Skip to main content
Skip table of contents

List of Modbus Registers

Warning!

Please note that the following table contains registers for all series of the Touch Point panels.

The Touch Point VAV series by default has no fan control and registers referring to fan control are inapplicable. If the fan control is activated on the Touch Point VAV series panel, the registers become applicable too.

Registers referring to the fan control, occupancy, and setpoints control are inapplicable to the Touch Point Network Sensor series.

Modbus Address

Decimal Address

Hex

Register Name

Access

Default Value

Value Range

Description

40001

0

0x00

VERSION_TYPE

Read/write

Shows a firmware version and type of the panel and enables 1 of 4 available actions (reset device, reload settings, reset settings, enter bootloader)

30002

1

0x01

ADDRESS_ROTARY_SWITCH

Read-only

0-9

Address set on a rotary switch

30003

2

0x02

PROTOCOL_DIPSWITCH

Read-only

0-1

Protocol set on a DIP switch

30004

3

0x03

RECEIVED_FRAMES_COUNTER

Read-only

0

The number of received Modbus frames reset at the start of the panel and at the change of transmission parameters

30006

5

0x05

ERROR_FRAMES_COUNTER

Read-only

0

The number of received error Modbus frames reset at the start of the panel and at the change of transmission parameters

30008

7

0x07

TRANSMITTED_FRAME_COUNTER

Read-only

0

The number of transmitted Modbus frames reset at the start of the panel and at the change of transmission parameters

30012

11

0x0B

LIVE_TIME

Read-only

Uptime of the panel in seconds

40015

14

0x0E

BACNET_DEVICE_ID

Read/write

0xFFFFFFFF

Device's BACnet ID

40017

16

0x10

BAUD_RATE

Read/write

11520

Sets the baud rate

40018

17

0x11

STOP_BITS

Read/write

1

1-2

Sets the number of stop bits

40019

18

0x12

DATA_BITS

Read/write

8

7-8

Sets the number of data bits (Modbus ASCII requires 7 bits)

40020

19

0x13

PARITY_BIT

Read/write

0

0-2

Determines the parity bit

40021

20

0x14

REPLY_DELAY

Read/write

0

Sets the delay time in ms before sending response

40023

22

0x16

ADDRESS

Read/write

1

Modbus address of the device

40024

23

0x17

PROTOCOL

Read/write

0

0-2

Sets the type of Modbus protocol (Modbus RTU (0), Modbus ASCII (1))

30029

28

0x1C

SENSORS

Read-only

Informs about built-in sensors

30201

200

0xC8

BACKLIGHT_LCD

Read-only

Actual display illumination value

30202

201

0xC9

BACKLIGHT_KEYPAD

Read-only

Actual keypad illumination value

40205

204

0xCC

DEVICE_CONFIGURATION

Read/write

105

Bit

Name

0

1

0

BUZZER

Not active

Active (def)

Activates/inactivates a buzzer

3

BACKLIGHT_LCD

Not active

Active (def)

Switches on/off display's backlight

4

BACKLIGHT_KEYPAD

Not active

Active (def)

Switches on/off keypad's backlight

5

CO2_ALARM_LCD

Not active

Active

Shows CO2 alarm on a display

6

CO2_ALARM_BUZZER

Not active

Active

Switches on/off CO2 alarm's buzzer on alarm

8

CO2_ALARM_CONFIRM

Not active

Active (def)

Switches on/off CO2 alarm confirmation by any button

11

PANEL_OFF

Panel on (def)

Panel off

Switches on/off the panel

12

KEYPAD_OFF

Keypad on (def)

Keypad off

Switches on/off the keypad

40207

206

0xCE

BACKLIGHT_LCD_ACTIVE

Read/write

60

Contains a value of the LCD display illumination in the active mode (expressed in %)

40208

207

0xCF

BACKLIGHT_LCD_IDLE

Read/write

40

Contains a value of the LCD display illumination in the idle mode (expressed in %)

40209

208

0xD0

BACKLIGHT_LCD_STANDBY

Read/write

0

Contains a value of the LCD display illumination in the standby mode (expressed in %)

40210

209

0xD1

BACKLIGHT_LCD_TIME_TO_IDLE

Read/write

10

Sets the time, after which the LCD display goes from the active mode to idle (expressed in seconds)

40211

210

0xD2

BACKLIGHT_LCD_TIME_TO_STANDBY

Read/write

5

Sets the time, after which the LCD display goes from the idle mode to standby (expressed in seconds)

40212

211

0xD3

BACKLIGHT_KEYPAD_ACTIVE

Read/write

10

Contains a value of the keypad illumination in the active mode (expressed in %)

40213

212

0xD4

BACKLIGHT_KEYPAD_IDLE

Read/write

40

Contains a value of the keypad illumination in the idle mode (expressed in %)

40214

213

0xD5

BACKLIGHT_KEYPAD_STANDBY

Read/write

60

Contains a value of the keypad illumination in the standby mode (expressed in %)

40215

214

0xD6

BACKLIGHT_KEYPAD_TIME_TO_IDLE

Read/write

10

Sets the time, after which the keypad goes from the active mode to idle (expressed in seconds)

40216

215

0xD7

BACKLIGHT_KEYPAD_TIME_TO_STANDBY

Read/write

5

Sets the time, after which the keypad goes from the idle mode to standby (expressed in seconds)

40217

216

0xD8

REFRESH_TIME

5

1-60

Sets the duration of the display time of particular parameters

40219

218

0xDA

ICON_DISPLAY

Read/write

Bit

Name

0

1

8

ECO

Not active

Active

Switches on/off an ECO LED

40226

225

0xE1

CO2_SETPOINT_FOR_ALARM

Read/write

1500

CO2 alarm setpoint

40227

226

0xE2

CO2_HYSTERESIS_FOR_ALARM

Read/write

100

CO2 alarm hysteresis

30230

229

0xE5

ALARM_STATUS

Read-only

CO2 current alarm status

30231

230

0xE6

NAVIGATIONAL_LED_MODE

Read/write

1

0-4

Sets a mode of the navigational LED

Bit

Name

0

1

0

OFF

Not active

Active

1

ON (default)

Not active

Active

2

Active on IDLE and STANDBY

Not active

Active

3

Active on IDLE only

Not active

Active

4

Active on STANDBY only

Not active

Active

30232

231

0xE7

NAVIGATIONAL_LED_BRIGHTNESS

Read/write

100

0-100

Navigational LED brightness

30233

232

0xE8

NAVIGATIONAL_LED_RED

Read/write

100

0-100

Navigational LED color - red component intensity

30234

233

0xE9

NAVIGATIONAL_LED_GREEN

Read/write

100

0-100

Navigational LED color - green component intensity

30235

234

0xE10

NAVIGATIONAL_LED_BLUE

Read/write

100

0-100

Navigational LED color - blue component intensity

30301

300

0x12C

TEMPERATURE_SENSOR

Read-only

Actual temperature sensor value with offset

30302

301

0x12D

HUMIDITY_SENSOR

Read-only

Actual humidity sensor value with offset

30303

302

0x12E

CO2_SENSOR

Read-only

Actual CO2 sensor value with offset

40304

303

0x12F

TEMPERATURE_SENSOR_OFFSET

Read/write

0

Temperature sensor offset

40305

304

0x130

HUMIDITY_SENSOR_OFFSET

Read/write

0

Humidity sensor offset

40306

305

0x131

CO2_SENSOR_OFFSET

Read/write

0

CO2 sensor offset

40307

306

0x132

TEMPERATURE_FILTER

Read/write

60

Filtering time for the temperature sensor (seconds)

40308

307

0x133

HUMIDITY_FILTER

Read/write

60

Filtering time for the humidity sensor (seconds)

40309

308

0x134

CO2_FILTER

Read/write

60

Filtering time for the CO2 sensor (seconds)

40316

315

0x13B

TEMPERATURE_CONFIGURATION

Read/write

17

Bit

Name

0

1

0

ACTIVE

Not active

Active (def)

Activates/deactivates the sensor

4

THIRD_POINT-ACTIVE

No decimal

Decimal (def)

Sets decimal places

40317

316

0x13C

HUMIDITY_CONFIGURATION

Read/write

17

Bit

Name

0

1

0

ACTIVE

Not active

Active (def)

Activates/deactivates the sensor

4

THIRD_POINT-ACTIVE

No decimal

Decimal (def)

Sets decimal places

40318

317

0x13D

CO2_CONFIGURATION

Read/write

1

Bit

Name

0

1

0

ACTIVE

Not active

Active

Activates/deactivates the sensor

40323

322

0x142

BUZZER_VOLUME

Read/write

50

0-100

Buzzer volume (%)

40324

323

0x143

BUZZER_FREQUENCY

Read/write

400

20-20000

Buzzer frequency (Hz)

31301

1300

0x514

FLASH_DEVICE_TYPE

Read-only

Version and type of device

31302

1301

0x515

FLASH_HW_VERSION

Read-only

HW version

31303

1302

0x516

FLASH_BOOT_VERSION

Read-only

Bootloader version

31304

1303

0x517

FW_VERSION

Read-only

FW version separated from the VERSION_TYPE register

31305

1304

0x518

FLASH_SERIAL_NUMBER_1

Read-only

Serial number

31306

1305

0x519

FLASH_SERIAL_NUMBER_2

Read-only

Serial number

31307

1306

0x51A

FLASH_SERIAL_NUMBER_3

Read-only

Serial number

31308

1307

0x51B

FLASH_SERIAL_NUMBER_4

Read-only

Serial number

41501

1500

0x5DC

SETPOINT_VALUE

Read/write

0-500

Temperature setpoint value

41502

1501

0x5DD

EFFECTIVE_SETPOINT

Read-only

Sum of setpoint and offset values

41503

1502

0x5DE

DEFAULT_SETPOINT

Read/write

210

0-500

Default temperature setpoint

41504

1503

0x5DF

OFFSET_SETPOINT

Read/write

0

0-500

Temperature offset for setpoint

41505

1504

0x5E0

SETPOINT_LOW_LIMIT

Read/write

180

Min. available setpoint value

41506

1505

0x5E1

SETPOINT_HIGH_LIMIT

Read/write

240

Max. available setpoint value

41507

1506

0x5E2

OFFSET_RANGE

Read/write

30

0-500

Limit offset value

41508

1507

0x5E3

SETPOINT_STEP

Read/write

10

Setpoint step value

41513

1512

0x5E8

SETPOINT_CONFIGURATION

Read/write

31

Setpoint configuration of parameters: Visible, Editable, Operating mode, Setpoint display, ThirdPointActive

Bit

Name

0

1

0

VISIBLE

Not visible

Visible (def)

Switches on/off a temperature setpoint visibility on a display

1

EDITABLE

Not editable

Editable (def)

Activates/inactivates editing of a temperature setpoint locally on the panel

2

OPERATING_MODE

Changing offset

Changing setpoint (def)

Switches between changing offset or setpoint

3

SETPOINT_DISPLAY

Show/change offset

Show/change effective setpoint (def)

Switches between changing offset or setpoint

4

THIRD_POINT_ACTIVE

No decimal

Decimal (def)

Activates/inactivates decimal points

41601

1600

0x640

FAN_CURRENT_SPEED

Read/write

0

Not available for the Touch Point VAV series.

Fan speed

41602

1601

0x641

FAN_MODE

Read/write

1

Not available for the Touch Point VAV series.

Fan mode

41603

1602

0x642

FAN_TYPE

Read/write

Not available for the Touch Point VAV series.

Fan type

41614

1613

0x64D

FAN_CONFIGURATION

Read/write

2

Not available for the Touch Point VAV series.

Bit

Name

0

1

1

EDITABLE

Not editable

Editable (def)

Switches on/off editing fan modes locally

2

PART_EDITABLE

Fully editable

Auto_Off_Mode

Switches editability of fan modes

6

FAN_CONFIG_LOCAL_MODE

BMS (def)

Local

Switches between BMS/local modes

41701

1700

0x6A4

OCCUPANCY_CURRENT_STATUS

Read/write

Occupancy status

41702

1701

0x6A5

OCCUPANCY_MODE

Read/write

Occupancy mode

41707

1706

0x6AA

OCCUPANCY_CONFIGURATION

Read/write

2

Bit

Name

0

1

1

EDITABLE

Not editable

Editable (def)

Switches on/off editing occupancy statues locally

6

OCCUPIED_CONFIG_LOCAL_MODE

BMS (def)

Local

Switches between BMS/local modes

List of Modbus registers

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.