The RAC18-IP controller works with three types of dedicated panels:
-
Touch Point panel;
-
Control Point panel;
-
LP panel with LCD display;
-
SP panel without display, fully passive;
-
FP panel.
The default application allows the user to select, which temperature sensor source is chosen to control algorithm.
The sensor is selected by the S3 DIP switches number 5 and 6.
|
No. |
Name |
Switches Configuration |
Function |
|
|---|---|---|---|---|
|
5 |
CV temperature source |
5 off |
6 off |
Panel |
|
5 off |
6 on |
Room sensor SI3 |
||
|
6 |
5 on |
6 off |
Air return temp SI1 |
|
|
5 on |
6 on |
Slave |
||
Sensor selection with the CFG DIP switch