List of BACnet Obejcts

Warning!

Please note that the following table contains objects for all series of the Touch Point panels.

The Touch Point VAV series by default has no fan control and objects referring to fan control are inapplicable. If the fan control is activated on the Touch Point VAV series panel, the objects become applicable too.

Objects referring to the fan control, occupancy, and setpoints control are inapplicable to the Touch Point Network Sensor series.

BACnet Type & ID

BACnet Property

Decimal Address

Hex

Object Name

Access

Default Value

Value Range

Description

Device

3030

0

0x00

VERSION_TYPE

Read/write

Shows version and type of the panel and enables 1 of 4 available actions

Device

5101

3

0x03

RECEIVED_FRAMES_COUNTER

Read-only

0

The number of received Modbus frames reset at the start of the panel and at the change of transmission parameters

Device

5103

5

0x05

ERROR_FRAMES_COUNTER

Read-only

0

The number of received error Modbus frames reset at the start of the panel and at the change of transmission parameters

Device

5104

7

0x07

TRANSMITTED_FRAME_COUNTER

Read-only

0

The number of transmitted Modbus frames reset at the start of the panel and at the change of transmission parameters

AI0

Present Value

11

0x0B

LIVE_TIME

Read-only

Uptime of the panel in seconds

Device

Object Identifier

14

0x0E

BACNET_DEVICE_ID

Read/write

0xFFFFFFFF

Device's BACnet ID

Device

3084

16

0x10

BAUD_RATE

Read/write

11520

Sets the baud rate

MSI1

Present Value

28

0x1C

SENSORS

Read-only

Informs about built-in sensors

AI1

Present Value

200

0xC8

BACKLIGHT_LCD

Read-only

Actual display illumination value

AI2

Present Value

201

0xC9

BACKLIGHT_KEYPAD

Read-only

Actual keypad illumination value

204

0xCC

DEVICE_CONFIGURATION

Read/write

BO0

Present Value

BUZZER_ACTIVE

1

Activates (1) or deactivates (0) a buzzer

BO3

Present Value

LCD_BACKLIGHT_ACTIVE

1

Switches the LCD background illumination on (1)

BO4

Present Value

KEYPAD_BACKLIGHT_ACTIVE

1

Switches the keypad background illumination on (1)

BO5

Present Value

CO2_ALARM_LCD

Switches on the function of LCD background illumination flashing when CO2 alarm occurs

BO6

Present Value

CO2_ALARM_BUZZER

Switches on a buzzer when the CO2 alarm occurs

BO63

Present Value

CO2_ALARM_CONFIRM

1

Allows to enable confirmation of the CO2 alarm with any button of the panel

BO11

Present Value

PANEL_OFF

0

Switches the panel off (1)

BO12

Present Value

KEYPAD_OFF

0

Switches the panel keypad off (1)

AO3

Present Value

206

0xCE

BACKLIGHT_LCD_ACTIVE

Read/write

60

Contains a value of the LCD display illumination in the active mode (expressed in %)

AO4

Present Value

207

0xCF

BACKLIGHT_LCD_IDLE

Read/write

40

Contains a value of the LCD display illumination in the idle mode (expressed in %)

AO5

Present Value

208

0xD0

BACKLIGHT_LCD_STANDBY

Read/write

0

Contains a value of the LCD display illumination in the standby mode (expressed in %)

AO6

Present Value

209

0xD1

BACKLIGHT_LCD_TIME_TO_IDLE

Read/write

10

Sets the time after which the LCD display goes from the active mode to idle (expressed in seconds)

AO7

Present Value

210

0xD2

BACKLIGHT_LCD_TIME_TO_STANDBY

Read/write

5

Sets the time after which the LCD display goes from the idle mode to standby (expressed in seconds)

AO8

Present Value

211

0xD3

BACKLIGHT_KEYPAD_ACTIVE

Read/write

10

Contains a value of the keypad illumination in the active mode (expressed in %)

AO9

Present Value

212

0xD4

BACKLIGHT_KEYPAD_IDLE

Read/write

40

Contains a value of the keypad illumination in the idle mode (expressed in %)

AO10

Present Value

213

0xD5

BACKLIGHT_KEYPAD_STANDBY

Read/write

60

Contains a value of the keypad illumination in the standby mode (expressed in %)

AO11

Present Value

214

0xD6

BACKLIGHT_KEYPAD_TIME_TO_IDLE

Read/write

10

Sets the time after which the keypad goes from the active mode to idle (expressed in seconds)

AO12

Present Value

215

0xD7

BACKLIGHT_KEYPAD_TIME_TO_STANDBY

Read/write

5

Sets the time after which the keypad goes from the idle mode to standby (expressed in seconds)

AO13

Present Value

216

0xD8

REFRESH_TIME

5

1-60

Sets the duration of the display time of particular parameters

218

0xDA

ICON_DISPLAY

Read/write

BO22

Present Value

ECO

Switches on an ECO LED

AO17

Present Value

223

0xDF

EXIT_EDIT_TIME

Read/write

Sets the time after which edition of any editable parameter is finished

AO19

Present Value

225

0xE1

CO2_SETPOINT_FOR_ALARM

Read/write

1500

CO2 alarm setpoint

AO20

Present Value

226

0xE2

CO2_HYSTERESIS_FOR_ALARM

Read/write

100

CO2 alarm hysteresis

BI0

Present Value

229

0xE5

ALARM_STATUS

Read-only

CO2 current alarm status

MSV5

Present Value

230

0xE6

NAVIGATIONAL_LED_MODE

Read/write

1

0-4

Sets a mode of the navigational LED

AO22

Present Value

231

0xE7

NAVIGATIONAL_LED_BRIGHTNESS

Read/write

100

0-100

Navigational LED brightness

AO23

Present Value

232

0xE8

NAVIGATIONAL_LED_RED

Read/write

100

0-100

Navigational LED color - red component intensity

AO24

Present Value

233

0xE9

NAVIGATIONAL_LED_GREEN

Read/write

100

0-100

Navigational LED color - green component intensity

AO25

Present Value

234

0xE10

NAVIGATIONAL_LED_BLUE

Read/write

100

0-100

Navigational LED color - blue component intensity

AI4

Present Value

300

0x12C

TEMPERATURE_SENSOR

Read-only

Actual temperature sensor value with offset

AI5

Present Value

301

0x12D

HUMIDITY_SENSOR

Read-only

Actual humidity sensor value with offset

AI6

Present Value

302

0x12E

CO2_SENSOR

Read-only

Actual CO2 sensor value with offset

AI4

4205

303

0x12F

TEMPERATURE_SENSOR_OFFSET

Read/write

0

Temperature sensor offset

AI5

4205

304

0x130

HUMIDITY_SENSOR_OFFSET

Read/write

0

Humidity sensor offset

AI6

4205

305

0x131

CO2_SENSOR_OFFSET

Read/write

0

CO2 sensor offset

AI4

4003

306

0x132

TEMPERATURE_FILTER

Read/write

60

Filtering time for the temperature sensor (seconds)

AI5

4003

307

0x133

HUMIDITY_FILTER

Read/write

60

Filtering time for the humidity sensor (seconds)

AI6

4003

308

0x134

CO2_FILTER

Read/write

60

Filtering time for the CO2 sensor (seconds)

315

0x13B

TEMPERATURE_CONFIGURATION

Read/write

AI4

Out Of Service

ACTIVE

1

Activates/deactivates the sensor

AI4

4202

THIRD_POINT_ACTIVE

Sets decimal places

316

0x13C

HUMIDITY_CONFIGURATION

Read/write

AI5

Out Of Service

ACTIVE

1

Activates/deactivates the sensor

AI5

4202

THIRD_POINT_ACTIVE

Sets decimal places

317

0x13D

CO2_CONFIGURATION

Read/write

AI6

Out Of Service

ACTIVE

1

Activates/deactivates the sensor

AO27

Present Value

322

0x142

BUZZER_VOLUME

Read/write

50

0-100

Buzzer volume (%)

AO28

Present Value

323

0x143

BUZZER_FREQUENCY

Read/write

400

20-20000

Buzzer frequency (Hz)

Device

3020

1301

0x515

FLASH_HW_VERSION

Read-only

HW version

AV56

Present Value

1500

0x5DC

SETPOINT_VALUE

Read/write

0-500

Temperature setpoint value

AI 3

Present Value

1501

0x5DD

EFFECTIVE_SETPOINT

Read-only

Sum of setpoint and offset values

AV 57

Present Value

1502

0x5DE

DEFAULT_SETPOINT

Read/write

210

0-500

Default temperature setpoint

AV 58

Present Value

1503

0x5DF

OFFSET_SETPOINT

Read/write

0

0-500

Temperature offset for setpoint

AV 56

Low Limit

1504

0x5E0

SETPOINT_LOW_LIMIT

Read/write

180

Min. available setpoint value

AV 56

High Limit

1505

0x5E1

SETPOINT_HIGH_LIMIT

Read/write

240

Max. available setpoint value

AV 59

Present Value

1506

0x5E2

OFFSET_RANGE

Read/write

30

0-500

Limits offset value

AV 56

4206

1507

0x5E3

SETPOINT_STEP

Read/write

10

Setpoint step value

1512

0x5E8

SETPOINT_CONFIGURATION

Read/write

Setpoint configuration of parameters: Visible, Editable, Operating mode, Setpoint display, ThirdPointActive

AV56

Out Of Service

VISIBLE

Enables or disables the temperature setpoint to be visible on the panel's display

AV56

4200

EDITABLE

Enables or disables editing of the temperature setpoint locally from the panel

BO55

Present Value

OPERATING_MODE

Sets the operating mode of the temperature setpoint configuration

BO56

Present Value

SETPOINT_DISPLAY

Configures the temperature setpoint display

AV56

4202

THIRD_POINT_ACTIVE

Enables or disables decimal values in the temperature setpoint

MSV0

Present Value

1600

0x640

FAN_CURRENT_SPEED

Read/write

0

Not available for the Touch Point VAV series.

Fan speed

MSV1

Present Value

1601

0x641

FAN_MODE

Read/write

1

Not available for the Touch Point VAV series.

Fan mode

MSV2

Present Value

1602

0x642

FAN_TYPE

Read/write

Not available for the Touch Point VAV series.

Fan type

41614

1613

0x64D

FAN_CONFIGURATION

Read/write

2

Not available for the Touch Point VAV series.

MSV1

Editable

EDITABLE

Not available for the Touch Point VAV series.

Activates or inactivated editing fan modes locally in the panel

BO58

Present Value

FAN_PART_EDITABLE

Not available for the Touch Point VAV series.

Configures editing of fan modes

BO60

Present Value

FAN_CONFIG_LOCAL_MODE 

Not available for the Touch Point VAV series.

Local/BMS mode

MSV3

Present Value

1700

0x6A4

OCCUPANCY_CURRENT_STATUS

Read/write

Occupancy status

MSV4

Present Value

1701

0x6A5

OCCUPANCY_MODE

Read/write

Occupancy mode

1706

0x6AA

OCCUPANCY_CONFIGURATION

Read/write

2

MSV4

4200

EDITABLE

Activates or inactivated editing occupancy statutes locally in the panel

BO62

Present Value

OCCUPANCY_CONFIG_LOCAL_MODE

Local/BMS mode

List of BACnet objects