Registered Access
|
Modbus Address |
Decimal Address |
Hex Address |
Register Name |
Access |
Description |
|---|---|---|---|---|---|
|
30001 |
0 |
0x00 |
Version/Type |
Read |
Version and type of the device |
|
30002 |
1 |
0x01 |
Switches |
Read |
Switches state |
|
40003 |
2 |
0x02 |
Baud Rate |
Read/write |
RS485 baud rate |
|
40004 |
3 |
0x03 |
Stop Bits & Data Bits |
Read/write |
No. of stop bits & data bits |
|
40005 |
4 |
0x04 |
Parity |
Read/write |
Parity bit |
|
40006 |
5 |
0x05 |
Response Delay |
Read/write |
Response delay in ms |
|
40007 |
6 |
0x06 |
Modbus Mode |
Read/write |
Modbus mode (ASCII or RTU) |
|
40010 |
9 |
0x09 |
Analog Filtering |
Read/write |
Analog filtering configuration |
|
40033 |
32 |
0x20 |
Received Packets LSR (Least Significant Register) |
Read/write |
No. of received packets |
|
40034 |
33 |
0x21 |
Received Packets MSR (Most Significant Register) |
Read/write |
|
|
40035 |
34 |
0x22 |
Incorrect Packets LSR |
Read/write |
No. of received packets with error
|
|
40036 |
35 |
0x23 |
Incorrect Packets MSR |
Read/write |
|
|
40037 |
36 |
0x24 |
Sent Packets LSR |
Read/write |
No. of sent packets
|
|
40038 |
37 |
0x25 |
Sent Packets MSR |
Read/write |
|
|
30051 |
50 |
0x32 |
Inputs |
Read |
Connected inputs
|
|
40052 |
51 |
0x33 |
Outputs |
Read/write |
Alarms state
|
|
30053 |
52 |
0x34 |
Analog 1 |
Read |
Value of Analog Input
|
|
30054 |
53 |
0x35 |
Analog 2 |
Read |
|
|
30055 |
54 |
0x36 |
Analog 3 |
Read |
|
|
30056 |
55 |
0x37 |
Analog 4 |
Read |
|
|
30057 |
56 |
0x38 |
Analog 5 |
Read |
|
|
30058 |
57 |
0x39 |
Analog 6 |
Read |
|
|
30059 |
58 |
0x3A |
Analog 7 |
Read |
|
|
30060 |
59 |
0x3B |
Analog 8 |
Read |
|
|
30061 |
60 |
0x3C |
Value of 1. Alarm Input |
Read |
Current values of voltage / current for alarm inputs |
|
30062 |
61 |
0x3D |
Value of 2. Alarm Input |
Read |
|
|
40063 |
62 |
0x3E |
MAX Alarm Level 1 |
Read/write |
If the analog signal exceeds this value the corresponding alarm flag is set |
|
40064 |
63 |
0x3F |
MAX Alarm Level 2 |
Read/write |
|
|
40065 |
64 |
0x40 |
MAX Alarm Level 3 |
Read/write |
|
|
40066 |
65 |
0x41 |
MAX Alarm Level 4 |
Read/write |
|
|
40067 |
66 |
0x42 |
MAX Alarm Level 5 |
Read/write |
|
|
40068 |
67 |
0x43 |
MAX Alarm Level 6 |
Read/write |
|
|
40069 |
68 |
0x44 |
MAX Alarm Level 7 |
Read/write |
|
|
40070 |
69 |
0x45 |
MAX Alarm Level 8 |
Read/write |
|
|
40071 |
70 |
0x46 |
MIN Alarm Level 1 |
Read/write |
If the analog signal is below this value corresponding alarm flag is set |
|
40072 |
71 |
0x47 |
MIN Alarm Level 2 |
Read/write |
|
|
40073 |
72 |
0x48 |
MIN Alarm Level 3 |
Read/write |
|
|
40074 |
73 |
0x49 |
MIN Alarm Level 4 |
Read/write |
|
|
40075 |
74 |
0x4A |
MIN Alarm Level 5 |
Read/write |
|
|
40076 |
75 |
0x4B |
MIN Alarm Level 6 |
Read/write |
|
|
40077 |
76 |
0x4C |
MIN Alarm Level 7 |
Read/write |
|
|
40078 |
77 |
0x4D |
MIN Alarm Level 8 |
Read/write |
|
|
40079 |
78 |
0x4E |
Alarm Settings 1 |
Read/write |
Alarm settings
|
|
40080 |
79 |
0x4F |
Alarm Settings 2 |
Read/write |
|
|
40081 |
80 |
0x50 |
Alarm Settings 3 |
Read/write |
|
|
40082 |
81 |
0x51 |
Alarm Settings 4 |
Read/write |
|
|
40083 |
82 |
0x52 |
Alarm Settings 5 |
Read/write |
|
|
40084 |
83 |
0x53 |
Alarm Settings 6 |
Read/write |
|
|
40085 |
84 |
0x54 |
Alarm Settings 7 |
Read/write |
|
|
40086 |
85 |
0x55 |
Alarm Settings 8 |
Read/write |
|
|
40087 |
86 |
0x56 |
Input 1 settings |
Read/write |
Analog input mode:
|
|
40088 |
87 |
0x57 |
Input 2 settings |
Read/write |
|
|
40089 |
88 |
0x58 |
Input 3 settings |
Read/write |
|
|
40090 |
89 |
0x59 |
Input 4 settings |
Read/write |
|
|
40091 |
90 |
0x5A |
Input 5 settings |
Read/write |
|
|
40092 |
91 |
0x5B |
Input 6 settings |
Read/write |
|
|
40093 |
92 |
0x5C |
Input 7 settings |
Read/write |
|
|
40094 |
93 |
0x5D |
Input 8 settings |
Read/write |
|
|
40095 |
94 |
0x5E |
Output 1 settings |
Read/write |
Alarm output settings
|
|
40096 |
95 |
0x5F |
Output 2 settings |
Read/write |
|
|
40097 |
96 |
0x60 |
Alarm Value 1 |
Read/write |
Alarm value for outputs |
|
40098 |
97 |
0x61 |
Alarm Value 2 |
Read/write |
|
|
40099 |
98 |
0x62 |
Alarm Hysteresis 1 |
Read/write |
The hysteresis value for alarm outputs |
|
40100 |
99 |
0x63 |
Alarm Hysteresis 2 |
Read/write |
Registered access
Bit Access
|
Modbus Address |
Dec Address |
Hex
|
Register Name |
Access |
Description |
|---|---|---|---|---|---|
|
801 |
800 |
0x320 |
Input 1 |
Read |
Set when the input is connected |
|
802 |
801 |
0x321 |
Input 2 |
Read |
Set when the input is connected |
|
803 |
802 |
0x322 |
Input 3 |
Read |
Set when the input is connected |
|
804 |
803 |
0x323 |
Input 4 |
Read |
Set when the input is connected |
|
805 |
804 |
0x324 |
Input 5 |
Read |
Set when the input is connected |
|
806 |
805 |
0x325 |
Input 6 |
Read |
Set when the input is connected |
|
807 |
806 |
0x326 |
Input 7 |
Read |
Set when the input is connected |
|
808 |
807 |
0x327 |
Input 8 |
Read |
Set when the input is connected |
|
817 |
816 |
0x330 |
Alarm 1 |
Read |
Alarm state 1 |
|
818 |
817 |
0x331 |
Alarm 2 |
Read |
Alarm state 2 |
|
819 |
818 |
0x332 |
Alarm 3 |
Read |
Alarm state 3 |
|
820 |
819 |
0x333 |
Alarm 4 |
Read |
Alarm state 4 |
|
821 |
820 |
0x334 |
Alarm 5 |
Read |
Alarm state 5 |
|
822 |
821 |
0x335 |
Alarm 6 |
Read |
Alarm state 6 |
|
823 |
822 |
0x336 |
Alarm 7 |
Read |
Alarm state 7 |
|
824 |
823 |
0x337 |
Alarm 8 |
Read |
Alarm state 8 |
|
825 |
824 |
0x338 |
Digital Output 1 |
Read/write |
State of digital output 1 |
|
826 |
825 |
0x339 |
Digital Output 1 |
Read/write |
State of digital output 2 |
Bit access