Default Settings
If the device is used for the first time or the default settings have just been restored, the following default settings are active:
Communication | ||
---|---|---|
Register | Number | Default Value |
BAUD RATE | 40017 | 76800 |
STOP BITS | 40018 | 1 |
DATA BITS | 40019 | 8 |
PARITY BITS | 40020 | 0 |
REPLY DELAY | 40021 | 0 |
COUNTERS | 30004-30012 | 0 |
I/O | ||
DI BLOCKING | 40102 | 0 (UNBLOCKED) |
DI DIMMING OFF | 40254-40255 bit 4 | 0 (ON) |
SI PIR TYPE | 40103-40104 | 6 (NC) |
SI DELAY OFF TIME | 40107-40108 | 300 |
SI BLOCKING | 40254-40255 bit 3 | 0 (UNBLOCKED) |
DALI1 + DALI2 | ||
ON OFF STATE | 40253 (40254 bit 0) | 0 |
COUNTERS | 30229-30247 | 0 |
DIMMING STATE | 40266-40267 | 0 |
FADE RATE | 40462-40463 | 7 |
FADE TIME | 40466-40467 | 0 |
POWER ON LEVEL | 40470-40471 | 254 |
SYSTEM FAILURE LEVEL | 40474-40475 | 254 |
BALLASTS SETPOINT | 40270-40301 | 254 |
BALLASTS MIN | 40334-40365 | 0 |
BALLASTS MAX | 40398-40429 | 254 |
NUMBER OF BALLASTS | 30258-30259 | 0 |
LLC | ||
LLC SETPOINT ZONE 1 | 40489 | 1000 lx |
LLC SETPOINT ZONE 2 | 40490 | 1000 lx |
LLC ZONE COUNT | 40493 | 2 |
LUX MIN SENSOR 1 | 40494 | 0 lx |
LUX MIN SENSOR 2 | 40495 | 0 lx |
LUX MAX SENSOR 1 | 40498 | 3000 lx |
LUX MAX SENSOR 2 | 40499 | 3000 lx |
LLC OFFSET | 40478 | 0 |
LUX SENSOR TYPE 1 | 40502 | 0 (0-10 V) |
LUX SENSOR TYPE 2 | 40503 | 0 (0-10 V) |
LUX SENSOR ENABLE | 40506 | 3 (BOTH ENABLED) |
LLC PIR 1 DIMM TIME | 40485 | 0 s |
LLC PIR 2 DIMM TIME | 40486 | 0 s |
LLC PIR 1 DIMM LEVEL | 40481 | 20 % |
LLC PIR 2 DIMM LEVEL | 40482 | 20 % |
LLC KP ZONE 1 | 40507 | 0,021 |
LLC KP ZONE 2 | 40509 | 0,021 |
LLC KI ZONE 1 | 40515 | 0,007 |
LLC KI ZONE 2 | 40517 | 0,007 |
LLC KD ZONE 1 | 40523 | 0,012 |
LLC KD ZONE 2 | 40525 | 0,012 |
Restoring Default Settings
WARNING! Be careful with using this function! All registers are set back to their default settings, including I/O, DALI interfaces, and communication parameters!
To restore the default device settings, please follow the steps below:
- Turn off the power supply.
- Set section 6 of the PROTOCOL DIP switch to the ON
- Turn on the power supply, wait until the power LED is blinking.
- Switch section 6 of the PROTOCOL DIP switch to the OFF position to restore the default settings. To cancel the reset procedure, turn off the power and switch section 6 of the PROTOCOL DIP switch to the OFF position.