If the device is used for the first time or the default settings have just been restored, the following default settings are active:
|
Communication |
||
|---|---|---|
|
Register |
Number |
Default Value |
|
BAUD RATE |
40017 |
76800 |
|
STOP BITS |
40018 |
1 |
|
DATA BITS |
40019 |
8 |
|
PARITY BITS |
40020 |
0 |
|
REPLY DELAY |
40021 |
0 |
|
COUNTERS |
30004-30012 |
0 |
|
I/O |
||
|
DI BLOCKING |
40102 |
0 (UNBLOCKED) |
|
DI DIMMING OFF |
40254-40255 bit 4 |
0 (ON) |
|
SI PIR TYPE |
40103-40104 |
6 (NC) |
|
SI DELAY OFF TIME |
40107-40108 |
300 |
|
SI BLOCKING |
40254-40255 bit 3 |
0 (UNBLOCKED) |
|
DALI1 + DALI2 |
||
|
ON OFF STATE |
40253 (40254 bit 0) |
0 |
|
COUNTERS |
30229-30247 |
0 |
|
DIMMING STATE |
40266-40267 |
0 |
|
FADE RATE |
40462-40463 |
7 |
|
FADE TIME |
40466-40467 |
0 |
|
POWER ON LEVEL |
40470-40471 |
254 |
|
SYSTEM FAILURE LEVEL |
40474-40475 |
254 |
|
BALLASTS SETPOINT |
40270-40301 |
254 |
|
BALLASTS MIN |
40334-40365 |
0 |
|
BALLASTS MAX |
40398-40429 |
254 |
|
NUMBER OF BALLASTS |
30258-30259 |
0 |
|
LLC |
||
|
LLC SETPOINT ZONE 1 |
40489 |
1000 lx |
|
LLC SETPOINT ZONE 2 |
40490 |
1000 lx |
|
LLC ZONE COUNT |
40493 |
2 |
|
LUX MIN SENSOR 1 |
40494 |
0 lx |
|
LUX MIN SENSOR 2 |
40495 |
0 lx |
|
LUX MAX SENSOR 1 |
40498 |
3000 lx |
|
LUX MAX SENSOR 2 |
40499 |
3000 lx |
|
LLC OFFSET |
40478 |
0 |
|
LUX SENSOR TYPE 1 |
40502 |
0 (0-10 V) |
|
LUX SENSOR TYPE 2 |
40503 |
0 (0-10 V) |
|
LUX SENSOR ENABLE |
40506 |
3 (BOTH ENABLED) |
|
LLC PIR 1 DIMM TIME |
40485 |
0 s |
|
LLC PIR 2 DIMM TIME |
40486 |
0 s |
|
LLC PIR 1 DIMM LEVEL |
40481 |
20 % |
|
LLC PIR 2 DIMM LEVEL |
40482 |
20 % |
|
LLC KP ZONE 1 |
40507 |
0,021 |
|
LLC KP ZONE 2 |
40509 |
0,021 |
|
LLC KI ZONE 1 |
40515 |
0,007 |
|
LLC KI ZONE 2 |
40517 |
0,007 |
|
LLC KD ZONE 1 |
40523 |
0,012 |
|
LLC KD ZONE 2 |
40525 |
0,012 |
Default values
Restoring Default Settings
WARNING! Be careful with using this function! All registers are set back to their default settings, including I/O, DALI interfaces, and communication parameters!
To restore the default device settings, please follow the steps below:
-
Turn off the power supply.
-
Set section 6 of the PROTOCOL DIP switch to the ON
-
Turn on the power supply, wait until the power LED is blinking.
-
Switch section 6 of the PROTOCOL DIP switch to the OFF position to restore the default settings. To cancel the reset procedure, turn off the power and switch section 6 of the PROTOCOL DIP switch to the OFF position.
DIP switch for restoring default settings