Mounting and Installation

The VAV14-IP controller is mounted directly on an air duct or in a panel with access to a damper shaft.

The VAV14-IP controller is delivered ready for mounting:

  • calibrated to 95°,

  • with sheet-metal tapping screw (fi 4.2 mm L 13 mm), slotted hexagon head,

  • with bearing bushes with flange fi 5 mm (inner) fi 6 mm (outer), L 35 mm,

  • and with pressure hose fi 7 mm (outer), L 1 m.

Mounting Orientation

To prevent condensation that might occur on damper shaft and get into the controller's housing, VAV14-IP should be installed in any position above the damper shaft level (from 0° to 180°).

Working positions.png
VAV14-IP controller’s recommended mounting orientation

Installation Steps

Tools for installation:

  • 8 mm wrench,

  • screwdriver.

1. Loosen the U-bracket

First, loosen the U-bracket installed around a hole for a damper shaft. The U-bracket is tightened with 2 M5 hexagon flange nuts.

Loosen u-brakcet.png


2. Mount the VAV14-IP controller

When the U-bracket is loosened, mount the VAV14-IP controller onto the damper shaft bearing in mind the recommended working orientation of the controller.

General.png

Please note that the minimum required length of the damper shaft for a proper mounting of the VAV14-IP controller is 40 mm/1.5 in.


3. Tighten the U-bracket

Use the wrench to re-tighten the U-bracket around the damper shaft.

Tighten U-bracket.png


4. Tighten the mounting screw

Lastly, use the screwdriver to tighten the mounting screw on the side of the controller opposite to the damper shaft.

Screw tightening.png