Objects Adjustable Locally from the Room Panel

Room Panel Settings

Accessing any setting menu from the main menu level is possible if the room panel is in the active mode. The OK button together with the Menu button have to be pushed for a time longer than the time value stored in the ENTER_MENU_TIME object. The access to any settings menu is protected by a password stored in the PANEL_PASSWORD object (the default password is 1000).

The current settings menu name blinks on the 14-segment display block.

A different settings menu can be chosen by pushing up and down arrow buttons.

To enter the particular settings menu, push the OK button.

After entering the particular settings menu on the 14-segment display block, the number of the parameter with the lowest number is displayed.

Different available parameters inside the settings menu can be chosen by pushing up or down buttons.

All the parameters are described in more details in particular sections of this User Manual.

Configuration (CONF)

The configuration menu contains objects responsible for the configuration. The main part of all available objects refers to main communication objects such as a baud rate, an address, stop bits, parity bits, and protocol selection. From the configuration menu level the user can change the room panel password or read information about the implemented firmware version. All available parameters are listed in the table below:

Parameter Number

BACnet ID

Object Property

Object Name

Access

Description

1.1

Device

3084

BAUD_RATE

Read & Write Memory

48-1152 (*100kbs)


1.2

Device

3201

ADDRESS

Read & Write Memory

Default: 1

1.3

-

-

STOP_BITS

Read & Write Memory

1 – one stop bit

2 – two stop bits

1.4

-

-

PARITY_BITS

Read & Write Memory

0 – disabled

1 – ODD

2 - EVEN


1.5

-

-

PROTOCOL

Read & Write Memory

0 – Modbus RTU

1 – Modbus ASCII

2 – BACnet MS/TP

1.6

AO 0

Present Value

PANEL_PASSWORD

Read & Write Memory

Default: 1000

1.7

-

-

FIRMWARE_VERSION

Read Only

Software version

The CONF menu structure

Device (DEV)

The device settings menu contains objects responsible for global settings. Changing any of particular parameter has influence on different modes and functions implemented in the room panel. Some of the parameters refer to time settings such as the TIME_FORMAT, ENTER_MENU_TIME, EXIT_MENU_TIME, or REFRESH_TIME. In the device settings menu, the user can switch the beeper off, or disable background illumination in the LCD display or the keypad. All available parameters are listed in the table below:

Parameter Number

BACnet ID

Object Property

Object Name

Access

Description

2.1

BO 0

Present value

DEVICE CONFIGURATION

BEEPER

Read & Write Memory

0-inactive

1-active(def)

2.2

BO 1

Present value

DEVICE CONFIGURATION

TIME FORMAT

Read & Write Memory

0-24h(def)

1-12h

2.3

BO 2

Present value

DEVICE CONFIGURATION

TEMPERATURE UNIT

Read & Write Memory

Not supported

2.4

BO 3

Present value

DEVICE CONFIGURATION

BACKGROUND ILLUMINATION LCD ACTIVE

Read & Write Memory

0-inactive

1-active(def)

2.5

BO 4

Present value

DEVICE CONFIGURATION

BACKGROUND ILLUMINATION KEYPAD ACTIVE

Read & Write Memory

0-inactive(def)

1-active

2.6

AO16

Present value

ENTER MENU TIME

Read & Write Memory

Default value: 2 sec.

2.7

AO 17

Present value

EXITED IT TIME

Read & Write Memory

Default value: 5 sec.

2.8

AO 18

Present value

EXIT MENU TIME

Read & Write Memory

Default value: 10 sec.

2.9

AO 13

Present value

REFRESH TIME

Read & Write Memory

Default value: 2 sec.

The DEV monu structure

Temperature (TEMP)

The temperature settings menu contains objects referring to the temperature sensor display and temperature control settings. The user is able to switch on/off the temperature sensor value displaying, set the temperature sensor filter, or change the temperature sensor offset. All available parameters are listed in the table below:

Parameter Number

BACnet ID

Object Property

Object Name

Access

Description

3.1

AO 4

4200

TEMPERATURE_CONFIGURATION

ACTIVE

Read & Write Memory

0-inactive

1-active(def)

3.2

AO 4

4202

TEMPERATURE_ CONFIGURATION

THIRDPOINTACTIVE

Read & Write Memory

0-inactive

1-active(def)

3.3

AO 4

4003

TEMPERATURE_FILTER

Read & Write Memory

Default value: 60 sec

3.4

AO 4

4205

TEMPERATURE_OFFSET

Read & Write Memory

Default value: 0

The TEMP menu structure

Humidity (HUM)

The humidity settings menu contains objects referring to the humidity sensor display and humidity control settings. The user is able to switch on/off the humidity sensor value displaying, set the humidity sensor filter, or change the humidity sensor offset. All available parameters are listed in the table below:

Parameter Number

BACnet ID

Object Property

Object Name

Access

Description

4.1

AO 5

4200

HUMIDITY_CONFIGURATION

ACTIVE

Read &Write Memory

0-inactive

1-active(def)

4.2

AO 5

4202

HUMIDITY_CONFIGURATION

THIRDPOINTACTIVE

Read &Write Memory

0-inactive

1-active(def)

4.3

AO 5

4003

HUMIDITY_FILTER

Read &Write Memory

Default value: 60 sec

4.4

AO 5

4205

HUMIDITY_OFFSET

Read &Write Memory

Default value: 0

The HUM menu structure

CO2 (CO2)

The CO2 settings menu contains objects referring to the CO2 sensor display and CO2 control settings. The user is able to switch on/off the CO2 sensor value displaying, set the CO2 sensor filter, or change the CO2 sensor offset. All available parameters are listed in the table below:

Parameter Number

BACnet ID

Object Property

Object Name

Access

Description

5.1

AO 6

4200

CO2_CONFIGURATION

ACTIVE

Read & Write Memory

0-inactive

1-active(def)

5.2

AO 46

4003

CO2_FILTER

Read & Write Memory

Default value: 60 sec

5.3

AO 6

4205

CO2_OFFSET

Read & Write Memory

Default value: 0

 5.4

AO 19

Present value

CO2_SETPOINT

Read & Write Memory

Default value: 1500 ppm

Setpoint (SETP)

In the setpoint settings menu, the user has access to the main setpoint objects. It is possible to change the most useful setpoint parameters such as the default setpoint, a low and high setpoint limit, a setpoint step, or a offset range locally from the room panel. The user can also decide if the setpoint value should be displayed in the main menu, or if the setpoint or offset should be changed during the setpoint edition. All available parameters are listed in the table below:

Parameter Number

BACnet ID

Object Property

Object Name

Access

Description

6.1

AV 56

OUT OF SERVICE

SETPOINT_CONFIGURATION

ACTIVE

Read & Write Memory

0-inactive

1-active(def)

6.2

AV56

4200

SETPOINT_CONFIGURATION

EDITABLE

Read & Write Memory

0-inactive

1-active(def)

6.3

BO 55

Present value

SETPOINT_CONFIGURATION

OPERATING MODE

Read & Write Memory

0-changing offset

1-changing setpoint(def)

6.4

BO 56

Present value

SETPOINT_CONFIGURATION

SETPOINTDISPLAY

Read & Write Memory

0-changing offset

1-changing effective setpoint(def)

6.5

AV 56

4202

SETPOINT_CONFIGURATION

THIRDPOINT_ACTIVE

Read & Write Memory

0-inactive

1-active(def)

6.6

BO 57

Present value

SETPOINT_CONFIGURATION

FAST_EDIT_MODE

Read & Write Memory

0-inactive(def)

1-active

6.7

AV 57

Present value

DEFAULT_SETPOINT

Read & Write Memory

Default value: 210

6.8

AV 56

LOW LIMIT

SETPOINT_LOW_LIMIT

Read & Write Memory

Default value: 180

6.9

AV 56

HIGH LIMIT

SETPOINT_HIGH_LIMIT

Read & Write Memory

Default value: 240

6.10

AV 59

Present value

OFFSET_RANGE

Read & Write Memory

Default value: 30

6.11

AV 56

DEFAULT STEP INCREMENT

SETPOINT_STEP

Read & Write Memory

Default value: 10

The SETP menu structure

Fan (FAN)

The objects of the fan settings menu refer to fan configuration settings. The user can change the fan type or decide if the fan status should be displayed in the main menu or not. The editable parameter can determine if the user can change particular fan modes. All available parameters are listed in the table below:

Parameter Number

BACnet ID

Object Property

Object Name

Access

Description

 7.1

MV 1

OUT OF SERVICE

FAN_CONFIGURATION VISABLE_FAN_CURRENT_SPEED

Read & Write Memory

0-inactive

1-active(def)

7.2

MV 1

4200

FAN_CONFIGURATION

EDITABLE

Read & Write Memory

0-inactive

1-active(def)

7.3

BO 59

Present value

FAN_CONFIGURATION

PART_EDITABLE

Read & Write Memory

0-inactive(def)

1-active

7.4

BO 60

Present value

FAN_CONFIGURATION

FAST_EDIT_MODE

Read & Write Memory

0-inactive(def)

1-active

7.5

AO 21

Present value

FAN_ICON_FLASHING_TIME

Read & Write Memory

Default value: 500 ms

7.6

MV 2

1602

FAN_TYPE

Read & Write Memory

0-0-10 V(def)

1-1-Speed

2-2-Speed

3-3-Speed

The FAN menu structure

Occupancy (OCCU)

The occupancy settings menu contains objects referring to the occupancy configuration. The user can decide if the current occupancy status should be displayed in the main menu or not. The editable parameter can determine if the user can change the occupancy mode. All available parameters are listed in the table below:

Parameter Number

BACnet D

Object Property

Object Name

Access

Description

8.1

MV 4

OUT OF SERVICE

OCCUPANCY_CONFIGURATION

VISABLE_OCCUPANCY_CURRENT_STATUS

Read & Write Memory

0-inactive

1-active(def)

8.2

MV 4

4200

OCCUPANCY_CONFIGURATION

EDITABLE

Read & Write Memory

0-inactive

1-active(def)

8.3

BO 61

Present value

OCCUPANCY_CONFIGURATION

FAST_EDIT_MODE

Read & Write Memory

0-inactive(def)

1-active

The OCCU menu structure