Published article
Issue
After upgrading the AAC20’s firmware to 6.4 version and trying to connect to the controller using the iSMA Tool 1.2.6, a dialog window with missing manifests notification is displayed:
Possible cause and solutions
iSMA Tool 1.2.6 does not contain kits manifest compatible with the 6.4 firmware.
Solution 1
If using the iSMA Tool 1.2.6, it is required to:
-
download the newest AAC20 software bundle from https://support.ismacontrolli.com/03%20HVAC%20%26%20Plant%20Control/iSMA-B-AAC20/Software%20Bundle/;
-
unzip the file and go to iSMA Tool and select:
Sedona→Import Sedona Files;
-
go to the downloaded software bundle and select a zipped iC_kits file from the Kits folder;
-
confirm.
After confirmation, a success dialog window should appear:
The controller is now ready for connecting.
Solution 2
The other option is to install and use the iC Tool 1.5 for AAC20 configuration. It is available to download here: https://support.ismacontrolli.com/Software%20%26%20Tools/iC%20Tool/Software/
In the iC Tool, newest versions of kits are imported by default and, therefore, there should be no problem with missing manifests.