.

Flow rate SP X8

This register is used only if the actuator is assembled with a custom valve and allow to set the eighth value of the flow rate (in percent) multiplied by ten. This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41094

BACnet object: analog value, object ID: 30, properties: present value.

Valve position Y8

This register is used only if the actuator is assembled with a custom valve and allow to set the eighth value of the valve position (in percent) multiplied by ten. This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41095

BACnet object: analog value, object ID: 31, properties: present value.

Flow rate SP X9

This register is used only if the actuator is assembled with a custom valve and allow to set the nineth value of the flow rate (in percent) multiplied by ten. This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41096

BACnet object: analog value, object ID: 32, properties: present value.

Valve position Y9

This register is used only if the actuator is assembled with a custom valve and allow to set the nineth value of the valve position (in percent) multiplied by ten. This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41097

BACnet object: analog value, object ID: 33, properties: present value.

Flow rate SP X10

This register is used only if the actuator is assembled with a custom valve its value of the flow rate is set to the 100 (that multiplied by 10 is 1000) (fixed value). This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41098

BACnet object: analog value, object ID: 34, properties: present value.

Valve position Y10

This register is used only if the actuator is assembled with a custom valve its value is set to the 100 (that multiplied by 10 is 1000) (fixed value). This parameter with the other ones allows to building the custom valve characteristic curve.

Modbus register: 41099

BACnet object: analog value, object ID: 35, properties: present value.

Valve flow curve window.png
Valve flow curve window

Indicated flow rate

This register calculates the indicated flow rate as m3/h (the value is multiplied by 100) for EBV/MVE-2-RS and as l/h (no multiplied factor) for MVC-2-RS.

Modbus register: 31100

BACnet object: analog value, object ID: 36, properties: present value.

Setpoints Section

Setpoint ΔT Control Heating (°C)

This register contains the value of the setpoint for the heating ΔT control loop.

The value contained in the register is multiplied by 10.

Modbus register: 41101

BACnet object: analog value, object ID: 37, properties: present value.

Setpoint ΔT Control Cooling (°C)

This register contains the value of the setpoint for the cooling ΔT control loop.

The value contained in the register is multiplied by 10.

Modbus register: 41102

BACnet object: analog value, object ID: 38, properties: present value.

Setpoint Supply Temperature Control Heating (°C)

This register contains the value of the setpoint for the heating supply temperature loop.

The value contained in the register is multiplied by 10.

Modbus register: 41103

BACnet object: analog value, object ID: 39, properties: present value.

Setpoint Supply Temperature Control Cooling (°C)

This register contains the value of the setpoint for the cooling supply temperature loop.

The value contained in the register is multiplied by 10. 

Modbus register: 41104

BACnet object: analog value, object ID: 40, properties: present value.

Setpoint Supply Temperature Control Heating (°C)

This register contains the value of the setpoint for the heating return temperature loop.

The value contained in the register is multiplied by 10.

Modbus register: 41105

BACnet object: analog value, object ID: 41, properties: present value.

Setpoint Supply Temperature Control Cooling (°C)

This register contains the value of the setpoint for the cooling return temperature loop.

The value contained in the register is multiplied by 10.

Modbus register: 41106

BACnet object: analog value, object ID: 42, properties: present value.

Setpoint Minimum ΔT Heating (°C)

This register contains the value of the setpoint for the heating ΔT limitation loop.

The value contained in the register is multiplied by 10.

Modbus register: 41107

BACnet object: analog value, object ID: 43, properties: present value.

Setpoint Minimum ΔT Cooling (°C)

This register contains the value of the setpoint for the cooling ΔT limitation loop.

The value contained in the register is multiplied by 10.

Modbus register: 41108

BACnet object: analog value, object ID: 44, properties: present value.

Setpoint Max. Supply Temperature Heating (°C)

This register contains the value of the setpoint for the heating supply temperature limitation loop.

The value contained in the register is multiplied by 10.

Modbus register: 41109

BACnet object: analog value, object ID: 45, properties: present value.

Setpoint Min. Supply Temperature Cooling (°C)

This register contains the value of the setpoint for the cooling supply temperature limitation loop.

The value contained in the register is multiplied by 10. 

Modbus register: 41110

BACnet object: analog value, object ID: 46, properties: present value.

Setpoint Max. Return Temperature Heating (°C)

This register contains the value of the setpoint for the heating return temperature limitation loop.

The value contained in the register is multiplied by 10.

Modbus register: 41111

BACnet object: analog value, object ID: 47, properties: present value.

Setpoint Min. Return Temperature Cooling (°C)

This register contains the value of the setpoint for the cooling return temperature limitation loop.

The value contained in the register is multiplied by 10.

Modbus register: 41112

BACnet object: analog value, object ID: 48, properties: present value.

Power Control/Limit Section

Design Power

This register allows to set the maximum power control, this value is multiplied by 10 (kW).

Modbus register: 41113

BACnet object: analog value, object ID: 49, properties: present value.

Set Max Power Limit

This register allows to set the maximum power limit, this value is multiplied by 10 (kW).

Modbus register: 41114

BACnet object: analog value, object ID: 50, properties: present value.

Temperature Sensors Section

Supply Temperature (°C)

This register contains the supply temperature value. The value stored in the register is multiplied by 10.

If the sensor is disconnected or faulty, the stored value is 5000.

Modbus register: 31115

BACnet object: analog input, object ID: 0, properties: present value.

Return Temperature (°C)

This register contains the return temperature value.

The value stored in the register is multiplied by 10.

If the sensor is disconnected or faulty, the stored value is 5000.

Modbus register: 31116

BACnet object: analog input, object ID: 1, properties: present value.

ΔT (°C)

This register contains the value of the difference between the supply and return temperatures (ΔT).

The value stored in the register is multiplied by 10.

If the supply and/or return temperature sensor is disconnected or faulty, the stored value is 5000.

Modbus register: 31117

BACnet object: analog value, object ID: 51, properties: present value.

Energy Heating/Cooling Section

Instant power

This register calculates the instant power (kW*10).

Modbus register: 31120

BACnet object: analog value, object ID: 52, properties: present value.

Heating energy LSR

This register contains the least significant data of the total calculated heating energy (kWh*10).

Modbus register: 31121

BACnet object: analog value, object ID: 53, properties: present value.

Heating energy MSR

This register contains the most significant data of the total calculated heating energy (kWh*10).

Modbus register: 31122

BACnet object: analog value, object ID: 53, properties: present value.

Cooling energy LSR

This register contains the least significant data of the total calculated cooling energy (kWh*10).

Modbus register: 31123

BACnet object: analog value, object ID: 54, properties: present value.

Cooling energy MSR

This register contains the most significant data of the total calculated cooling energy (kWh*10).

Modbus register: 31124

BACnet object: analog value, object ID: 54, properties: present value.

Heating energy at 31/12 LSR

This register allows to read for the least significant data of the total heating energy (kWh*10) at the end of the year.

Modbus register: 31139

BACnet object: analog value, object ID: 55, properties: present value.

Heating energy at 31/12 MSR

This register allows to read for the most significant data of the total heating energy (kWh*10) at the end of the year.

Modbus register: 31140

BACnet object: analog value, object ID: 55, properties: present value.

Heating energy value 1

This register contains the energy (heating) consumption (MWh*10) for the month of January.

Modbus register: 31141

BACnet object: analog value, object ID: 56, properties: present value.

Heating energy value 2

This register contains the energy (heating) consumption (MWh*10) for the month of February.

Modbus register: 31142

BACnet object: analog value, object ID: 57, properties: present value.

Heating energy value 3

This register contains the energy (heating) consumption (MWh*10) for the month of March.

Modbus register: 31143

BACnet object: analog value, object ID: 58, properties: present value.

Heating energy value 4

This register contains the energy (heating) consumption (MWh*10) for the month of April.

Modbus register: 31144

BACnet object: analog value, object ID: 59, properties: present value.

Heating energy value 5

This register contains the energy (heating) consumption (MWh*10) for the month of May.

Modbus register: 31145

BACnet object: analog value, object ID: 60, properties: present value.

Heating energy value 6

This register contains the energy (heating) consumption (MWh*10) for the month of June.

Modbus register: 31146

BACnet object: analog value, object ID: 61, properties: present value.

Heating energy value 7

This register contains the energy (heating) consumption (MWh*10) for the month of July.

Modbus register: 31147

BACnet object: analog value, object ID: 62, properties: present value.

Heating energy value 8

This register contains the energy (heating) consumption (MWh*10) for the month of August.

Modbus register: 31148

BACnet object: analog value, object ID: 63, properties: present value.

Heating energy value 9

This register contains the energy (heating) consumption (MWh*10) the month of September.

Modbus register: 31149

BACnet object: analog value, object ID: 64, properties: present value.

Heating energy value 10

This register contains the energy (heating) consumption (MWh*10) for the month of October.

Modbus register: 31150

BACnet object: analog value, object ID: 65, properties: present value.

Heating energy value 11

This register contains the energy (heating) consumption (MWh*10) for the month of November.

Modbus register: 31151

BACnet object: analog value, object ID: 66, properties: present value.

Heating energy value 12

This register contains the energy (heating) consumption (MWh*10) for the month of December.

Modbus register: 31152

BACnet object: analog value, object ID: 67, properties: present value.

Cooling energy at 31/12 LSR

This register allows to read the least significant data of the total cooling energy (kWh*10) at the end of the year.

Modbus register: 31153

BACnet object: analog value, object ID: 68, properties: present value.

Cooling energy at 31/12 MSR

This register contains the most significant data of the total cooling energy (kWh*10) at the end of the year.

Modbus register: 31154

BACnet object: analog value, object ID: 68, properties: present value.

Cooling energy value 1

This register contains the energy (cooling) consumption (MWh*10) for the month of January.

Modbus register: 31155

BACnet object: analog value, object ID: 69, properties: present value.

Cooling energy value 2

This register contains the energy (cooling) consumption (MWh*10) for the month of February.

Modbus register: 31156

BACnet object: analog value, object ID: 70, properties: present value.

Cooling energy value 3

This register contains the energy (cooling) consumption (MWh*10) for the month of March.

Modbus register: 31157

BACnet object: analog value, object ID: 71, properties: present value.

Cooling energy value 4

This register contains the energy (cooling) consumption (MWh*10) for the month of April.

Modbus register: 31158

BACnet object: analog value, object ID: 72, properties: present value.

Cooling energy value 5

This register contains the energy (cooling) consumption (MWh*10) for the month of May.

Modbus register: 31159

BACnet object: analog value, object ID: 73, properties: present value.

Cooling energy value 6

This register contains the energy (cooling) consumption (MWh*10) for the month of June.

Modbus register: 31160

BACnet object: analog value, object ID: 74, properties: present value.

Cooling energy value 7

This register contains the energy (cooling) consumption (MWh*10) for the month of July.

Modbus register: 31161

BACnet object: analog value, object ID: 75, properties: present value.

Cooling energy value 8

This register contains the energy (cooling) consumption (MWh*10) for the month of August.

Modbus register: 31162

BACnet object: analog value, object ID: 76, properties: present value.

Cooling energy value 9

This register contains the energy (cooling) consumption (MWh*10) for the month of September.

Modbus register: 31163

BACnet object: analog value, object ID: 77, properties: present value.

Cooling energy value 10

This register contains the energy (cooling) consumption (MWh*10) for the month of October.

Modbus register: 31164

BACnet object: analog value, object ID: 78, properties: present value.

Cooling energy value 11

This register contains the energy (cooling) consumption (MWh*10) for the month of November.

Modbus register: 31165

BACnet object: analog value, object ID: 79, properties: present value.

Cooling energy value 12

This register contains the energy (cooling) consumption (MWh*10) for the month of December.

Modbus register: 31166

BACnet object: analog value, object ID: 80, properties: present value.

Clock Function Section

Clock Minutes

This database register contains the value of the minutes received during the time synchronization phase.

Modbus register: 41182

BACnet object:

Analog value object

Device object

Object ID

Property

Object ID

Property

81

Present value

1

Local time

Clock Minutes object in BACnet

Clock Hours

This register contains the value of the hours received during the time synchronization phase.

Modbus register: 41183

BACnet object:

Analog value object

Device object

Object ID

Property

Object ID

Property

82

Present value

1

Local time

Clock Hours object in BACnet

Clock Day

This register contains the value of the day received during the time synchronization phase.

Modbus register: 41184

BACnet object:

Analog value object

Device object

Object ID

Property

Object ID

Property

83

Present value

1

Local date

Clock Day object in BACnet

Clock Month

This register contains the value of the month received during the time synchronization phase.

Modbus register: 41185

BACnet object:

Analog value object

Device object

Object ID

Property

Object ID

Property

84

Present value

1

Local date

Clock Month object in BACnet

Clock Year

This register contains the value of the year received during the time synchronization phase.

Registers from address 1181 to address 1185 contain the values that store the date and time of the actuator once they have been synchronized (only necessary in the case of energy calculation).

The actuator doesn’t have a “buffer” battery so that every time it is turned off or reset the date and time are lost, a new synchronization will therefore be required. If the date and time are not synchronized, the default date/time is: 01/01/2000 00:00.

Modbus register: 41186

BACnet object:

Analog value object

Device object

Object ID

Property

Object ID

Property

85

Present value

1

Local date

Clock Year object in BACnet

Loop Output Section

Loop Output Dynamic Balancing (EBV only)

This register contains the percentage output value of the dynamic balancing loop.

The value inside the register is multiplied by 10.

Modbus register: 31192

Loop Output BMS (%)

This register contains the percentage output value of the BMS loop.

The value inside the register is multiplied by 10.

Modbus register: 31193

Loop Output flow rate control (MVE/MVC-2-RS only)

This register contains the percentage output value of the output flow rate control loop.

The value inside the register is multiplied by 10.

Modbus register: 31194

Loop Output power

This register contains the percentage output value of the power loop.

If one or both of the temperature sensors are disconnected or faulty, the stored value is 65535.

The value inside the register is multiplied by 10.

Modbus register: 31196

Loop Output power limit

This register contains the percentage output value of the power limit loop.

If one or both of the temperature sensors are disconnected or faulty, the stored value is 65535.

The value inside the register is multiplied by 10.

Modbus register: 31197

Loop Output Temperature Control (%)

This register contains the percentage output value of the Temperature control loop.

If one or both of the temperature sensors are disconnected or faulty, the stored value is 5000.

The value inside the register is multiplied by 10.

Modbus register: 31198

Loop Output Temperature Limitations (%)

This register contains the percentage output value of the Temperature limit loop.

If one or both of the temperature sensors are disconnected or faulty, the stored value is 5000.

The value inside the register is multiplied by 10.

Modbus register: 31199

Operating loop output (%)

This register contains the percentage out value of the operating loop resulting from the actually enabled functions.

The value inside the register is multiplied by 10.

Modbus register: 31200

Power Section

Max. power

This register allows to set of the valve nominal power (kW*10).

Modbus register: 41207

BACnet object: analog value, object ID: 86, properties: present value.

Media density

This register allows to set the density of the fluid, the default value is for water at 20°C (997.8 Kg/m3). The value is multiplied by 10, so in the register is: 9978.

The maximum value is 6553.5.

Modbus register: 41208

BACnet object: analog value, object ID: 87, properties: present value.

 Media specific heat

This database register allows to set the specific heat of the fluid, the default value is for water at 20°C (4196 J/Kg °C). The value is multiplied by 10, so in the register is: 41960.

The maximum value is 6553.5.

Modbus register: 41209

BACnet object: analog value, object ID: 88, properties: present value.

Custom nominal power ΔT 20K

This register contains the valve nominal power at 20°C (kW*10).

Modbus register: 31213

Loop Parameters Section

Action Type

This database register contains the type of loop action that can be:

Addr.1230

Action type

0

Proportional (P)

1

Proportional Integral (PI)

2

Proportional Integral Derivative (PID)

Selection of the action type

Modbus register: 41231

BACnet object: multi state value, object ID: 8, properties: present value.

Derivative Time

This register contains the derivative time of the derivative action expressed as "gain" from 1 to 10 (default value is 1).

Modbus register: 41232

BACnet object: analog value, object ID: 89, properties: present value.

Integral Time (min)

This register contains the integral time of the integral action expressed in minutes from 0 to 30.

Modbus register: 41233

BACnet object: analog value, object ID: 90, properties: present value.

Proportional Bandwidth (°C)

This register contains the proportional bandwidth for all loops. The value stored in the register is multiplied by 10, so the range is from 0 to 100 (from 0 to 10°C)

Modbus register: 41234

BACnet object: analog value, object ID: 91, properties: present value.

Month timestamp of 31st December

This register allows to read the year end month total energy, it is set to December.

Modbus register: 31241

BACnet object: analog value, object ID: 92, properties: present value.

Year timestamp of 31st December

This register allows to read the year of the last reading recorded on 31 December.

Modbus register: 31242

BACnet object: analog value, object ID: 93, properties: present value.

Month timestamp of value 1

This register contains the month in which the actuator has registered the energy consumption, it is set to January.

Modbus register: 31243

BACnet object: analog value, object ID: 94, properties: present value.

Year timestamp of value 1

This register contains the year in which the actuator has registered the energy consumption in January.

Modbus register: 31244

BACnet object: analog value, object ID: 95, properties: present value.

Month timestamp of value 2

This register contains the month in which the actuator has registered the energy consumption, it is set to February.

Modbus register: 31245

BACnet object: analog value, object ID: 96, properties: present value.

Year timestamp of value 2

This register contains the year in which the actuator has registered the energy consumption in February.

Modbus register: 31246

BACnet object: analog value, object ID: 97, properties: present value.

Month timestamp of value 3

This register contains the month in which the actuator has registered the energy consumption, it is set to March.

Modbus register: 31247

BACnet object: analog value, object ID: 98, properties: present value.

Year timestamp of value 3

This register contains the year in which the actuator has registered the energy consumption in March.

Modbus register: 31248

BACnet object: analog value, object ID: 99, properties: present value.

Month timestamp of value 4

This register contains the month in which the actuator has registered the energy consumption, it is set to April.

Modbus register: 31249

BACnet object: analog value, object ID: 100, properties: present value.

Year timestamp of value 4

This register contains the year in which the actuator has registered the energy consumption in April.

Modbus register: 31250

BACnet object: analog value, object ID: 101, properties: present value.

Month timestamp of value 5

This register contains the month in which the actuator has registered the energy consumption, it is set to May.

Modbus register: 31251

BACnet object: analog value, object ID: 102, properties: present value.

Year timestamp of value 5

This register contains the year in which the actuator has registered the energy consumption in May.

Modbus register: 31252

BACnet object: analog value, object ID: 103, properties: present value.

Month timestamp of value 6

This register contains the month in which the actuator has registered the energy consumption, it is set to June.

Modbus register: 31253

BACnet object: analog value, object ID: 104, properties: present value.

Year timestamp of value 6

This register contains the year in which the actuator has registered the energy consumption in June.

Modbus register: 31254

BACnet object: analog value, object ID: 105, properties: present value.

Month timestamp of value 7

This register contains the month in which the actuator has registered the energy consumption, it is set to July.

Modbus register: 31255

BACnet object: analog value, object ID: 106, properties: present value.

Year timestamp of value 7

This register contains the year in which the actuator has registered the energy consumption in July.

Modbus register: 31256

BACnet object: analog value, object ID: 107, properties: present value.

Month timestamp of value 8

This register contains the month in which the actuator has registered the energy consumption, it is set to August.

Modbus register: 31257

BACnet object: analog value, object ID: 108, properties: present value.

Year timestamp of value 8

This register contains the year in which the actuator has registered the energy consumption in August.

Modbus register: 31258

BACnet object: analog value, object ID: 109, properties: present value.

Month timestamp of value 9

This register contains the month in which the actuator has registered the energy consumption, it is set to September.

Modbus register: 31259

BACnet object: analog value, object ID: 110, properties: present value.

Year timestamp of value 9

This register contains the year in which the actuator has registered the energy consumption in September.

Modbus register: 31260

BACnet object: analog value, object ID: 111, properties: present value.

Month timestamp of value 10

This register contains the month in which the actuator has registered the energy consumption, it is set to October.

Modbus register: 31261

BACnet object: analog value, object ID: 112, properties: present value.

Year timestamp of value 10

This register contains the year in which the actuator has registered the energy consumption in October.

Modbus register: 31262

BACnet object: analog value, object ID: 113, properties: present value.

Month timestamp of value 11

This register contains the month in which the actuator has registered the energy consumption, it is set to November.

Modbus register: 31263

BACnet object: analog value, object ID: 114, properties: present value.

Year timestamp of value 11

This register contains the year in which the actuator has registered the energy consumption in November.

Modbus register: 31264

BACnet object: analog value, object ID: 115, properties: present value.

Month timestamp of value 12

This register contains the month in which the actuator has registered the energy consumption, it is set to December.

Modbus register: 31265

BACnet object: analog value, object ID: 116, properties: present value.

Year timestamp of value 12

This register contains the year in which the actuator has registered the energy consumption in December.

Modbus register: 31266

BACnet object: analog value, object ID: 117, properties: present value.