Name |
Units |
Access |
Modbus Address |
BACnet Object |
Default Value |
Description |
|
|---|---|---|---|---|---|---|---|
|
DischargeTemp |
ºC |
RO |
1000 |
AV0 |
N/a |
Discharge Air Temperature sensor reading |
|
|
ReturnTemp |
ºC |
RO |
1002 |
AV1 |
N/a |
Return Air Temperature sensor reading |
|
|
OutsideTemp |
ºC |
RO |
1004 |
AV2 |
N/a |
Outside Air Temperature sensor reading |
|
|
ReturnWTemp |
ºC |
RO |
1006 |
AV3 |
N/a |
Return Water Temperature sensor reading |
|
|
DischargePress |
Pa |
RO |
1008 |
AV4 |
N/a |
Discharge Air Pressure sensor reading |
|
|
ReturnPress |
Pa |
RO |
1010 |
AV5 |
N/a |
Return Air Pressure sensor reading |
|
|
CO2 |
ppm |
RO |
1012 |
AV6 |
N/a |
CO2 concentration sensor reading |
|
|
DischargeHum |
%RH |
RO |
1014 |
AV7 |
N/a |
Discharge Air Humidity sensor reading |
|
|
ReturnHum |
%RH |
RO |
1016 |
AV8 |
N/a |
Return Air Humidity sensor reading |
|
|
CoolLimTemp |
ºC |
RO |
1018 |
AV9 |
N/a |
Cooling Limit air temperature sensor reading |
|
|
MedMixExTemp |
ºC |
RO |
1020 |
AV10 |
N/a |
Medium, Mixing or Exhaust Temperature sensor reading |
|
|
OutsideHum |
%RH |
RO |
1022 |
AV11 |
N/a |
Outside Air Humidity sensor reading |
|
|
PlantMode |
N/a |
RO |
1038 |
MV0 |
N/a |
Plant Mode reading set according to schedule event |
|
|
Modbus |
BACnet |
||||||
|
0 – Off 2 – Night cycle 4 – Occupied period |
1 - Off 3 - Night cycle 5 - Occupied period |
||||||
|
ERdiffPressure |
N/a |
RO |
2000:0 |
BV0 |
N/a |
Differential pressure switch on the exchanger status reading |
|
|
Filters |
N/a |
RO |
2000:1 |
BV1 |
N/a |
Differential pressure switch on the filters - common status reading |
|
|
Thermostat |
N/a |
RO |
2000:2 |
BV2 |
N/a |
(Pre)Heater freeze thermostat status reading |
|
|
PreHPumpStatus |
N/a |
RO |
2000:3 |
BV3 |
N/a |
(Pre)Heater pump status reading |
|
|
FanDiffPressure |
N/a |
RO |
2000:4 |
BV4 |
N/a |
Differential pressure switch on the fans -common status reading |
|
|
OperationSwitch |
N/a |
RO |
2000:5 |
BV5 |
N/a |
Manual operation switch status reading |
|
|
HumidifierStatus |
N/a |
RO |
2000:6 |
BV6 |
N/a |
Humidifier status reading |
|
|
ReHPumpStatus |
N/a |
RO |
2000:7 |
BV7 |
N/a |
ReHeater pump status reading |
|
|
Hygrostat |
N/a |
RO |
2000:8 |
BV8 |
N/a |
High Limit Hygrostat status reading |
|
|
ERStatus |
N/a |
RO |
2000:9 |
BV9 |
N/a |
Exchanger status reading |
|
|
Reset |
N/a |
RO |
2001:15 |
BV21 |
N/a |
Manual reset input reading (for MIX18 only) |
|
|
DischargeFanControl |
% |
RO |
1024 |
AV12 |
N/a |
Discharge Fan Control output reading |
|
|
ReturnFanControl |
% |
RO |
1026 |
AV13 |
N/a |
Return Fan Control output reading |
|
|
ERControl |
% |
RO |
1028 |
AV14 |
N/a |
Exchanger Control output reading |
|
|
PreHeatValve |
% |
RO |
1030 |
AV15 |
N/a |
(Pre)Heater Valve actuator output reading |
|
|
CoolValve |
% |
RO |
1032 |
AV16 |
N/a |
Cooler Valve actuator output reading |
|
|
ReHeatValve |
% |
RO |
1034 |
AV17 |
N/a |
ReHeater Valve actuator output reading |
|
|
HumidifierControl |
% |
RO |
1036 |
AV18 |
N/a |
Humidifier Control output reading |
|
|
DampersCommand |
N/a |
RO |
2000:10 |
BV10 |
N/a |
Dampers Command output state reading |
|
|
FansCommand |
N/a |
RO |
2000:11 |
BV11 |
N/a |
Fans Command output state reading |
|
|
PreHeatPump |
N/a |
RO |
2000:12 |
BV12 |
N/a |
(Pre)Heater Pump Command output state reading |
|
|
ERCommand |
N/a |
RO |
2000:13 |
BV13 |
N/a |
Exchanger Command output state reading |
|
|
HumidifierCommand |
N/a |
RO |
2000:14 |
BV14 |
N/a |
Humidifier Command output state reading |
|
|
ReHeatPump |
N/a |
RO |
2000:15 |
BV15 |
N/a |
ReHeater Pump Command output state reading |
|
|
FanFailureAlarm |
N/a |
RO |
2001:0 |
BV16 |
N/a |
Fan Failure Alarm state reading |
|
|
PreHeatPumpAlarm |
N/a |
RO |
2001:1 |
BV17 |
N/a |
(Pre)Heater Pump Failure Alarm state reading |
|
|
ReHeatPumpAlarm |
N/a |
RO |
2001:2 |
BV18 |
N/a |
ReHeater Pump Failure Alarm state reading |
|
|
ERFailureAlarm |
N/a |
RO |
2001:3 |
BV19 |
N/a |
Exchanger Failure Alarm state reading |
|
|
HumidifierFailureAlarm |
N/a |
RO |
2001:4 |
BV20 |
N/a |
Humidifier Failure Alarm state reading |
|
|
TempSetpoint |
ºC |
RW |
1100 |
AV19 |
22 |
Room/Return Temperature setpoint |
|
|
HumiditySetpoint |
%RH |
RW |
1102 |
AV20 |
55 |
Room/Return Humidity setpoint |
|
|
CO2Setpoint |
ppm |
RW |
1104 |
AV21 |
600 |
Room/Return CO2 concentration setpoint |
|
|
DischargePressureSpt |
Pa |
RW |
1106 |
AV22 |
500 |
Discharge Fan Differential Pressure setpoint |
|
|
DischargePressureSpt |
Pa |
RW |
1108 |
AV23 |
500 |
Return Fan Differential Pressure setpoint |
|
|
HeaterMode |
N/a |
RW |
1200 |
AV24 |
2 |
Heater operating mode settings 1 – Water PreHeater as single Water Heater 2 – Water PreHeater & Water ReHeater use |
|
|
EnergyRecovMode |
N/a |
RW |
1202 |
AV25 |
1 |
Exchanger operating mode settings 0 – no exchanger 1 – Wheel exchanger 2 – CrossFlow exchanger 3 – Mixing Dampers as exchanger 4 – TwinCoil with Pump on Return 5 – TwinCoil with Pump on Discharge |
|
|
CoolerMode |
N/a |
RW |
1204 |
AV26 |
1 |
Cooler operating mode settings 0 – no cooler 1 – Water Cooler |
|
|
HumidifierMode |
N/a |
RW |
1206 |
AV27 |
1 |
Humidifier operating mode settings 0 – no humidifier 1 – Water humidifier 2 – Steam humidifier |
|
|
EconomizerMode |
N/a |
RW |
1208 |
AV28 |
1 |
Economizer operating mode settings 0 – no economizer function use 1 – Economizer function based on Return Air Temperature 2 – Economizer function based on Enthalpy |
|
|
TempCtrlMode |
N/a |
RW |
1210 |
AV29 |
1 |
Temperature control mode settings 1 – Cascade Temperature control 2 – Constant Discharge Temperature control 3 – Comfort Zone Temperature control |
|
|
HumCtrlMode |
N/a |
RW |
1212 |
AV30 |
1 |
Humidity control mode settings 1 – Comfort Humidity control 2 – Return Humidity control 3 – Discharge Absolute Humidity control 4 – Constant Discharge Absolute Humidity control |
|
|
CO2Range |
ppm |
RW |
1214 |
AV31 |
2000 |
CO2 concentration transmitter range |
|
|
DisPressRange |
Pa |
RW |
1216 |
AV32 |
1000 |
Discharge Differential Pressure transducer range |
|
|
RetPressRange |
Pa |
RW |
1218 |
AV33 |
1000 |
Return Differential Pressure transducer range |
|
|
PlantSchedule |
- |
RW |
1500 |
SCH0 |
N/a |
AHU Plant Schedule |
|
Network variables