Skip to main content
Skip table of contents

Modbus Settings

Setting Modbus Address

To determine the address on the Modbus network, the device has two rotary switches, S1 and S2, located on the top panel of the device.

It is possible to set the device address from 0 to 99.

The formula for setting the address is as follows:

Address = S2 10 + S1,

where S1 and S2 are values of switches.

For example:

Setting Modbus address with rotary switches

Switches set as in figure above will set the device address to 11.

Setting Baud Rate

Transmission baud rate is determined by the S3 DIP switch (sections 1, 2 and 3) in accordance with the following table:

1

2

3

Baud Rate

Off (0)

Off (0)

Off (0)

Defined by the user in the register

Off (0)

Off (0)

On (1)

76800

Off (0)

On (1)

Off (0)

4800

Off (0)

On (1)

On (1)

9600

On (1)

Off (0)

Off (0)

19200

On (1)

Off (0)

On (1)

38400

On (1)

On (1)

Off (0)

57600

On (1)

On (1)

On (1)

115200 (factory set)

Setting baud rate

Setting Protocol

Protocol selection is made by sections 4 and 5 of the S3 DIP switch according to the table:

4

5

Protocol

Off (0)

Off (0)

Modbus RTU

Off (0)

On (1)

Modbus ASCII

On (1)

Off (0)

N/A

On (1)

On (1)

N/A

Setting protocol

Free Modbus TCP Sockets Counter

Note:

The free Modbus TCP sockets counter is implemented from the 3.0 firmware.

The counter of free Modbus TCP sockets informs the user about the number of available Modbus TCP connections for the device.

The maximum number of TCP connections is 4.

The number of free Modbus TCP sockets can be reached in two ways:

  • in the 292 Modbus register (read-only): the register shows values from 0 to 4, where 0 means no available connections, 4 means 4 available connections;
  • in the IP Configuration tab in the web server.
JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.