iSMA-B-FCU-HH |
iSMA-B-FCU-HL
|
iSMA-B-FCU-LL |
||
|---|---|---|---|---|---|
|
Power Supply
|
Voltage |
230 V AC ± 10% |
24 V AC ± 10% |
||
|
Power consumption |
Max. 12 VA (including 7 VA for triac outputs) |
||||
|
Special Inputs
|
Temperature input |
Measurement with attached RTDS (Real Time Digital Simulator)
|
|||
|
Voltage input |
Voltage measurement from 0 to 10 V DC (input impedance 120 kΩ)
|
||||
|
Resistance input |
Resistance measurement from 0 to 700 kΩ
|
||||
|
Dry contact input |
Output current ~0.2 mA |
||||
|
Measurement resolution |
12 bits |
||||
|
Digital Inputs
|
Type |
Dry contact |
|||
|
Max. input frequency |
100 Hz |
||||
|
Analog Outputs
|
Voltage range |
0 to 10 V DC |
|||
|
Max. load current |
5 mA |
||||
|
Resolution |
12 bits |
||||
|
Accuracy |
±1% |
||||
|
Digital Outputs (Relays)
|
Resistive load (FAN, CLG) |
6 A at 230 V AC or 6 A at 30 V AC |
|||
|
Inductive load AC3 (FAN, CLG) |
75 VA at 230 V AC or 10 W at 30 V AC |
||||
|
Resistive load (HTG) |
10 A at 230 V AC or 10 A at 30 V AC |
||||
|
Inductive load AC3 (HTG) |
750 VA at 230 V AC |
||||
|
Triac Outputs
|
Load |
Min.: 1 mA
|
Min.: 1 mA
|
Min.: 1 mA
|
|
|
Peak load per channel |
1.5 A (30 s) |
||||
|
Gate control |
Zero crossing turn ON |
||||
|
Frequency range |
47 to 63 Hz |
||||
|
Snubber |
Snubberless triac |
||||
|
Power Supply Output |
Power supply output |
24 V AC ± 20%, 7 VA |
24 V AC ± 20%, 7 VA** In HL this power supply is also used for triac outputs |
||
|
COM1
|
RS485 interface |
Up to 128 devices
|
|||
|
Communication protocols |
Modbus RTU, Modbus ASCII or BACnet MS/TP set by switch |
||||
|
Ports |
Screw connector |
||||
|
Baud rate |
From 2400 to 115200 set by switch |
||||
|
Address |
0 to 255 set by DIP switch |
||||
|
COM2
|
RS485 interface |
Switch mode, up to 128 devices |
|||
|
Communication protocol |
Modbus RTU |
||||
|
Ports |
2 RJ12 ports |
||||
|
Baud rate |
From 2400 to 115200 |
||||
|
Power supply for external device |
34 V DC ± 15%, 2.5 W |
||||
|
USB1 |
USB |
Mini USB 2.0 |
|||
|
Ingress Protection |
IP |
IP40 for indoor installation |
|||
|
Temperature
|
Storage |
-40°C to +85°C (-40°F to +185°F) |
|||
|
Operating |
-10°C to +50°C (14°F to 122°F) |
||||
|
Humidity |
Relative |
5 to 95% |
|||
|
Connectors
|
Inputs/outputs, power supply, and communication |
Removable |
|||
|
HTG relay |
Constant |
||||
|
Maximum cable size |
2.5 mm2 |
||||
|
Dimensions
|
Width |
123.30 mm/4.85 in |
|||
|
Length |
136.60 mm/5.38 in |
||||
|
Height |
54.50 mm/2.15 in |
||||
Technical specification